Plan Review Details - Permit 08040135
| Plan Review Stops For Permit 08040135 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-02-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-19 |
Time |
16:43 |
Rev Time |
0.37 |
| Received By |
jwitmer |
Date |
2009-02-19 |
Time |
16:43 |
Sent To |
PC |
|
| Notes |
| 2009-02-19 16:44:08 | TRUSS DRAWING AND LAYOUT SHEET- OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-30 |
Time |
16:23 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-30 |
Time |
16:23 |
Sent To |
PC |
|
| Notes |
| 2008-12-30 16:30:51 | BUILDING PLAN REVIEW | | | PERMIT: 08040135 | | | ADD: 3199 CUMBERLAND DRIVE | | | CONT: ALTEK STEEL INDUSTRIES | | | TEL: (561)662-8352 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | TRUSS SHOP DRAWING REVIEW | | | ACTION: DENIED | | | | | | | | | 1)THE INDIVIDUAL TRUSS SHOP DRAWING HAS A RAISED SEAL | | | BUT PHOTOCOPIED SIGNATURE NOT ORIGINAL TWO WILL BE KEPT | | | FOR POSSIBLE STATE REVIEW AND ENGINEERS BOARD. PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY | | | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN | | | PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-24 |
Time |
16:01 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-10-24 |
Time |
16:01 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-04-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-17 |
Time |
15:53 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-04-17 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2008-04-17 16:57:19 | BUILDING PLAN REVIEW | | | PERMIT: 08040135 | | | ADD: 3199 CUMBERLAND DRIVE | | | CONT: AITEK STEEL | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 2) GABLE END WALL THERE IS NO INFORMATION AS TO HOW | | | MUCH STEEL AND OR CONCRERE WILL BE REQUIRED AROUND THE | | | APPATURE FOR THE LOUVER?106.1.2 ADDITIONAL | | | INFORMATION. | | | | | | 3) PLEASE REVIEW FLORIDA ROOFING REPORT NUMBER 5204 FOR | | | PRESSURES IN ZONE# 3. PRESSURES FOR ZONE 3 EXCEED THAT | | | LISTED IN THE PRODUCT APPROVAL REQUIRING RATIONAL | | | ANALYSIS AND SHALL BE PREPARED BY A QUALIFIED DESIGN | | | PROFESSIONAL. SEE TABLE 1609.6.2.1(2). | | | | | | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE.) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-13 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-13 |
Time |
09:29 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-04 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-04 |
Time |
10:32 |
Sent To |
ENG |
|
| Notes |
| 2008-11-04 10:35:41 | PLANS ROUTED TO ENGINEERING. | | | ELECTRICAL OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-07 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-07 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2008-10-07 08:48:14 | | | | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE CONTACT THIS OFFICE/REVIEWER TO GO OVER ANY | | | OF THE COMMENTS | | | | | | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE | | | CALCULATIONS SHOWN ON SHEET 3 ARE SHOWN AS A MINIMUM | | | DESIGN. THE SECTION OF THE ENERGY CODE GIVEN ON | | | PREVIOUS REVIEW AND THE INTENT OF CHAPTER 13 IS TO | | | LIMIT THE AMOUNT OF WATTS PER SQ FT. THIS SHOULD HAVE | | | BEEN DONE AS A MAXIMUM OF THE WATTS PER SQ FT. BASED ON | | | THE .8 WHICH WAS APPARENTLY TAKEN FROM TABLE 13-415.2.B | | | AND THE FIXTURES ON PLANS, THE DESIGN WOULD BE OVER THE | | | ALLOWANCE. THERE WERE NO ALLOWANCES SHOWN FOR EXTERIOR. | | | PLEASE PROVIDE ALL FIXTURES. | | | THE SECTIONS NOTED ON PREVIOUS REVIEW 13-415.2 | | | ABC.1.1,.1.2 AND .1.3. | | | PLEASE CALL TO GO OVER SO THE DESIGN AND ALLOWANCE WILL | | | BE CODE COMPLIANT FOR USE/OCCUPANCY. | | | | | | 2) NOTE: PLEASE SEE THE EXHAUST FAN AT THE GABLE END | | | NEEDS TO BE ON A DEDICATED CIRCUIT. THE 3/4 HP MOTOR | | | BASED ON TABLE 430.248 PLACES THE AMPERAGE AT 13.8AMPS. | | | AS THE VA RATING IS ABOVE 750VA, AND A MOTOR CIRCUIT | | | THIS WOULD REQUIRE A DEDICATED CIRCUIT. THIS IS | | | CURRENTLY BEING SHOWN ON CIRCUIT B-8 WHICH IS A 120V | | | CIRCUIT FEEDING OTHER WALL RECEPTACLES IN SPACE. | | | | | | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM MAIN AT THE DETACHED BUILDING TO THE NEW | | | SUB PANEL *P2* AS DESIGNATED ON RISER. THE PLANS CALL | | | THIS PANEL AS *B*. THE DESIGNATIONS APPEAR TO BE A | | | MISPRINT. | | | PLEASE SIZE THE EQUIPMENT GROUND PER 250.122. | | | 250.6,250.24,250.110,250.32 ETC | | | | | | 4) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS. | | | PLEASE CLARIFY IF THE