Plan Review Details - Permit 08040121
Plan Review Stops For Permit 08040121
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-04-25 Cont ID  
Sent By lursu Date 2008-04-25 Time 10:35 Rev Time 0.00
Received By lursu Date 2008-04-25 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-08-12 Cont ID  
Sent By rmcdouga Date 2008-08-12 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2008-08-12 Time 11:44 Sent To  
Notes
2008-08-12 11:46:14REVISED DRAINAGE PLANS ARE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2008-07-31 Cont ID  
Sent By rmcdouga Date 2008-07-31 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2008-07-31 Time 07:31 Sent To  
Notes
2008-07-31 08:10:22REVISED DRAINAGE PLAN IS DENIED BY BUILDING.
  
 1) THE SHEET NUMBERING DOES NOT CORRESPOND TO THE
 APPROVED DRAINAGE PLANS. THERE ARE 5 SHEETS. PLEASE
 CORRECT.
  
 2) TWO SHEETS 3 OF 4 WERE SUBMITTED AND SHEET 2 OF 4
 WITH POLLUTION INFORMATION WAS MISSING.
  
 3) IT APPEARS THAT THE ONLY SHEETS THAT NEED TO BE
 REVISED FROM THE APPROVED PLANS ARE SHEETS 3 OF 5 AND 4
 0F 5.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2008-07-01 Cont ID  
Sent By rmcdouga Date 2008-07-01 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2008-07-01 Time 13:59 Sent To  
Notes
2008-07-01 13:59:40TRUSS SUBMITTAL
  
 DENIED BY BUILDING
  
 1) THE PROJECT NAME AND ADDRESS ON THE TRUSS DRAWING
 COVER SHEET IS NOT CORRECT. FAC 61G15-23.002
  
 2) THE TRUSS ENGINEER'S WET SIGNATURE IS REQUIRED ON
 THE DOCUMENTS. THE COVERSHEETS AND TRUSS LAYOUT PLANS
 ARE NOT ORIGINAL SIGNATURES. PHOTOCOPIES AND SIGNATURE
 STAMPS ARE NOT ACCEPTABLE. FS471 AND FAC 61G15-23.002
  
 3) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED
 TO REVIEW AND APPROVE THE TRUSS LAYOUT.
  
 NOTE: THE TRUSS INFORMATION IS NOT REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. IT IS TO BE GIVEN TO THE
 BUILDING INSPECTOR IN THE FIELD AT THE ROOF FRAMING
 INSPECTION. THE ABOVE CORRECTIONS ARE REQUIRED TO BE
 COMPLETED PRIOR TO THE INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-27 Cont ID  
Sent By rmcdouga Date 2008-05-27 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2008-05-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By rmcdouga Date 2008-04-17 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2008-04-17 Time 17:10 Sent To  
Notes
2008-04-17 17:57:032004 FBC W/2007 REVISIONS
 NEW GARAGE APARTMENT
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE ADDRESS IN THE TITLE BLOCK IS FOR THE MAIN HOUSE
 THE ADDRESS FOR THE GARAGE APARTMENT IS 227- 10TH
 STREET. PLEASE CORRECT.
  
 4) THE TYPE OF CONSTRUCTION SPECIFIED ON SHEET A1.1 IS
 V AND ON S3 IT IS SPECIFIED AS III-B WITH THE OCCUPANCY
 AS R2. THE CORRECT OCCUPANCY TYPE IS R3 AND
 CONSTRUCTION TYPE IS V-B UNSPRINKLERED. PLEASE REVISE.
 SEE FBC 602 AND 302.
  
 5) SPECIFY THE HEIGHT OF THE GUARD RAILS AT THE
 BALCONIES ON THE PLANS. SEE FBC R312.1
  
 6) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED TO
 A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION SO AS TO NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED SO AS TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE AWAY FROM FOUNDATION WALLS
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 7) THE PLANS REFERENCE THE 2004 FBC WITH 2006
 AMENDMENTS. THE CORRECT REFERENCE IS THE 2004 FBC WITH
 2007 AMENDMENTS.
  
 8)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 9) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. ONE OF THEM HAS NOT BEEN SIGNED. SEE
 FBC 13-600.3ABC.2
  
 10) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9B-72. NOTE: THEY ARE REQUIRED TO APPROVED IN WRITING
 BY THE DESIGNER OF RECORD. FBC 106.3.3* CITY
 AMENDMENTS
  
 11) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 FLAT ROOF ZONES 1, 2 AND 3 FOR EXPOSURE CATEGORY C AND
 A 20' MEAN ROOF HEIGHT ON THE STRUCTURAL PLANS.SEE
 FBC TABLE R301.2(2) AND TABLE R 301.2(3). NOTE: THE
 UPLIFT FOR ROOF ZONE 3 (CORNERS) EXCEEDS THE MAXIMUM
 DESIGN PRESSURE OF -98.3 PSF FOR THE JOHNS MANVILLE BUR
 SYSTEM.
  
