Plan Review Details - Permit 08040135
Plan Review Stops For Permit 08040135
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-02-19 Cont ID  
Sent By jwitmer Date 2009-02-19 Time 16:43 Rev Time 0.37
Received By jwitmer Date 2009-02-19 Time 16:43 Sent To PC
Notes
2009-02-19 16:44:08TRUSS DRAWING AND LAYOUT SHEET- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-30 Cont ID  
Sent By jwitmer Date 2008-12-30 Time 16:23 Rev Time 0.77
Received By jwitmer Date 2008-12-30 Time 16:23 Sent To PC
Notes
2008-12-30 16:30:51BUILDING PLAN REVIEW
 PERMIT: 08040135
 ADD: 3199 CUMBERLAND DRIVE
 CONT: ALTEK STEEL INDUSTRIES
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 TRUSS SHOP DRAWING REVIEW
 ACTION: DENIED
  
  
 1)THE INDIVIDUAL TRUSS SHOP DRAWING HAS A RAISED SEAL
 BUT PHOTOCOPIED SIGNATURE NOT ORIGINAL TWO WILL BE KEPT
 FOR POSSIBLE STATE REVIEW AND ENGINEERS BOARD. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 16:01 Rev Time 3.33
Received By jwitmer Date 2008-10-24 Time 16:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By jwitmer Date 2008-04-17 Time 15:53 Rev Time 3.33
Received By jwitmer Date 2008-04-17 Time 15:53 Sent To  
Notes
2008-04-17 16:57:19BUILDING PLAN REVIEW
 PERMIT: 08040135
 ADD: 3199 CUMBERLAND DRIVE
 CONT: AITEK STEEL
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) GABLE END WALL THERE IS NO INFORMATION AS TO HOW
 MUCH STEEL AND OR CONCRERE WILL BE REQUIRED AROUND THE
 APPATURE FOR THE LOUVER?106.1.2 ADDITIONAL
 INFORMATION.
  
 3) PLEASE REVIEW FLORIDA ROOFING REPORT NUMBER 5204 FOR
 PRESSURES IN ZONE# 3. PRESSURES FOR ZONE 3 EXCEED THAT
 LISTED IN THE PRODUCT APPROVAL REQUIRING RATIONAL
 ANALYSIS AND SHALL BE PREPARED BY A QUALIFIED DESIGN
 PROFESSIONAL. SEE TABLE 1609.6.2.1(2).
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-13 Cont ID  
Sent By dpalmer Date 2009-02-13 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2009-02-13 Time 09:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 10:32 Sent To ENG
Notes
2008-11-04 10:35:41PLANS ROUTED TO ENGINEERING.
 ELECTRICAL OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-07 Cont ID  
Sent By dpalmer Date 2008-10-07 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2008-10-07 Time 08:48 Sent To  
Notes
2008-10-07 08:48:14 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE CONTACT THIS OFFICE/REVIEWER TO GO OVER ANY
 OF THE COMMENTS
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ON SHEET 3 ARE SHOWN AS A MINIMUM
 DESIGN. THE SECTION OF THE ENERGY CODE GIVEN ON
 PREVIOUS REVIEW AND THE INTENT OF CHAPTER 13 IS TO
 LIMIT THE AMOUNT OF WATTS PER SQ FT. THIS SHOULD HAVE
 BEEN DONE AS A MAXIMUM OF THE WATTS PER SQ FT. BASED ON
 THE .8 WHICH WAS APPARENTLY TAKEN FROM TABLE 13-415.2.B
 AND THE FIXTURES ON PLANS, THE DESIGN WOULD BE OVER THE
 ALLOWANCE. THERE WERE NO ALLOWANCES SHOWN FOR EXTERIOR.
 PLEASE PROVIDE ALL FIXTURES.
 THE SECTIONS NOTED ON PREVIOUS REVIEW 13-415.2
 ABC.1.1,.1.2 AND .1.3.
 PLEASE CALL TO GO OVER SO THE DESIGN AND ALLOWANCE WILL
 BE CODE COMPLIANT FOR USE/OCCUPANCY.
  
