Plan Review Details - Permit 08040103
Plan Review Stops For Permit 08040103
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-17 Cont ID  
Sent By amorse Date 2008-09-17 Time 17:18 Rev Time 0.00
Received By amorse Date 2008-09-17 Time 17:18 Sent To PC
Notes
2008-09-17 17:20:08 
  
 PASSED REVISIONS FOR BUILDING ALONG WITH PRODUCT
 APPROVALS AND SIGNED TRUSS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-09-13 Cont ID  
Sent By amorse Date 2008-09-13 Time 07:09 Rev Time 0.00
Received By amorse Date 2008-09-13 Time 07:09 Sent To E
Notes
2008-09-13 07:27:43 
  
 DENIED
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR THE REAR DOOR WAS
 TO CHANGE IT FROM A FRENCH DOOR TO A STEEL INSULATED
 DOOR PER THE NEW SHEETS A-1.0 AND A-2.0 BUT THE NOA IS
 ALSO FOR A GLAZED DOOR. THE NOA IS SPECIFIC AND THE
 DOOR ON PAGE 6 CANNOT BE CIRCLED WITH A NOTE "NO
 GLAZING" THE CORRECT NOA MUST BE SUBMITTED. JELD-WEN
 HAS THIS DOOR UNDER FL# 539.33 WITH MIAMI-DADE NOA #
 07-07310.02, IF THIS IS NOT THE CORRECT DOOR PLEASE
 CONTACT SUPPLIER FOR THE CORRECT PRODUCT APPROVAL.
  
 2) ALL OTHER REVISED PRODUCT APPROVALS ARE OK AND MAY
 BE REMOVED BEFORE RESUBMITTAL, NEW SHEETS ARE OK FOR
 BUILDING AND UPON APPROVAL OF ELECTRICAL SHEETS MAY
 ALSO BE REMOVED WHEN RESUBMITTING DOOR PRODUCT
 APPROVAL.
  
 3) THE SUBMITTAL FOR THE ENHANCED FASTENING FOR THE
 ROOF IS APPROVED AND HAS BEEN ATTACHED TO THE NEW
 ROOFING PRODUCT APPROVAL.
  
 4) THE SUBMITTAL OF THE ROOF TRUSS ENGINEERING HAS BEEN
 DENIED, A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES
 ARE NOT ACCEPTABLE PER 471.025 F.S.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By amorse Date 2008-07-01 Time 14:09 Rev Time 0.00
Received By amorse Date 2008-07-01 Time 14:09 Sent To PC
Notes
2008-07-01 14:12:55 
  
 PASSED
  
 *******PROVISO*********
  
 REQUIRES CORRECTED ENHANCED FASTENER CALCULATIONS FOR
 JOHNS MANSVILLE APP MODIFIED BITUMEN ROOFING SYSTEM.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-17 Cont ID  
Sent By amorse Date 2008-06-17 Time 15:10 Rev Time 0.00
Received By amorse Date 2008-06-17 Time 15:10 Sent To PC
Notes
2008-06-17 15:51:41 
  
 DENIED
  
 1)CHOOSE THE INSTALLATION METHOD FOR THE TPO ROOF
 MEMBRANE FROM CHOICES ON PAGES 5 & 6 OF THE PRODUCT
 APPROVAL, PROVIDE SIGNED AND SEALED CALCULATIONS FOR
 THE CHOSEN METHOD AS REQUIRED BY LIMITATION #7 ON PAGE
 7 FOR THE ENHANCED FASTENING FOR PERIMETER AND CORNER
 ROOF ZONES. PLEASE NOTE THAT ROOF DECK ATTACHMENT PER
 THE PRODUCT APPROVAL REQUIRES #8 SCREWS AT 6" O/C.
  