 12) SPECIFY FIREBLOCKING AS REQUIRED BY FBC R602.1.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By btrobaug Date 2008-11-06 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2008-11-06 Time 14:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By btrobaug Date 2008-04-09 Time 08:51 Rev Time 0.00
Received By btrobaug Date 2008-04-09 Time 07:50 Sent To M
Notes
2008-04-09 08:51:23 
  
  
 REDLINED BATH CIRCUIT 210.11(C)(3) ON PANEL SCHEDULE
 AND SMOKE ALARM R313.1.1 IN THE GARAGE./WRT

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-05-22 Cont ID  
Sent By mperson Date 2008-05-22 Time 09:33 Rev Time 0.00
Received By mperson Date 2008-05-22 Time 09:33 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-15 Cont ID  
Sent By mperson Date 2008-04-15 Time 09:29 Rev Time 0.00
Received By mperson Date 2008-04-15 Time 09:29 Sent To B
Notes
2008-04-15 10:01:00GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW ON SHEET A7.1 GAS PIPING ISOMETRIC TO
 MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 *NOTE: NOT ALL CUT SECTIONS OF PIPE ARE INDICATING
 CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED CUT SECTIONS THAT REQUIRE
 CORRESPONDING LENGTHS. PER FBC FUEL GAS SECTION 401.1
 SCOPE.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: BTU LOAD 50,000 FOR THE TANKLESS WATER HEATER
 SEEMS LOW PLEASE CLARIFY. PER (W.P.B.) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS, SECTION 106.1.2
 ADDITIONAL DATA AND FBC FUEL GAS SECTION 401.1 SCOPE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THIS INCLUDES THE EXISTING MAIN HOUSE GAS
 SYSTEMS LONGEST LENGTH AS WELL AS THE PROPOSED GUEST
 HOUSE WORK. ALSO IF THE GAS SYSTEM IS NATURAL GAS
 PLEASE CORRECT THE INDICATED FUEL GAS TABLE TO BE
 402.4(2).
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER AND DRYER PER FBC-2004 FUEL GAS
 CODE SECTION 304.
  
 6. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI OR WC)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2. NATURAL GAS
 SPECIFY .5 PSI OR 2 PSI. UNDILUTED PROPANE (LP) 11 INCH
 WC, 2 PSI OR 10 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: THE MANUFACTURER'S SPECIFICATION SHEET AT A
 MINIMUM SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (THIRD PARTY LISTING).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 16:49 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 16:49 Sent To E
Notes
2008-10-31 16:50:13TO "BTROBUAG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 10:49 Sent To M
Notes
2008-09-03 10:49:40TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 09:09 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 09:09 Sent To M
Notes
2008-08-27 09:10:11TO "MECH" TOM G.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 10:58 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 10:58 Sent To B
Notes
2008-08-04 10:59:06TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 13:49 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 13:49 Sent To B
Notes
2008-07-29 13:49:27TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 15:59 Sent To B
Notes
2008-06-30 15:59:31TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 16:40 Sent To Z
Notes
2008-05-14 16:41:06TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-17 Cont ID  
Sent By rmcdouga Date 2008-04-17 Time 18:16 Rev Time 0.00
Received By rmcdouga Date 2008-04-07 Time 11:20 Sent To  
Notes
2008-04-07 11:20:20TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By tgordon Date 2008-09-04 Time 14:59 Rev Time 0.45
Received By tgordon Date 2008-09-04 Time 14:59 Sent To  
Notes
2008-09-04 15:01:05REVISION TO MECH. PLAN AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 13:57 Rev Time 0.45
Received By tgordon Date 2008-08-27 Time 13:57 Sent To  
Notes
2008-08-27 14:19:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN
 *** DENIED ***
  
 1) MECHANICAL PLAN ON FILE WAS SIGNED AND SEALED BY AN
 ARCHITECT (DAVID LAWRENCE) AND ONLY HE MAY MAKE
 REVISIONS.
  
 2) REVISED MECHANICAL PLAN EQUIPMENT SCHEDULE IS
 SHOWING A 13 SEER SYSTEM, ENERGY CALCULATIONS ON FILE
 ARE CALLING FOR A 14 SEER SYSTEM THAT'S A HEAT PUMP.
 PLEASE CORRECT PLAN OR REVISE ENERGY CAL'S, PER 2004
 FBC 13-103.1.2.
  