 2) NOTE: PLEASE SEE THE EXHAUST FAN AT THE GABLE END
 NEEDS TO BE ON A DEDICATED CIRCUIT. THE 3/4 HP MOTOR
 BASED ON TABLE 430.248 PLACES THE AMPERAGE AT 13.8AMPS.
 AS THE VA RATING IS ABOVE 750VA, AND A MOTOR CIRCUIT
 THIS WOULD REQUIRE A DEDICATED CIRCUIT. THIS IS
 CURRENTLY BEING SHOWN ON CIRCUIT B-8 WHICH IS A 120V
 CIRCUIT FEEDING OTHER WALL RECEPTACLES IN SPACE.
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN AT THE DETACHED BUILDING TO THE NEW
 SUB PANEL *P2* AS DESIGNATED ON RISER. THE PLANS CALL
 THIS PANEL AS *B*. THE DESIGNATIONS APPEAR TO BE A
 MISPRINT.
 PLEASE SIZE THE EQUIPMENT GROUND PER 250.122.
 250.6,250.24,250.110,250.32 ETC
  
 4) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS.
 PLEASE CLARIFY IF THE LOAD CALCULATIONS AS SHOWN ARE
 FOR THE ENTIRE SERVICE OR FOR THE NEW BUILDING ONLY? IF
 FOR ENTIRE SERVICE SEE NOTES BELOW AND ALSO PROVIDE
 LOAD ON PANEL FOR NEW BUILDING AS THERE IS NO TOTAL
 LOAD AT THE BOTTOM OF PANEL *B/P2*.
 IF THIS CALCULATION IS FOR THE ENTIRE SERVICE THEN
 PLEASE SEE NEC 220 FOR ALL OTHER LOADS INCLUDING KNOWN
 LIGHT LOADS. IF THIS LOAD CALCULATION IS ONLY FOR THIS
 NEW BUILDING PLEASE VERIFY WHY THE A/C IS ON THIS
 PANEL.
 PLEASE SEE SOME SPECIFIC SECTIONS WOULD BE 220.18,
 220.50, 220.14(D)(E) AND (F).
  
 WHEN SIZING A SERVICE WITH UNKNOWN LOADS THE CODE
 PROVIDES TABLES FOR MINIMUM VA PER SQ FT AND MINIMUM VA
 PER RECEPTACLE ETC HOWEVER WHEN KNOWN LIGHTING LOADS
 AND DEDICATED LOADS ARE SHOWN AND BEING INSTALLED THEN
 THE SIZING OF THE CIRCUITS AND THE SERVICE ARE REQUIRED
 TO MEET THE SPECIFIC SECTIONS. THE DE-RATINGS ARE
 PERMITTED ONCE DEDICATED KNOWN LOADS ARE FIGURED.
 AS THERE IS NO FIXTURE LEGEND SHOWN AND ONLY THE
 INTERIOR FIXTURES IN NEW BUILDING ARE NOTED AS 250VA
 THE FINAL LOADS CAN NOT BE VERIFIED TO SEE WHICH IS THE
 LARGER OF LOADS.
  
  
 ** AS NOTED ABOVE, PLEASE CONTACT THIS OFFICE TO GO
 OVER COMMENTS FOR ANY CLARIFICATION OR QUESTIONS.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By dpalmer Date 2008-04-09 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2008-04-09 Time 16:56 Sent To  
Notes
2008-04-09 16:56:50** DENIED REVIEW**
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON PLANS FOR ELECTRICAL REVIEW AS A
 MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 PER: FBC 106.1.2, 106.3.5, FS 553.73
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE NEW SERVICE
 WHICH IS NOT GOING TO BE INSTALLED ON THIS NEW
 BUILDING. AS THIS IS NOT SHOWN AT THIS TIME.
 110.26, 240.24, 230.70 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE CORRELATE SITE PLANS AND ELECTRICAL
 PLANS. THE ELECTRICAL SPECIFIED ON SITE PLANS IS NOT
 THE SAME AS ON ELECTRICAL PLANS.
 ONE EXAMPLE IS:
 PLEASE SEE SITE PLANS WHICH SHOW A 125AMP MAIN
 DISCONNECT AT NEW BUILDING YET THE ELECTRICAL RISER ON
 SHEET 3 SHOWS 200AMP.?
 ** THIS IS NOT ALL ITEMS.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2. PLEASE BE SURE TO SEE
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO SEE AS BUILDING APPEARS TO BE CONDITIONED
 SPACE, PLEASE SUBMIT ENERGY CALCULATIONS. SEE POSSIBLE
 MECHANICAL REVIEW NOTES.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO INDICATE A
 NEW CONDENSING UNIT HOWEVER THE PLANS DOES NOT SHOW
 LOCATION OF THIS UNIT, LOCATION OF DISCONNECT OR
 REQUIRED GFI DEPENDING ON NEW LOCATION.
 110.26, 440.11, 210.8B, 210.63 ETC
  
 6) NOTE: PLEASE INDICATE CIRCUITING FOR EMERGENCY
 LIGHTS/EXIT LIGHTS PER 700.12F.
  