 2)THE CHANGE OF CONTRACTOR REQUIRES A FEE AND A NEW
 PERMIT APPLICATION TO BE FILLED OUT, PLEASE NOTE THAT
 ALL SUB CONTRACTORS CAN BE LISTED ON THE NEW PERMIT OR
 THEY CAN PULL THEIR OWN PERMITS SEPARATELY
  
 3)A NEW NOC WILL NEED TO BE RECORDED WITH NEW
 CONTRACTOR LISTED, THE NOC PROVIDED WAS RECORDED WITH
 THE OWNER AS THE CONTRACTOR
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-18 Cont ID  
Sent By amorse Date 2008-04-18 Time 17:03 Rev Time 0.00
Received By amorse Date 2008-04-18 Time 17:03 Sent To PC
Notes
2008-04-18 16:24:41 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $508.60 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 5)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN
 BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 8)NO PRODUCT APPROVALS WERE SUBMITTED FOR DOORS,
 WINDOWS, ROOFING, LINTELS,AND CONNECTORS AND STRAPS.
 IN LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE
 LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE WITH THE
 STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON
 TIE'S COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED
  
 9)SUBMIT 2 COPIES OF THE SIGNED AND SEALED ENGINEERED
 TRUSS DRAWINGS THAT COMPLY WITH R802.10.1 FBC WITH
 PERMIT APPLICATION OR BEFORE INSTALLATION THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
  
 10)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO
 BUILDING PER 1603.1.4 FBC,PLEASE NOTE THAT THE CITY
 OF WEST PALM BEACH IS IN THE 140 MPH (3 SECOND GUST)
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 12)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 13)COLUMN SCHEDULE ON S-1.0 CALLS FOR C-2 TYPE COLUMN
 AT LOCATIONS WITH SPANS OVER 6'-0" WOULD A C-2 BE
 REQUIRED AT CORNER OF UTILITY AREA
  
 14)OWNER BUILDER EXEMPTION CANNOT BE CLAIMED FOR
 PROPERTY THAT IS RENTED OR LEASED. THIS OWNER HAS THREE
 PROPERTIES THE ONE AT 10851 OLD BRIDGEPORT LANE HAS
 HOMESTEAD EXEMPTION AND IS CONSIDERED MAIN RESIDENCE.
 PLEASE FILL OUT A CHANGE OF CONTRACTOR FORM AND HAVE A
 LICENSED CONTRACTOR PERFORM THE WORK.
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006&2007
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006&2007 AMENDMENTS
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 11:56 Sent To PC
Notes
2008-10-08 11:57:47REVISED SERVICE TO METER MAIN COMBO AT THE DETACHED
 GARAGE. THE HOUSE IS NOW SUB FED TO A NEW MCB PANEL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-29 Cont ID  
Sent By dpalmer Date 2008-09-29 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2008-09-29 Time 14:53 Sent To Z
Notes
2008-09-29 14:54:02PLANS ROUTED TO ZONING AS THERE ARE NEW SITE PLANS IN
 BOTH SETS.
2008-09-29 14:53:42 
 ** DENIED **
  
 1) NOTE: THE ELECTRICAL RISER HAS NOW BEEN COMPLETELY
 REVISED WHICH HAS CREATED NEW COMMENTS WHICH COULD HAVE
 BEEN MADE ON PREVIOUS REVIEW.
 PLEASE SEE THE PANEL *B* AT MAIN HOUSE IS MISSING A
 MAIN DISCONNECTING MEANS PER 225.31-225.39. THE
 PREVIOUS RISER HAD THIS AS A MAIN CIRCUIT BREAKER
 PANEL. EVEN IF THERE IS OVER CURRENT PROTECTION AT THE
 GARAGE A DISCONNECTING MEANS IS REQUIRED AT THE MAIN
 HOUSE PER SECTIONS OF CODE GIVEN ABOVE.
 THEY CAN BE FOUND IN THE 2005 NFPA-70 (NEC).
  
 2) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING
 ELECTRODE SYSTEM REQUIRED AT MAIN HOUSE. THIS IS NOW
 THE NEW DETACHED BUILDING. NEW FOOTER STEEL IS REQUIRED
 WHICH WAS ON PREVIOUS PLANS ISSUED FOR PERMIT, COLD
 WATER PIPE (WHEN METALLIC) AND ANY MADE ELECTRODES AS
 LISTED. NO GROUNDING ELECTRODE SYSTEM IS SHOWN AT MAIN
 HOUSE.
  
