Plan Review Details - Permit 08040169
Plan Review Stops For Permit 08040169
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-04-12 Cont ID  
Sent By mjacobs Date 2008-04-12 Time 15:08 Rev Time 0.00
Received By mjacobs Date 2008-04-12 Time 13:47 Sent To  
Notes
2008-04-12 14:41:07PROVISO:
 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PAINT ON DRYWALL DOES NOT MEET THIS
 REQUIREMENT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 11:09 Sent To  
Notes
2008-04-10 11:09:15ADDRESS ON ELECTRICAL PLANS NOT CORRECT REDLINED
 CONGRESS AVE ON TITLE BLOCKS.
 ADDRESSIS NOT 45TH ST.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 12:59 Rev Time 0.00
Received By mwennerg Date 2008-04-18 Time 12:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 12:59 Rev Time 0.00
Received By mwennerg Date 2008-04-08 Time 08:25 Sent To  
Notes
2008-04-08 08:25:46TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 11:26 Rev Time 0.30
Received By tgordon Date 2008-04-10 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-15 Cont ID  
Sent By mperson Date 2008-04-15 Time 15:30 Rev Time 0.00
Received By mperson Date 2008-04-15 Time 15:30 Sent To  
Notes
2008-04-15 15:31:53******PROVISO******
 SHEET A.0:
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-08 Cont ID  
Sent By choops Date 2008-04-08 Time 08:40 Rev Time 0.00
Received By choops Date 2008-04-08 Time 08:40 Sent To  
Notes
2008-04-08 08:40:58*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.