 7) NOTE: PLEASE SEE THE LOAD ON THE CONDENSING UNIT
 CIRCUIT EXCEEDS THAT OF THE BRANCH CIRCUIT WHICH IS
 PROVIDED. THIS INCLUDES CONDUCTORS AND BREAKER. 240.4,
 310.16, 408.4 ETC.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SE THE LOAD ON THE WELDER UNIT CIRCUIT
 EXCEEDS THAT OF THE BRANCH CIRCUIT WHICH IS PROVIDED.
 THIS INCLUDES CONDUCTORS AND BREAKER. 240.4, 310.16,
 408.4 ETC.
 FBC 106.3.5.1.2
 FOR EXAMPLE: PANEL SCHEDULE SHOWS 20.8 AMPS ON EACH
 PHASE OF THE PANEL FOR THIS UNIT AS WELL AS THE SAME AS
 SHOWN FOR CONDENSING UNIT ABOVE. THIS IS SHOWN PER
 PHASE WHICH IS 41.6 AMPS.
  
 9) NOTE: PLEASE INDICATE AND SHOW LIGHTING CONTROLS PER
 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ON BUILDING. ONE
 OF TWO PERMITTED CONTROLS MUST BE USED.
  
 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE FROM NEW MAIN B TO MAIN AT THE DETACHED
 BUILDING.
 250.110, 250.24, 250.122, 250.32.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-11-04 Cont ID  
Sent By   Date 2008-11-04 Time   Rev Time 1.00
Received By mgonzale Date 2008-11-04 Time 13:57 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-10-06 Cont ID  
Sent By dlauderm Date 2008-10-06 Time 14:31 Rev Time 0.00
Received By dlauderm Date 2008-10-06 Time 14:31 Sent To  
Notes
2008-10-06 14:30:41NO CIVIL PLAN SUBMITTED. CIVIL PLAN WAS SUBMITTED TO
 ENGINEERING SERVICES DEPARTMENT AT 1000-45TH STREET ON
 9-16-08. IT WAS GIVEN TO MANNY GONZALEZ FOR REVIEW ON
 9-25-08. PLAN NEEDS TO SHOW:
 1-SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO
 BE DISTURBED (NEW BUILDING SITE, TRENCH FROM NEW
 BUILDING TO EXISTING FOR ELECTRICAL CONDUITS).
 2-FILTER FABRIC IS REQUIRED UNDER THE TWO CATCH BASINS
 GRATES ON SITE TO STOP SOLIDS FROM ENTER THE SYSTEM.
 THEY ALSO NEED TO BE CLEANED AS NEEDED.
 3-NEED IMPERVIOUS/PERVIOUS INFORMATION FOR BEFORE AND
 AFTER DEVELOPMENT.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-09-19 Cont ID  
Sent By rchokshi Date 2008-09-19 Time 13:39 Rev Time 0.00
Received By rchokshi Date 2008-09-19 Time 13:31 Sent To  
Notes
2008-09-19 13:39:10FAILED FOR FOLLOWING REASONS:
  
 1.PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE. HEIGHT OF
 FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON YOUR STORM WATER QUALITY CALCULATION
 THAT YOU HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25,
 100 YEAR FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU
 DETERMINE THE FIRST FLOOR ELEVATION. FIRST FLOOR
 ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER THAN HIGHEST
 CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. ALSO,
 STORM WATER QUALITY CALS MUST BE APPROVED FROM 1000
 45TH STREET ENGINEERING SERVICES BEFORE WE ISSUE A
 PERMIT.
  