 3) NOTE: PLEASE INDICATE THE AIC RATING FOR NEW
 METER/MAIN. 110.9
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-16 Cont ID  
Sent By dpalmer Date 2008-09-16 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2008-09-16 Time 15:27 Sent To B
Notes
2008-09-16 15:28:08 
 ** DENIED REVIEW OF REVISIONS**
  
 1) NOTE: PLEASE COORDINATE RISER AND PANELS. THE
 FOLLOWING ARE SOME EXAMPLES:
  
 PANEL *A* SHOWS A 40AMP FEED AND #8 CONDUCTORS TO SUB
 PANEL *B* YET THE RISER SHOWS SUB PANELS *B* WITH A
 30AMP MAIN AND #6 CONDUCTORS.
 PLEASE SEE CONDUIT SIZE ON THE PANEL *A* SHOWS A 1INCH
 CONDUIT WHEN THE RISER SHOWS 3/4INCH.
 PLEASE SEE THE RISER STILL INDICATE *OVERHEAD SVC*.
 PLEASE SEE NOTE ON RISER WHICH POINTS TO PIE FROM METER
 TO THE MAIN PANEL *A* AS FPL SERVICE. THIS CONDUIT
 AFTER ANY METERING EQUIPMENT DOES NOT BELONG TO FPL. IN
 FACT THE METER CAN AND ANYTHING ON THE LOAD SIDE OF THE
 METER CAN IS HOMEOWNER SERVICE.
 PLEASE COORDINATE ALL OF THE ABOVE.
 230.2,230.70,230.71, 240.4, 310.16, TABLE 9 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 ** PLEASE KNOW IT HAS COME TO THE ATTENTION OF THIS
 OFFICE THAT POOL EQUIPMENT WILL BE MOVING UP TO MAIN
 HOUSE. AS THIS AFFECT NOT ONLY THE LAYOUT OF PLANS, IT
 MAY CERTAINLY AFFECT HOW THE ELECTRICIAN WILL FEED
 EQUIPMENT. IT JUST MAY NOT BE FED FROM THE PANEL *B*
 WHICH IS AT THE GARAGE.
  
 **PLANS ROUTED BACK TO THE BUILDIGN REVIEWER AT THE
 OWNER'S REQUEST.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-12 Cont ID  
Sent By mperson Date 2008-06-09 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2008-06-12 Time 16:35 Sent To B
Notes
2008-06-12 16:35:39** REDLINED PLANS **
  
 1) NOTE: RESPONSE FOR OWNER BUILDER COMMENT AS THIS
 DOES NOT APPEAR TO BE PRIMARY RESIDENCE MENTIONS THE
 PROJECT WILL CHANGE TO CONTRACTOR HOWEVER NO CHANGE OF
 CONTRACTOR WAS SUBMITTED OR PERMIT APPLICATION FOR NEW
 CONTRACTOR WAS SUBMITTED.
 PLEASE SEE FS 489 AS THIS RESIDENCE IS REQUIRED TO BE
 FOR THE OWN USE AND OCCUPANCY OF THE OWNER BUILDER.
 THIS MAY BE VERIFIED BY THE LICENSING BOARD AND PALM
 BEACH COUNTY.
  
 2) NOTE: GARAGE PANEL IS SHOWN AS EXISTING AND IS NOT
 IN SCOPE OF WORK. THE PANEL SHALL BE VERIFIED TO MEET
 225.31-225.39, 250.32 AND 250.50 AS NEW FUTURE
 ELECTRICAL WILL BE GETTING FED FROM THIS EQUIPMENT.
 THE PERMIT FOR THE SWIMMING POOL WAS ALREADY APPLIED
 FOR AND PLANS DO NOT COORDINATE FOR BOTH APPLIED.
  
 3) NOTE: PANEL SCHEDULE ONLY LIST ARC FAULT PROTECTION
 FOR RECEPTACLES. CODE SECTION210.12 OF THE 2005 NEC
 REQUIRED THE PROTECTION OF ALL OUTLETS IN DWELLING UNIT
 SLEEPING ROOMS.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
2008-06-03 18:57:062008-06-03 18:57:06
  
 SENT TOLUIS MARTINEZ TO ROUTE TO OTHER TRADES FIRST.
 ROUTE BACK TO ELEC WHEN OTHERS ARE DONE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-08 Cont ID  
Sent By dpalmer Date 2008-04-08 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2008-04-08 Time 16:22 Sent To M
Notes
2008-04-08 16:22:54** DENIED REVIEW**
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 FBC 106.1.2, 106.3.5, FS 553.73 FOR INFORMATION
 REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS PLANS SHOW
 SMOKE DETECTION DEVICES AS *SMOKE DETECTORS*. SMOKE
 DETECTORS ARE DEVICES WHICH ONLY DETECT AND DO NOT
 SOUND AN ALARM. PLEASE SEE NFPA72 AS * SMOKE ALARMS ARE
 DEVICES WHICH DETECT AND SOUND AN ALARM. IF THESE ARE
 SMOKE DETECTORS PLEASE INCLUDE THE REMAINDER OF THE
 SYSTEM SUCH AS HORN DEVICES, FIRE ALARM PANEL ETC. IF
 THESE ARE DEVICES WHICH ARE INDEED DEVICES WHICH DETECT
 AND SOUND AN ALARM PLEASE ADJUST DESIGNATIONS. PLEASE
 SEE THE NEXT COMMENT FOR ALL LOCATIONS.
  
