Plan Review Details - Permit 08040161
Plan Review Stops For Permit 08040161
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-10 Cont ID  
Sent By btrobaug Date 2008-06-10 Time 11:17 Rev Time 0.00
Received By btrobaug Date 2008-06-10 Time 11:13 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-23 Cont ID  
Sent By btrobaug Date 2008-04-23 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2008-04-23 Time 15:06 Sent To FIRE
Notes
2008-04-23 15:13:36 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 PER 105.3.1.2(5).FBC AS AMENDED: ANY SPECIALIZED
 MECHANICAL, ELECTRICAL, OR PLUMBING DOCUMENT FOR ANY
 NEW BUILDING OR ADDITION WHICH INCLUDES A MEDICAL GAS,
 OXYGEN, STEAM, VACUUM, TOXIC AIR FILTRATION, HALON, OR
 FIRE DETECTION AND ALARM SYSTEM WHICH COSTS MORE THAN
 $5,000.MUST BE PREPARED BY AN ENGINEER REGISTERED UNDER
 471 FS.
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2008-04-08 11:02:49 
  
  
 SENT TO FIRE./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-10 Cont ID  
Sent By mwennerg Date 2008-06-10 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2008-06-10 Time 14:33 Sent To  
Notes
2008-06-10 14:35:02***PROVISO***
  
 1) WORK TO COMPLY WITH NFPA 101, 2003 EDITION SECTIONS
 7.2.1.6.1 AND 7.2.1.6.2 FOR ACCESS CONTROL SYSTEMS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By mwennerg Date 2008-04-25 Time 09:53 Rev Time 0.00
Received By mwennerg Date 2008-04-25 Time 09:53 Sent To  
Notes
2008-04-25 10:08:29***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT REGARDING FBC
 REQUIREMENTS FOR DRAWINGS.
  
 2) WORK TO COMPLY WITH NFPA 101, 2003 EDITION SECTIONS
 7.2.1.6.1 AND 7.2.1.6.2 FOR ACCESS CONTROL SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 09:45 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 09:45 Sent To E
Notes
2008-06-04 09:45:37TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-25 Cont ID  
Sent By mwennerg Date 2008-04-25 Time 10:14 Rev Time 0.00
Received By mwennerg Date 2008-04-07 Time 13:27 Sent To  
Notes
2008-04-07 13:27:51TO "E" BOX