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT WITH SOIL
 CONDUCTIVITY USED IN EX-FILTRATION TRENCH AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 1000 45TH
 STREET ENGINEERING BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By rchokshi Date 2008-04-11 Time 09:18 Rev Time 0.00
Received By rchokshi Date 2008-04-11 Time 09:09 Sent To  
Notes
2008-04-11 09:18:03FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT WITH SOIL
 CONDUCTIVITY USED IN EX-FILTRATION TRENCH AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. ALSO, STORM WATER CALS MUST
 BE APPROVED FROM 100045TH STREET ENGINEERING SERVICES
 BEFORE WE APPROVED.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 1000 45TH
 STREET ENGINEERING BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 10:35 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 10:23 Sent To  
Notes
2008-10-21 10:28:44*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ACKNOWLEDGED; THE APPROPIATE PLAN SHEET(S) TO BE
 FIRE STAMPED WHEN ALL OTHER REVIEWER'S COMMENTS HAVE
 BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-15 Cont ID  
Sent By mawillia Date 2008-05-07 Time 10:56 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 15:09 Sent To  
Notes
2008-05-06 15:38:35*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OOR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 3. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-11 Cont ID  
Sent By adarroug Date 2009-03-11 Time 08:23 Rev Time 0.00
Received By adarroug Date 2009-03-11 Time 08:23 Sent To ENG
Notes
2009-03-11 08:24:22TO "ENG" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 16:08 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 16:08 Sent To E
Notes
2009-02-09 16:08:41TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-01 Cont ID  
Sent By adarroug Date 2008-12-01 Time 16:50 Rev Time 0.00
Received By adarroug Date 2008-12-01 Time 16:50 Sent To B
Notes
2008-12-01 16:51:04TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 13:34 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 13:34 Sent To E
Notes
2008-11-03 13:34:52TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 12:47 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 12:47 Sent To  
Notes
2008-09-16 12:49:20TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 15:09 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 15:39 Sent To  
Notes
2008-04-04 15:43:02TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-09-29 Cont ID  
Sent By rregueir Date 2008-09-29 Time 10:26 Rev Time 0.00
Received By rregueir Date 2008-09-29 Time 10:16 Sent To  
Notes
2008-09-29 10:26:12***NOTE***
  
 PLAN INDICATES NO AIR CONDITIONING TO BE INSTALLED IN
 THIS BUILDING. FLOOR PLAN SHOWS ADEQUATE OPENINGS FOR
 NATURAL VENTILATION IN ACCORDANCE WITH FBCM SECTION
 402. NO MECHANICAL PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-29 Cont ID  
Sent By rregueir Date 2008-04-29 Time 09:25 Rev Time 0.00
Received By rregueir Date 2008-04-29 Time 09:09 Sent To  
Notes
2008-04-29 09:25:51REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 SHEET #3 LOAD CALCULATIONS INDICATE THAT ALL OR A
 PORTION OF THIS BUILDING WILL BE AIR CONDITIONED.
 PLEASE SHOW WHICH AREA OF THE BUILDING IS TO BE
 CONDITIONED AND THE RELATED BUILDING ENVELOPE
 COMPONENTS. ALSO PROVIDE ENERGY CALCULATIONS WITH
 COOLING LOAD CALCULATIONS IN ACCORDANCE WITH FBCB
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-18 Cont ID  
Sent By adavila Date 2008-09-18 Time 17:14 Rev Time 0.00
Received By adavila Date 2008-09-18 Time 17:14 Sent To  
Notes
2008-09-18 17:14:49PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By adavila Date 2008-04-10 Time 17:07 Rev Time 0.00
Received By adavila Date 2008-04-10 Time 12:01 Sent To  
Notes
2008-04-10 17:08:17PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE SITE PLAN SUBMITTED WITH THIS PERMIT APPLICATION
 DOES NOT MATCH THE APPROVED FORMAL SITE PLAN AND MINOR
 PD.PLEASE REVISE.
 A. PARKING REQUIREMENTS SHOW THE WAREHOUSE TO BE 5,324
 SQUARE FEET, AND NOT 4,900 SQUARE FEET AS APPROVED.
  
 2. THE FLOOR AND LIFE SAFETY PLAN AND FOUNDATION PLAN
 DO NOT MATCH THE APPROVED SITE PLAN.PLEASE REVISE.
 A. FLOOR AND LIFE SAFETY PLAN AND FOUNDATION PLAN SHOW
 THE PROPOSED WAREHOUSE BUILDING TO BE 76 FEET WIDE, AND
 NOT 74.7 FEET.
 B. PLEASE ENSURE THAT WIDTH AND DEPTH DIMENSIONS ADD UP
 TO THE APPROVED SQUARE FOOTAGE (1,976 SQUARE FEET).
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.