 3) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1,
 11.8.3 AS THE EXISTING DWELLING SHALL ALSO CONTAIN
 HARDWIRED DEVICES BEING BROUGHT UP TO THE CURRENT
 NFPA-72.
 PLEASE SHOW ALL LOCATIONS MEETING EXISTING MEETING CODE
 OR NEW TO BE INSTALLED.
  
 4) NOTE: PLEASE VERIFY THE SCOPE OF WORK AS APPLIED AND
 SHOWN ON PLANS. FOR EXAMPLE: ELECTRICAL PLANS SHOWS GAS
 GENERATOR, AND OTHER ITEMS WHICH NO INFORMATION,
 ELECTRICAL OR OTHER WISE WAS SUBMITTED. IF THE
 GENERATOR IS TO BE IN THE SCOPE OF WORK, PLEASE
 COMPLETE PLANS ACCORDINGLY AND SUBMIT MANUFACTURES
 SPECS/CUT SHEETS ON NEW TRANSFER SWITCH AND GENERATOR.
 PLEASE ADJUST RISER, SITE PLANS, ETC.
 AS THE PLANS ARE NOT COMPLETE FOR THESE OTHER ITEMS, NO
 REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME.
 110.3, 90.7, 702.5, 240.4, 310.16 ETC.
 FBC 106.3.5.4, 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE MISSING INFORMATION ON REQUIRED
 FEED TO GARAGE WITH FEEDERS, LIGHTS, GFI ETC.
 PLEASE SEE NEC 2005. 310.16, 215.5, 250.32,
 225.31-225.39, 210.8A, 210.52G ETC
 THE LOAD SCHEDULE NOW SHOWS ALL CIRCUITS TO DETACHED
 BUILDING AND EQUIPMENT AS SEPARATE FEEDS HOWEVER THIS
 DOES NOT COMPLY WITH THE MINIMUM REQUIRED PER
 225.31-225.39 AND 250.32, 250.50.
  
 6) NOTE: PLEASE BE SURE TO SHOW THE LOCATION OF THE CU
 ON ELECTRICAL PLANS INCLUDING DISCONNECT PER 440.11.
 THE ELECTRICAL PLANS APPEAR TO SHOW SOME SORT OF
 DISCONNECT HOWEVER THE LOCATION OUTSIDE THE BATHROOM
 DOES NOT COORDINATE WITH THE MECHANICAL PLANS
 SUBMITTED.
 210.63, 210.8A, 440.11
  
 7) NOTE: PLEASE SUBMIT A PANEL SCHEDULE SHOWING ALL
 MINIMUM AND OTHER BRANCH CIRCUITS PER 408.4, 310.16,
 240.4.
 FBC 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE SPACING IN NEW
 BEDROOM REQUIRED WITHIN 6FT OF DOOR PER 210.52.
  
 9) NOTE: PLEASE SEE 210.52D AS THE REQUIRED GFI IN NEW
 BATH SHALL BE WITHIN 3FT OF SINK/LAVATORY EDGE. THIS
 DOES NOT PERMIT CROSSING OVER OF SINK TO GAIN ACCESS TO
 GFI RECEPTACLE.
 PLEASE RELOCATE OR ADD ADDITIONAL GFI.
  
 10) NOTE: PLEASE SEE 210.8A7 AS ALL 15/20AMP 120V
 RECEPTACLES WITHIN 6FT OF LAUNDRY SINK SHALL BE GFI/GFI
 PROTECTED. THIS INCLUDES DEDICATED CIRCUITS SUCH AS
 WASHER. THIS WAS A CHANGE IN THE 2005 NEC.
  
 11) NOTE: PLEASE SEE 210.11C2, 220.52B AS THE LAUNDRY
 AND WASHER LOADS SHALL BE 1500VA MIN.
  
