Plan Review Details - Permit 08040122
Plan Review Stops For Permit 08040122
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By rmcdouga Date 2008-05-21 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2008-05-21 Time 15:16 Sent To  
Notes
2008-05-21 15:29:27SUBMITTED ENGINEERED DRAWINGS FOR STRUCTURAL REPAIRS AT
 SUNROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-01 Cont ID  
Sent By rmcdouga Date 2008-05-01 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2008-05-01 Time 09:44 Sent To  
Notes
2008-05-01 09:47:32ENGINEER SUBMITTED JAMB REINFORCING CLARIFICATION
 DETAIL PER BLDG. INSPECTOR'S REQUEST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-04-17 Cont ID  
Sent By rmcdouga Date 2008-04-17 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2008-04-16 Time 18:34 Sent To  
Notes
2008-04-17 08:34:16BUILDING PROVISO
  
 1) MOTORIZED SHUTTERS FOR THE TWO DOORS BEING REPLACED
 AT THE REAR OF THE STRUCTURE WITH NON-IMPACT RATED
 FRENCH DOORSARE TO BE UNDER A SEPARATE PERMIT.
  
 2) SUBMIT SIGNED AND SEALED STRUCTURAL REPAIR DETAILS
 FROM THE DESIGNER OF RECORD FOR PATCHING THE ROOF
 OPENING WHERE THE ROOF TOP PACKAGE A/C UNIT IS BEING
 REMOVED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By btrobaug Date 2008-11-06 Time 15:47 Rev Time 0.00
Received By btrobaug Date 2008-11-06 Time 15:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By btrobaug Date 2008-04-09 Time 12:07 Rev Time 0.00
Received By btrobaug Date 2008-04-09 Time 09:21 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-09-23 Cont ID  
Sent By mperson Date 2008-09-23 Time 09:02 Rev Time 0.00
Received By mperson Date 2008-09-23 Time 09:02 Sent To PC
Notes
2008-09-23 09:05:55REVISION SHEET A2.3 MAIN HOUSE: "OK" GAS PIPING TO MAIN
 HOUSE REPLACED, AND VALUE INCREASED PER MARSHALL &
 SWIFT. *MRPERSON.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By mperson Date 2008-09-23 Time 08:53 Rev Time 0.00
Received By mperson Date 2008-09-23 Time 08:53 Sent To PC
Notes
2008-09-23 09:02:27GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A7.1 HAS A DIFFERENT ADDRESS FROM THE MAIN
 HOUSE (227 10TH STREET) AS WELL AS A DIFFERENT MASTER
 PERMIT NUMBER (#08040121). PLEASE KNOW THAT REVISED
 PLANS FOR THE GARAGE MUST BE SUBMITTED UNDER MASTER
 PERMIT #08040121.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By mperson Date 2008-09-03 Time 11:51 Rev Time 0.00
Received By mperson Date 2008-09-03 Time 11:51 Sent To PC
Notes
2008-09-03 11:59:44GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS.
  
 2. NOT ALL PIPIE SIZES AND MATERIAL TYPES ARE BEING
 INDICATED ON THE GAS RISER. PLEASE CLEARLY INDICATE THE
 PIPE SIZES AND MATERIAL TYPES OF THE ABOVE GROUND
 PIPING AT THE METER LOCATION AND TO THE EXISTING STOVE.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: CLEARLY INDICATE IF THE GAS METER ALSO DELIVERS
 GAS TO THE GARAGE AND GUEST HOUSE ON PERMIT #08040121.
 IF THIS GAS METER DOES DELIVER GAS TO THE GARAGE AND
 GUEST HOUSE CLEARLY INDICATE THAT IT DOES AND CLEARLY
 INDICATE THE BTU'S OF THE GARAGE/GUEST HOUSE
 (GARAGE/GUEST HOUSE HAS A 140,000 BTU WATER HEATER;
 22,000 BTU DRYER; AND A 65,000 BTU RANGE).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: CLEARLY INDICATE THE LONGEST LENGTH OF THE
 SYSTEM. THIS INCLUDES THE GARAGE/GUEST HOUSE (SEE
 COMMENT #2). PLEASE KNOW THE THE ADDED SUM OF THE
 INDICATED CUT SECTION CORRESPONDING LENGTHS IS 110',
 HOWEVER THE SUBMITTED GAS ISOMETRIC INDICATES 108'.
 PLEASE KNOW THE THE LONGEST LENGTH OF 108' IS WRONG AND
 THAT IT NEEDS TO BE CORRELATED WITH COMMENT #1 ON THE
 RESUBMITTAL.
  
 5. CLEARLY INDICATE IF THE MP REGULATORS (2 PSI TO O.5
 PSI) ARE NEW OR EXISTING ON THE RESUBMITTAL. IF THEY
 ARE NEW PLEASE SUBMIT MANUFACTURE SHEETS FOR THE MP
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
 MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE MAKE,
 MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES = CSA,
 AGA, UL)
  
 6. CLEARLY INDICATE THAT THE FUTURE GAS FIRE PLACE LOGS
 ARE CAPPED GAS TIGHT. PER FBC-2004 FUEL GAS SEC. 404.12
 OUTLET CLOSURES: GAS OUTLETS THAT DO NOT CONNECT TO
 APPLIANCES SHALL BE CAPPED GAS TIGHT.
  
 7. SHEETS A2.1 AND A2.2, DO NOT INDICATE A FUTURE GAS
 FIRE PLACE LOGS ON THE MAIN HOUSE FLOOR PLAN. PLEASE
 PROVIDE A REVISED PLAN SHEET WITH THE LOCATION OF THE
 FUTURE GAS FIRE PLACE LOGS. PER (W.P.B. AS AMENDED)
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 16:38 Sent To E
Notes
2008-10-31 16:39:02TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 09:59 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 09:59 Sent To G
Notes
2008-09-18 10:00:07TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 16:28 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 16:28 Sent To P
Notes
2008-09-02 16:28:38TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 15:14 Sent To B
Notes
2008-05-20 15:14:41TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:07 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:07 Sent To E
Notes
2008-04-30 14:07:35TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-17 Cont ID  
Sent By rmcdouga Date 2008-04-17 Time 08:39 Rev Time 0.00
Received By rmcdouga Date 2008-04-04 Time 16:33 Sent To  
Notes
2008-04-04 16:33:24TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 08:38 Rev Time 0.20
Received By tgordon Date 2008-04-10 Time 08:38 Sent To P
Notes
2008-04-10 08:40:21NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 **WHEN REPLACEINT THE EXISTING A/C SYSTEM A MECHANICAL
 PERMIT WILL BE REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-15 Cont ID  
Sent By jleech Date 2008-04-15 Time 07:22 Rev Time 0.00
Received By jleech Date 2008-04-15 Time 07:15 Sent To B
Notes
2008-04-15 07:22:48FIXTURE CHANGE OUT ONLY

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-08 Cont ID  
Sent By mflis Date 2008-04-08 Time 08:39 Rev Time 0.00
Received By mflis Date 2008-04-08 Time 08:39 Sent To E
Notes
2008-04-08 08:39:42ZONING REVIEW: PASSED
  
 * REVIEW OF NEW DOORS AND WINDOWS AT MAIN HOUSE
  
 MATT FLIS - 822-1445