LOAD CALCULATIONS AS SHOWN ARE | | | FOR THE ENTIRE SERVICE OR FOR THE NEW BUILDING ONLY? IF | | | FOR ENTIRE SERVICE SEE NOTES BELOW AND ALSO PROVIDE | | | LOAD ON PANEL FOR NEW BUILDING AS THERE IS NO TOTAL | | | LOAD AT THE BOTTOM OF PANEL *B/P2*. | | | IF THIS CALCULATION IS FOR THE ENTIRE SERVICE THEN | | | PLEASE SEE NEC 220 FOR ALL OTHER LOADS INCLUDING KNOWN | | | LIGHT LOADS. IF THIS LOAD CALCULATION IS ONLY FOR THIS | | | NEW BUILDING PLEASE VERIFY WHY THE A/C IS ON THIS | | | PANEL. | | | PLEASE SEE SOME SPECIFIC SECTIONS WOULD BE 220.18, | | | 220.50, 220.14(D)(E) AND (F). | | | | | | WHEN SIZING A SERVICE WITH UNKNOWN LOADS THE CODE | | | PROVIDES TABLES FOR MINIMUM VA PER SQ FT AND MINIMUM VA | | | PER RECEPTACLE ETC HOWEVER WHEN KNOWN LIGHTING LOADS | | | AND DEDICATED LOADS ARE SHOWN AND BEING INSTALLED THEN | | | THE SIZING OF THE CIRCUITS AND THE SERVICE ARE REQUIRED | | | TO MEET THE SPECIFIC SECTIONS. THE DE-RATINGS ARE | | | PERMITTED ONCE DEDICATED KNOWN LOADS ARE FIGURED. | | | AS THERE IS NO FIXTURE LEGEND SHOWN AND ONLY THE | | | INTERIOR FIXTURES IN NEW BUILDING ARE NOTED AS 250VA | | | THE FINAL LOADS CAN NOT BE VERIFIED TO SEE WHICH IS THE | | | LARGER OF LOADS. | | | | | | | | | ** AS NOTED ABOVE, PLEASE CONTACT THIS OFFICE TO GO | | | OVER COMMENTS FOR ANY CLARIFICATION OR QUESTIONS. | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-09 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-09 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2008-04-09 16:56:50 | ** DENIED REVIEW** | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES | | | ARE STATED ON PLANS FOR ELECTRICAL REVIEW AS A | | | MINIMUM. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | PER: FBC 106.1.2, 106.3.5, FS 553.73 | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE NEW SERVICE | | | WHICH IS NOT GOING TO BE INSTALLED ON THIS NEW | | | BUILDING. AS THIS IS NOT SHOWN AT THIS TIME. | | | 110.26, 240.24, 230.70 ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 3) NOTE: PLEASE CORRELATE SITE PLANS AND ELECTRICAL | | | PLANS. THE ELECTRICAL SPECIFIED ON SITE PLANS IS NOT | | | THE SAME AS ON ELECTRICAL PLANS. | | | ONE EXAMPLE IS: | | | PLEASE SEE SITE PLANS WHICH SHOW A 125AMP MAIN | | | DISCONNECT AT NEW BUILDING YET THE ELECTRICAL RISER ON | | | SHEET 3 SHOWS 200AMP.? | | | ** THIS IS NOT ALL ITEMS. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS PER 13-415.2. PLEASE BE SURE TO SEE | | | 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | PLEASE ALSO SEE AS BUILDING APPEARS TO BE CONDITIONED | | | SPACE, PLEASE SUBMIT ENERGY CALCULATIONS. SEE POSSIBLE | | | MECHANICAL REVIEW NOTES. | | | | | | 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO INDICATE A | | | NEW CONDENSING UNIT HOWEVER THE PLANS DOES NOT SHOW | | | LOCATION OF THIS UNIT, LOCATION OF DISCONNECT OR | | | REQUIRED GFI DEPENDING ON NEW LOCATION. | | | 110.26, 440.11, 210.8B, 210.63 ETC | | | | | | 6) NOTE: PLEASE INDICATE CIRCUITING FOR EMERGENCY | | | LIGHTS/EXIT LIGHTS PER 700.12F. | | | | | | 7) NOTE: PLEASE SEE THE LOAD ON THE CONDENSING UNIT | | | CIRCUIT EXCEEDS THAT OF THE BRANCH CIRCUIT WHICH IS | | | PROVIDED. THIS INCLUDES CONDUCTORS AND BREAKER. 240.4, | | | 310.16, 408.4 ETC. | | | FBC 106.3.5.1.2 | | | | | | 8) NOTE: PLEASE SE THE LOAD ON THE WELDER UNIT CIRCUIT | | | EXCEEDS THAT OF THE BRANCH CIRCUIT WHICH IS PROVIDED. | | | THIS INCLUDES CONDUCTORS AND BREAKER. 240.4, 310.16, | | | 408.4 ETC. | | | FBC 106.3.5.1.2 | | | FOR EXAMPLE: PANEL SCHEDULE SHOWS 20.8 AMPS ON EACH | | | PHASE OF THE PANEL FOR THIS UNIT AS WELL AS THE SAME AS | | | SHOWN FOR CONDENSING UNIT ABOVE. THIS IS SHOWN PER | | | PHASE WHICH IS 41.6 AMPS. | | | | | | 9) NOTE: PLEASE INDICATE AND SHOW LIGHTING CONTROLS PER | | | 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ON BUILDING. ONE | | | OF TWO PERMITTED CONTROLS MUST BE USED. | | | | | | 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE FROM NEW MAIN B TO MAIN AT THE DETACHED | | | BUILDING. | | | 250.110, 250.24, 250.122, 250.32. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-11-04 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2008-11-04 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2008-10-06 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
dlauderm |
Date |
2008-10-06 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2008-10-06 14:30:41 | NO CIVIL PLAN SUBMITTED. CIVIL PLAN WAS SUBMITTED TO | | | ENGINEERING SERVICES DEPARTMENT AT 1000-45TH STREET ON | | | 9-16-08. IT WAS GIVEN TO MANNY GONZALEZ FOR REVIEW ON | | | 9-25-08. PLAN NEEDS TO SHOW: | | | 1-SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO | | | BE DISTURBED (NEW BUILDING SITE, TRENCH FROM NEW | | | BUILDING TO EXISTING FOR ELECTRICAL CONDUITS). | | | 2-FILTER FABRIC IS REQUIRED UNDER THE TWO CATCH BASINS | | | GRATES ON SITE TO STOP SOLIDS FROM ENTER THE SYSTEM. | | | THEY ALSO NEED TO BE CLEANED AS NEEDED. | | | 3-NEED IMPERVIOUS/PERVIOUS INFORMATION FOR BEFORE AND | | | AFTER DEVELOPMENT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2008-09-19 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-09-19 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-09-19 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2008-09-19 13:39:10 | FAILED FOR FOLLOWING REASONS: | | | | | | 1.PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING | | | SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS | | | DURING CONSTRUCTION AND ALL DEMOLITION PHASE. HEIGHT OF | | | FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST | | | PARTICLES. | | | | | | 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | | 4060-07: | | | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | | FOLLOWING: | | | | | | 1. EROSION CONTROL, AND | | | 2. LAND STABILIZATION | | | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | | | 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | | SERVICES, PHONE# 494-1040 | | | | | | 4. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | | | 5. PLEASE SHOW ON YOUR STORM WATER QUALITY CALCULATION | | | THAT YOU HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25, | | | 100 YEAR FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU | | | DETERMINE THE FIRST FLOOR ELEVATION. FIRST FLOOR | | | ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER THAN HIGHEST | | | CROWN OF THE ROAD. | | | | | | 6. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA, | | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU | | | ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE | | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | | AND USED IN STORM WATER QUALITY CALCULATIONS. ALSO, | | | STORM WATER QUALITY CALS MUST BE APPROVED FROM 1000 | | | 45TH STREET ENGINEERING SERVICES BEFORE WE ISSUE A | | | PERMIT. | | | | | | | | | 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL | | | OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | | THESE. PLEASE RESUBMIT GEO-TECH REPORT WITH SOIL | | | CONDUCTIVITY USED IN EX-FILTRATION TRENCH AND ALL | | | ENVRONMENTAL REPORT. | | | | | | 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND | | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | | FLOODED AND HAVE ENOUGH DRAINS. | | | | | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 1000 45TH | | | STREET ENGINEERING BEFORE WE ISSUE A PERMIT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-04-11 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-04-11 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-04-11 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2008-04-11 09:18:03 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | | | | 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING | | | SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS | | | DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT | | | OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST | | | PARTICLES. | | | | | | 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | | 4060-07: | | | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | | FOLLOWING: | | | | | | 1. EROSION CONTROL, AND | | | 2. LAND STABILIZATION | | | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | | | 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | | SERVICES, PHONE# 494-1040 | | | | | | 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | | | 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA | | | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST | | | FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE | | | ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. | | | | | | 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | | PROVIDE A COPY OF THESE CALCULATIONS. | | | | | | 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | | THESE. PLEASE RESUBMIT GEO-TECH REPORT WITH SOIL | | | CONDUCTIVITY USED IN EX-FILTRATION TRENCH AND ALL | | | ENVRONMENTAL REPORT. | | | | | | 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | | FLOODED AND HAVE