 12) NOTE: PLEASE SEE THE LOAD SCHEDULE SHOWS ONLY ONE
 CIRCUIT AS *EXISTING* AND IF OTHER CIRCUITS ARE NOT
 SHOWN AS *EXISTING* IT WOULD AUTOMATICALLY BE *NEW*
 HOWEVER THE ELECTRICAL PLANS DO NOT ANY OTHER
 ELECTRICAL ITEMS SUCH AS KITCHEN ETC AS NEW?
 PLANS ARE NOT CLEAR WITH COMPLETE SCOPE OF WORK.
  
 13) NOTE: NOTE FOR INFORMATIONAL PURPOSE TO
 OWNER/BUILDER APPLICANT.FS 489 REQUIRES LOCATION TO
 BE OWNER OCCUPIED FOR OWN USE AND OCCUPANCY. PALM BEACH
 COUNTY PROPERTY APPRAISER OFFICE INDICATES MULTIPLE
 PROPERTIES INCLUDING SEPARATE PROPERTY AS HOMESTEAD.
 THIS WAS NOTED FOR INFORMATIONAL PURPOSE ONLY AS
 APPLICANT MUST USE THIS LOCATION FOR OWN USE AND
 OCCUPANCY.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-04-03 Cont ID  
Sent By swurafti Date 2008-04-03 Time 16:53 Rev Time 0.00
Received By swurafti Date 2008-04-03 Time 16:53 Sent To  
Notes
2008-04-03 16:53:47HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-06 Cont ID  
Sent By shill Date 2008-10-06 Time 16:43 Rev Time 0.00
Received By shill Date 2008-10-06 Time 16:43 Sent To E
Notes
2008-10-06 16:44:09TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 12:37 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 12:37 Sent To M
Notes
2008-09-30 12:38:57TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 10:42 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 10:42 Sent To E
Notes
2008-09-18 10:42:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 14:53 Sent To B
Notes
2008-09-16 14:55:17TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-09 Cont ID  
Sent By adarroug Date 2008-09-09 Time 08:30 Rev Time 0.00
Received By adarroug Date 2008-09-09 Time 08:30 Sent To Z
Notes
2008-09-09 08:30:42TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 15:47 Sent To Z
Notes
2008-06-25 15:47:39TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 14:31 Sent To Z
Notes
2008-05-23 14:31:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 14:29 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 10:58 Sent To  
Notes
2008-04-04 10:58:29TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-02 Cont ID  
Sent By tgordon Date 2008-10-02 Time 08:59 Rev Time 0.30
Received By tgordon Date 2008-10-02 Time 08:58 Sent To  
Notes
2008-10-02 08:58:59REVISION TO MECHANICAL PLAN.
  
 *** PROVISO ***
 1) RETURN AIR DUCTS MUST BE ATTACHED TO THE AIR HANDLER
 UNIT TO PREVENT AIR HANDLER FROM DRAWING AIR FROM THE
 BATHROOM, PER 2004 FBC/R M1602.2 (4).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-26 Cont ID  
Sent By tgordon Date 2008-06-26 Time 14:54 Rev Time 0.30
Received By tgordon Date 2008-06-26 Time 14:54 Sent To B
Notes
2008-06-26 14:55:28REVIEWED AND STAMPED ON 4-9-08.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-06 Cont ID  
Sent By tgordon Date 2008-06-06 Time 08:01 Rev Time 0.20
Received By tgordon Date 2008-06-06 Time 08:01 Sent To P
Notes
2008-06-06 08:02:07REVIEWED AND STAMPED ON 4-9-08.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By tgordon Date 2008-04-09 Time 13:29 Rev Time 0.30
Received By tgordon Date 2008-04-09 Time 13:29 Sent To P
Notes
2008-04-09 13:33:42*** PROVISO ***
 1) RETURN AIR DUCT MUST BE ATTACHED TO THE AIR HANDLER
 UNIT TO PREVENT AIR HANDLER FROM DRAWING AIR FROM THE
 BATHROOM, PER 2004 FBC/R M1602.2 (4).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By mperson Date 2008-06-09 Time 08:29 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 08:21 Sent To B
Notes
2008-06-09 08:24:19****************PROVISO****************
 THE TWO-WAY CLEANOUT AT THE JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER SHALL BE 5 FEET OR CLOSER TO
 THE BUILDING. PER FBC-2004 PLUMBING SECTION 708.3.5.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By mperson Date 2008-04-14 Time 08:05 Rev Time 0.00
Received By mperson Date 2008-04-14 Time 08:05 Sent To B
Notes
2008-04-14 11:33:54PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLARIFY THE SCOPE OF WORK. THE PERMIT
 APPLICATION INDICATES "ADDITION TO EXISTING HOME",
 HOWEVER SHEET E-1.0 IS INDICATING A GAS GENERATOR BY
 THE EXISTING GAS WATER HEATER WITH NO INFORMATION. IF
 IT IS THE INTENT TO HAVE THE GENERATOR IN THE SCOPE OF
 WORK, PLEASE CLEARLY INDICATE THIS AND COMPLETE THE
 PLANS ACCORDINGLY AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS/CUT SHEETS ON THE GENERATOR CLEARLY
 INDICATING THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY AS WELL AS THE FOLLOWING INFORMATION FOR THE
 GAS SYSTEM (OR DELETE THE GENERATOR FROM PLANS).
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 C. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (THIS INCLUDES THE EXISTING GAS SYSTEM)
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (THIS INCLUDES THE
 EXISTING GAS SYSTEM)
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 LP GAS SPECIFY .5 PSI, 2 PSI OR 10 PSI .
  
