Plan Review Details - Permit 08040140
Plan Review Stops For Permit 08040140
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-14 Cont ID  
Sent By shill Date 2008-04-14 Time 09:47 Rev Time  
Received By shill Date 2008-04-11 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By shill Date 2008-04-09 Time 13:08 Rev Time  
Received By shill Date 2008-04-07 Time 12:57 Sent To  
Notes
2008-04-09 13:21:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
 INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE
 MITIGATION.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____4.)FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 GRAPHICS AND LANGUAGE WERE PROVIDED, BUT ARE CONFUSING.
 IT APPEARS THAT THE CONTRACTOR HAS DRAWN A SHEET OF 4X8
 INSULATION, THEN DRAWN FASTENERS ALONG THE EDGE AS IF
 IT WERE BEING FASTENED LIKE A BASE SHEET BUT REFERED TO
 ZONES AS THE DRAWING WAS A ROOF.FOR INSTANCE, THE
 CORNER OF THE INSULATION BOARD IS SHOWN AS HAVING 4INCH
 SPACING ON FASTENERS, EDGE HAVING 6INCH AND IT REFERS
 TO THESE AREAS AS "CORNERS" AND "PERIMETERS".YOU ARE
 CONFUSING THREE DIFFERENT SCENARIOS/CONDITIONS; BASE
 SHEET FASTENING, INSULATION BOARD FASTENING, AND ROOF
 COMPONENT AND CLADDING ZONE, AND HAVE COMBINED THEM TO
 SUBMIT A CONVOLUTED FASTENING PATTERN WHICH CANNOT BE
 IMPLEMENTED IN THE FIELD.
  
 THE LANGUAGE ON THE ASSEMBLY STATES THAT THERE WILL BE
 72 FASTENERS PER BOARD.PLEASE INDICATE WHICH OF THE
 FASTENING OPTIONS YOU ARE USING (THERE ARE THREE
 DIFFERENT ONES FOR THIS ASSEMBLY), AND NOTE THAT THE
 INSULATION GETS FASTENED THROUGH THE BASE SHEET BUT THE
 FASTENING IS DETERMINED BY THE EDGE OF THE BASE SHEET,
 NOT THE EDGE OF THE INSULATION.PLEASE DISCARD THE
 PLAN OF FASTENING AND PROVIDE LANGUAGE CONSISTENT WITH
 THE PRODUCT APPROVAL - STATE FASTENER SPACING, NUMBER
 OF ROWS.PLEASE BE CLEAR AS TO WHETHER OR NOT THE
 NUMBER OF ROWS INCLUDES THE LAP ROW OR IF THE NUMBER OF
 ROWS SPECIFIED ARE FOR THE FIELD ROWS.
  
 PLEASE HAVE THE QUALIFIER FOR THE COMPANY REVIEW THE
 ENHANCED FASTENING PATTERN BEFORE RESUBMITTAL.
  
 TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS REQUIRED
 FOR ISSUANCE.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-04-04 Cont ID  
Sent By ssherman Date 2008-04-04 Time 14:59 Rev Time 0.00
Received By ssherman Date 2008-04-04 Time 14:59 Sent To  
Notes
2008-04-04 15:00:19HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 08:32 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 08:32 Sent To B
Notes
2008-04-11 08:32:45TO "SHILL" DESK/RESUB