ENOUGH DRAINS. | | | | | | 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | | WATER QUALITY CALCULATIONS. ALSO, STORM WATER CALS MUST | | | BE APPROVED FROM 100045TH STREET ENGINEERING SERVICES | | | BEFORE WE APPROVED. | | | | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM 1000 45TH | | | STREET ENGINEERING BEFORE WE ISSUE A PERMIT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-21 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-21 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2008-10-21 10:28:44 | *****PROVISO***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ACKNOWLEDGED; THE APPROPIATE PLAN SHEET(S) TO BE | | | FIRE STAMPED WHEN ALL OTHER REVIEWER'S COMMENTS HAVE | | | BEEN SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-07 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-06 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2008-05-06 15:38:35 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH | | | EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OOR THE | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES) . | | | | | | 3. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-03-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-11 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-11 |
Time |
08:23 |
Sent To |
ENG |
|
| Notes |
| 2009-03-11 08:24:22 | TO "ENG" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-02-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-09 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-09 |
Time |
16:08 |
Sent To |
E |
|
| Notes |
| 2009-02-09 16:08:41 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-01 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-01 |
Time |
16:50 |
Sent To |
B |
|
| Notes |
| 2008-12-01 16:51:04 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-03 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-03 |
Time |
13:34 |
Sent To |
E |
|
| Notes |
| 2008-11-03 13:34:52 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-16 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-16 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2008-09-16 12:49:20 | TO "COMM" BD#47 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-06 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-04 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2008-04-04 15:43:02 | TO "COMM" BD#8 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-29 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-29 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2008-09-29 10:26:12 | ***NOTE*** | | | | | | PLAN INDICATES NO AIR CONDITIONING TO BE INSTALLED IN | | | THIS BUILDING. FLOOR PLAN SHOWS ADEQUATE OPENINGS FOR | | | NATURAL VENTILATION IN ACCORDANCE WITH FBCM SECTION | | | 402. NO MECHANICAL PERMIT REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-29 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-29 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2008-04-29 09:25:51 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | SHEET #3 LOAD CALCULATIONS INDICATE THAT ALL OR A | | | PORTION OF THIS BUILDING WILL BE AIR CONDITIONED. | | | PLEASE SHOW WHICH AREA OF THE BUILDING IS TO BE | | | CONDITIONED AND THE RELATED BUILDING ENVELOPE | | | COMPONENTS. ALSO PROVIDE ENERGY CALCULATIONS WITH | | | COOLING LOAD CALCULATIONS IN ACCORDANCE WITH FBCB | | | CHAPTER 13. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-09-18 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-09-18 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2008-09-18 17:14:49 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-04-10 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-04-10 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2008-04-10 17:08:17 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. THE SITE PLAN SUBMITTED WITH THIS PERMIT APPLICATION | | | DOES NOT MATCH THE APPROVED FORMAL SITE PLAN AND MINOR | | | PD.PLEASE REVISE. | | | A. PARKING REQUIREMENTS SHOW THE WAREHOUSE TO BE 5,324 | | | SQUARE FEET, AND NOT 4,900 SQUARE FEET AS APPROVED. | | | | | | 2. THE FLOOR AND LIFE SAFETY PLAN AND FOUNDATION PLAN | | | DO NOT MATCH THE APPROVED SITE PLAN.PLEASE REVISE. | | | A. FLOOR AND LIFE SAFETY PLAN AND FOUNDATION PLAN SHOW | | | THE PROPOSED WAREHOUSE BUILDING TO BE 76 FEET WIDE, AND | | | NOT 74.7 FEET. | | | B. PLEASE ENSURE THAT WIDTH AND DEPTH DIMENSIONS ADD UP | | | TO THE APPROVED SQUARE FOOTAGE (1,976 SQUARE FEET). | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
|