 2. SITE PLAN ARCHITECTURAL NOTES, PLUMBING GENERAL
 NOTES (7): AIR CHAMBERS ARE NOT APPROVED BY THE FBC
 PLUMBING SECTION 604.9 WATER HAMMER. HOWEVER IF IT IS
 THE INTENT TO USE AIR CHAMBERS THEY SHALL BE INSTALLED
 PER "STANDARD PDI-WH 201" WITH A RECHARGABLE TYPE OF
 AIR CHAMBER (DETAIL REQUIRED) OR DELETE AIR CHAMBERS
 FROM PLANS.
  
 3. SHEET A-3.0 ROOF PLAN ROOF DRAINAGE CALCULATIONS
 APPEAR TO BE WRONG FOR EACHROOF AREA. AREA #1 & #2 ONLY
 HAVE 48 SQUARE INCHES OF PROVIDED SCUPPER. AREA #3
 SHOULD NOT HAVE ANY SCUPPERS. SQUARE FOOTAGE FOR AREA
 #2 APPEARS WAY TO LOW, THIS ROOF AREA IS RECIEVING ALOT
 MORE THAN THE INDICATED 207 SQ. FT. PLEASE CLEARLY
 IDENTIFY EACH SCUPPER WITH INDIVIDUAL SQUARE FOOTAGE
 AND VERTICAL WALL CALCULATIONS FOR EACH SCUPPER. PER
 FBC PLUMBING SECTION1101.1 SCOPE, 1101.7 ROOF DESIGN,
 AND 1106.4 VERTICAL WALLS.
  
 4. SHEET A-3.0 ROOF PLAN: PLEASE CLEARLY IDENTIFY ALL
 "UNDERCUT PARAPET FOR DRAINAGE", ONE IS NOT IDENTIFIED
 FROM AREA 1 TO AREA 2. PER FBC PLUMBING SECTION 1101.1
 SCOPE.
  
 5. SHEET A-3.0 ROOF PLAN: SECONDARY ROOF DRAINAGE IS
 REQUIRED. PER FBC PLUMBING SECTION 1107.1 SECONDARY
 DRAINAGE REQUIRED. THE SECONDARY ROOF DRAINAGE SYSTEM
 SHALL BE SEPERATE FROM THE PRIMARY ROOF DRAINAGE
 SYSTEM. PER FBC PLUMBING SECTION 1107.2 SEPERATE
 SYSTEMS REQUIRED.
  
 6. SHEET A-3.0 ROOF PLAN: DRAINAGE FOR THE SCUPPERS
 SHALL DRAIN A MINIMUM OF 1 FOOT AWAY FROM BUILDING
 STRUCTURE. PER FBC BUILDING SECTION 1503.6 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7. SHEET S-1.0 PART. PLUMBING RISER UTILITY: CLEARLY
 IDENTIFY THE TRAP FOR THE WASHING MACHINE AS BEING 2
 INCH. PER FBC PLUMBING SECTION 406.3 WASTE CONNECTION.
 A 3 INCH CLEANOUT IS REQUIRED FOR THE WASHING MACHINE
 DRAINAGE STACK PER FBC PLUMBING SECTION 708.7 MINIMUM
 SIZE. THE CLEANOUT SHALL BE LOCATED AT 4 FEET ABOVE
 FINNISH FLOOR. PER FBC PLUMBING SECTION 708.9 ACCESS.
  