 3) A/C SYSTEM MODEL NUMBER A.H.U. 19HX5 WITH C.U.
 2TTR3018 (FIRST COMPANY AND TRANE) LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE OR A MANUFACTURER'S DATA SHEET, PER 2004
 FBC 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 15:32 Rev Time 0.45
Received By tgordon Date 2008-05-21 Time 15:32 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 07:59 Rev Time 0.35
Received By tgordon Date 2008-04-10 Time 07:59 Sent To P
Notes
2008-04-10 08:24:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONE COPY OF THE ENERGY CALCULATIONS HAVE NOT BEEN
 SIGNED BY THE OWNER/AGENT, PLEASE CORRECT PER 2004 FBC
 13-103.3.
  
 2) GAS WATER HEATER AND GAS CLOTHES DRYER APPEAR TO BE
 IN A CONFINED SPACE. PLEASE ADD COMBUSTION AND MAKE-UP
 AIR CALCULATIONS TO MECHANICAL PLAN AND IF NEEDED
 PROVIDE COMBUSTION AND MAKE-UP AIR TO SPACE, PER 2004
 FBC/R G2407.1, G207.4, AND G2407.5.1. PLEASE ALSO CHECK
 THE BTU'S FOR THE GAS TANKLESS WATER HEATER AS MOST
 UNITS OPERATE AT 118,00 BTU'S OR MORE.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE GAS TANKLESS WATER HEATER, PER
 2004 WPB AMEND. 106.1.2.
  
 4)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE A/C SYSTEM SHOWING A CARRIER
 CONDENSER AND FIRST COMPANY AIR HANDLER HAVE BEEN
 DESIGNED AND TESTED TOGETHER TO RATE A 14 SEER, PER
 13-607.1.ABC.3.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-22 Cont ID  
Sent By mperson Date 2008-05-22 Time 09:33 Rev Time 0.00
Received By mperson Date 2008-05-22 Time 09:33 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-15 Cont ID  
Sent By mperson Date 2008-04-15 Time 09:04 Rev Time 0.00
Received By mperson Date 2008-04-15 Time 09:04 Sent To G
Notes
2008-04-15 09:28:50PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEETS A4.1 AND A5.1 THE SCUPPERS WILL REQUIRE A
 DOWNSPOUT PER FBC BUILDING SECTION
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 2. SHEET A7.1 SANITARY PLUMBING RISER PLEASE CORRECT
 THE FOLLOWING.
  
 A} CLEARLY INDICATE A TW0-WAY CLEANOUT BEING USED AT
 THE JUNCTION OF THE BUILBING DRAIN AND BUILDING SEWER.
 PER FBC PLUMBING SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 B} THE BRANCH DRAIN AND STACK FOR THE WASHING MACHINE
 SHALL BE A MINIMUM OF 3 INCH. PER FBC PLUMBING SECTION
 406.3 WASTE CONNECTION.
  
 C} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE 3
 INCH. PER FBC PLUMBING SECTION 708.7 MINIMUM SIZE.
  
 D} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4 FEET ABOVE FINNISH FLOOR. PER FBC PLUMBING
 SECTION 708.9 ACCESS.
  
 E} IF IT IS THE INTENT TO INSTALL A CLEANOUT FOR THE
 2ND FLOOR LAVATORY IT SHALL BE 2 INCH. PER FBC PLUMBING
 SECTION 708.7 MINIMUM SIZE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-19 Cont ID  
Sent By mflis Date 2008-05-19 Time 13:34 Rev Time 0.00
Received By mflis Date 2008-05-19 Time 13:34 Sent To M
Notes
2008-05-19 13:35:18ZONING REVIEW: PASSED
  
 ** IN FUTURE, PLEASE ATTACH COPY OF SURVEY TO DRAWING
 SETS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-08 Cont ID  
Sent By mflis Date 2008-04-08 Time 10:55 Rev Time 0.00
Received By mflis Date 2008-04-08 Time 10:55 Sent To E
Notes
2008-04-08 10:59:10ZONING REVIEW: FAILED
  
 1) PERMIT DWGS UNCLEAR. THEY INDICATE NEW CONSTRUCTION.
 CITY HAS REVIEWED IN THE PAST RENOVATIONS FOR THIS
 BUILDING. IS THIS TRULY ALL-NEW CONSTRUCTION IN LIEU OF
 REHAB?
  
 2) IF NEW CONSTRUCTION, DEMO PLANS SHOULD BE PROVIDED
 THAT CLEAR INDICATE THE STRUCTURE WILL BE TAKEN DOWN.
  
 3) SURVEY SHOULD BE PROVIDED INDICATED BUILDINGS ON
 PROPERTY.
  
 4) IF NEW CONSTRUCTION, PLEASE PROVIDE SQUARE FOOTAGE
 FOR GARAGE AREA AND FOR APARTMENT SEPARATELY.
  
 MATT FLIS - 822-1445