Plan Review Details - Permit 08040139
Plan Review Stops For Permit 08040139
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-28 Cont ID  
Sent By shill Date 2008-05-28 Time 17:51 Rev Time 0.00
Received By shill Date 2008-05-28 Time 17:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-15 Cont ID  
Sent By shill Date 2008-05-15 Time 09:51 Rev Time 0.00
Received By shill Date 2008-05-15 Time 09:51 Sent To  
Notes
2008-05-15 10:01:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE ENGINEERING FOR THE PREFAB SLAB IS TO BE SIGNED
 AND DATED AS WELL AS SEALED.SEE FAC61G15-23.002,
 FS471.
  
 2.A (GAS) LICENSE AS DEFINED IN FS527.01 IS REQUIRED
 FOR INSTALLATION OF A GAS GENERATOR.PLEASE REVISE
 PERMIT APPLICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By shill Date 2008-04-21 Time 08:07 Rev Time 0.00
Received By shill Date 2008-04-21 Time 08:07 Sent To  
Notes
2008-04-21 08:08:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ORIGINAL ENGINEERING FOR A PREFAB SLAB IS REQUIRED.
 ONE SHEET IS NOT SIGNED, SEALED AND DATED; THE OTHER
 SHEET HAS A PHOTOCOPY SIGNATURE.SEE FAC61G15-23.002.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By btrobaug Date 2008-04-09 Time 14:05 Rev Time 0.00
Received By btrobaug Date 2008-04-09 Time 13:50 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By mperson Date 2008-05-09 Time 15:04 Rev Time 0.00
Received By mperson Date 2008-05-09 Time 15:04 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By tgordon Date 2008-04-10 Time 09:08 Rev Time 0.00
Received By mperson Date 2008-04-11 Time 15:10 Sent To B
Notes
2008-04-11 15:29:49GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THERE ARE TWO DIFFERENT GENERATOR OPERATING DATA
 SHEETS SUBMITTED FOR THE 35 KW GENERATOR INDICATING TWO
 DIFFERENT BTU LOADS. PLEASE CORRELATE THE RESUBMITTAL
 WITH ONLY ONE DATA SHEET. PER FBC FUEL GAS SECTION
 401.1 SCOPE.
  
 2. CLEARLY INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE. THE ONLY CUT SECTION OF PIPE WITH
 A CORRESPONDING LENGTH IS THE UNDERGROUND PE PIPE .
 WHAT ARE THE CORRESPONDING LENGTHS TO THE ABOVE GROUND
 PIPING. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 **NEED PRINTED NAME, DATE AND SIGNATURES ON THE
 RESUBMITTED GAS ISOMETRIC RISER DIAGRAM.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 11:28 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 11:28 Sent To B
Notes
2008-05-21 11:29:07TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 12:50 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 12:50 Sent To G
Notes
2008-05-06 12:50:41TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By shill Date 2008-04-21 Time 08:08 Rev Time 0.00
Received By shill Date 2008-04-07 Time 14:33 Sent To  
Notes
2008-04-07 14:33:25TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 09:06 Rev Time 0.25
Received By tgordon Date 2008-04-10 Time 09:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-08 Cont ID  
Sent By choops Date 2008-04-08 Time 10:37 Rev Time 0.00
Received By choops Date 2008-04-08 Time 10:37 Sent To E
Notes
2008-04-08 10:38:31***APPROVED***
  
 PROVISO:GENERATOR MUST BE SETBACK A MINIMUM OF 11
 FEET FROM REAR SERVICE ROAD.
  
  
  
  
 SENT TO "E" - GENRES BOX