 8. SHEET S-1.0 PLUMBING RISER DIAGRAM: A TWO-WAY
 CLEANOUT SHALL BE LOCATED AT THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PLUMBING
 SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-09-10 Cont ID  
Sent By mcruz Date 2008-09-10 Time 13:28 Rev Time 0.00
Received By mcruz Date 2008-09-10 Time 13:28 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-26 Cont ID  
Sent By choops Date 2008-06-26 Time 14:06 Rev Time 0.00
Received By choops Date 2008-06-26 Time 13:52 Sent To M
Notes
2008-06-26 14:06:52***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-03 Cont ID  
Sent By choops Date 2008-06-03 Time 10:45 Rev Time 0.00
Received By choops Date 2008-06-03 Time 10:45 Sent To E
Notes
2008-06-03 11:08:24***FAILED - RESUB #1***
  
  
 1)A/C EQUIPMENT LOCATION DOES NOT MATCH BETWEEN THE
 SITE PLAN AND FLOOR PLAN/ELECTRIC PLAN.PLEASE
 CLARIFY.
  
 2)NOTE NEW POLICY CHANGE:DRIVEWAY MUST OBTAIN A
 SEPARATE PERMIT, AND SHALL BE REMOVED FROM THESE
 PLANS.
  
 FYI:THE DRIVEWAY AS PROPOSED DOES NOT COMPLY WITH
 SECTION 94-482 OF THE ZLDRS: REQUIRED OFF-STREET
 PARKING SPACES FOR LESS THAN FOUR RESIDENTIAL DWELLING
 UNITS SHALL BE LOCATED ON THE PROPERTY ON WHICH THE
 UNITS ARE CONSTRUCTED. REQUIRED PARKING MAY BE LOCATED
 IN A FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE
 FEET OR 75 PERCENT OF THE FRONT YARD AREA MUST BE
 LANDSCAPED. PARKING AREAS LOCATED IN THE FRONT YARD
 SHALL BE SURFACED WITH A SMOOTH, NONDUSTING SURFACE IN
 COMPLIANCE WITH SUBSECTION 33-485(E). IT SHALL BE A
 VIOLATION OF THIS CHAPTER TO PARK ON ANY UNPAVED AREAS
 AS DESCRIBED IN THIS ARTICLE.***THE TOTAL ALLOWABLE
 IMPERMEABLE SURFACE (EXISTING AND PROPOSED) WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO FRONT OF
 BUILDING) OF THIS PROPERTY SHALL NOT EXCEED 305 SQUARE
 FEET.
  
 3)SITE PLAN SHALL INDICATE SETBACK DIMENSIONS FROM
 EVERYTHING PROPOSED TO ALL ADJACENT PROPERTY LINES.
  
  
 NOTE:ANY NEWLY SUBMITTED PLANS SHALL BE RESTAMPED BY
 HISTORIC PRESERVATION
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-09 Cont ID  
Sent By choops Date 2008-04-07 Time 09:28 Rev Time 0.00
Received By choops Date 2008-04-07 Time 09:28 Sent To B
Notes
2008-04-07 09:31:07***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)CLARIFY SCOPE OF WORK.PERMIT APPLICATION
 INDICATES "ADDITION TO EXISTING HOME", HOWEVER, PLANS
 SHOW PROPOSED POOL, A GENERATOR AND PROPOSED DRIVEWAY.
 IF THESE ITEMS ARE TO BE INCLUDED UNDER THIS PERMIT,
 THEY SHALL BE ADDED TO THE SCOPE OF WORK, NECESSARY
 INFORMATION PROVIDED, AND THE DECLARED VALUE ADJUSTED
 ACCORDINGLY. IF NOT, THEY SHALL BE REMOVED FROM PLANS
 OR LABELED "TO BE PERMITTED SEPARATELY."CLARIFY.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 NOTE:ANY NEWLY SUBMITTED PLANS SHALL BE RESTAMPED BY
 HISTORIC PRESERVATION
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK