| 2008-04-08 09:31:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. |
| | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, |
| | PROVIDE CALCULATIONS. |
| | |
| | 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG.THIS IS REQUIRED IN |
| | ADDITION TO THE NOAS PROVIDED. |
| | |
| | 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1.THE EXISTING CLEAR |
| | OPENING CANNOT BE REDUCED BY MORE THAN 5%; NO |
| | INFORMATION WAS PROVIDED REGARDING THE EXISTING |
| | WINDOWS. |
| | |
| | 4.IF ENGINEERING IS INCLUDED IN THE PACKAGE, IT MUST |
| | COMPLY WITH FAC61G15-23.002.A LEGIBLE SEAL IS |
| | REQUIRED AND TWO ORIGINAL SETS ARE TO BE INCLUDED FOR |
| | PERMIT ISSUANCE. |
| | |