Plan Review Details - Permit 08040097
Plan Review Stops For Permit 08040097
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-23 Cont ID  
Sent By jwitmer Date 2008-04-23 Time 07:32 Rev Time 3.33
Received By jwitmer Date 2008-04-23 Time 07:32 Sent To  
Notes
2008-04-23 07:34:42BUILDING PLAN REVIEW
 PERMIT: 08040097
 ADD: 4720 N BROADWAY
 CONT: NUNNO BUILDERS
 TEL: (954)961-0777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS PLEASE
 CORRECT THE PLANS NOW INDICATE THE 2006 SUPPLEMENTS.
  
 1F) PLANS FAIL TO MENTION THE DESIGN REQUIREMENTS OF
 THE EXISTING BUILD
 ING CODE, 2004 WITH 2007 SUPPLEMENTS.
  
 1G) PLANS INDICATE THIS TO BE A TYPE III BUILDING. THE
 RESPONSE SHEET INDICATES THE PLAN WAS CHANGED TO A V-B,
 BUT THEY CLEARLY STATE TYPE III BUT DO NOT INDICATE A
 OR B? TABLE 503, TABLE 601.
  
 1H)PLANS ALSO INDICATE THIS TO BE A LEVEL I
 ALTERATION. PLEASE SEE THE EXISTING BUILDING CODE
 SECTION 305, LEVEL 3 APPLY WHERE THE WORK AREA EXCEEDS
 50 PER CENT OF THE AGGREGATE AREA OF THE BUILDING AND
 MADE WITHIN ANY 12-MONTH PERIOD.
  
 2) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: A)
 EFIS WALL SYSTEMS MISSING THE FLORIDA COVER SHEET/
 DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP IS REQUIRED, 2 SETS OF
 PRODUCT APPROVALS ONLY ONE SUBMITTED.
  
 B) TRUSS ANCHORS NONE SUBMITTED WILL REQUIRE THE
 FLORIDA COVER SHEET/ DESIGNER OF
 RECORD APPROVALWITH SHOP DRAWING STAMP.
  
 C) ROOFING ASSEMBLIES- NONE SUBMITTED,THE FLORIDA
 COVER SHEET/ DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP. SUBSYSTEMS ARE NOT
 HIGHLIGHTED. WILL REQUIRE ENHANCED
 FASTENING IN ZONES 2 & 3. PROVIDE RAS 117
 CALCULATIONS PER LIMITATION# 7.
  
 D) FIXED/ STOREFRONT WINDOWS-NONE WERE SUPPLIED.
 PROVIDETHE FLORIDA COVER SHEET/ PRODUCT TESTING
 SHEETS & DESIGNER OF RECORD APPROVALWITH SHOP DRAWING
 STAMP.
  
  
 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5A) 2ND REQUEST, SHEET A-4.1 INDICATES THE FRAMING
 DETAIL FOR THE NEWLY DESIGNEDTOWER, SHEET A-4.1
 INDICATES THE NEW TOWER HAS THE CENTER OPEN AND THE
 INSIDE WALLS HAVE A MODIFIED BITUMEN ROOFING MEMBRANE,
 THERE APPEARS TO BE NO ROOF DRAIN NOR OVERFLOW SCUPPERS
 TO ALLOW THE RAIN WATER OUT OF THIS BOX LOOKING TOWER.
 HOW WILL RAIN WATER BE DRAINED?
  
 5B) SHEET A.4.0, A.4.1 & A5.0 ALL SHOW THE PARAPET
 DETAILS, BUT NONE INDICATE HOW THE PARAPET WILL BE
 ATTACHED TO THE EXISTING STRUCTURE? 106.1.2*/ 1609 HOW
 WILL THE MOMENT OF OVERTURNING BE RESTRICTED?
  
 6) NOTE:COMPLIED CANOPY AND AWNINGS TO BE UNDER A
 SEPARATE PERMIT.A LETTER FROM THE OWNER (NOT TENANT)
 IS TO ACCOMPANY ALLFABRIC OR MEMBRANE-COVERED
 STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY
 MEMBRANE OR FABRIC TO ACKNOWLEDGE THEIR RESPONSIBILITY
 TO HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND
 EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER.
 THE LETTER MUST BE SIGNED BY THE OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 7)SHEET A-4.1 WALL SECTION D AT CUPOLA,PLEASE
 CORRECT NOTATION TO DESIGN OF AWNING TO FBC CHAPTER
 43NOTE TO WHICH DESIGN THIS FABRIC CUPOLA WILL BE
 DESIGNED TO, 3105.4.2.1 OR 3105.4.2.2,
  
 A LETTER FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY
 ALLFABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO
 ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING
 COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED
 WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER MUST BE
 SIGNED BY THE OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By dpalmer Date 2008-04-09 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2008-04-09 Time 10:40 Sent To  
Notes
2008-04-09 10:40:33** DENIED REVIEW**
  
 ** PLEASE SEE SOME NOTES UNDER PREVIOUS EXPIRED PERMIT
 APPLICATION WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 FBC 106.1.2, 106.3.5, FS 553.73
 FOR INFORMATION REQUIRED ON PLANS. SOME CODES MAY
 ALREADY BE ON PLANS BUT NOT ALL.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK IS
 TOO LOW. THE VALUE SHALL INCLUDE ALL EQUIPMENT, LABOR
 AND MATERIALS. FBC 108.3.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR ALL INTERIOR
 ELECTRICAL FOR NEW EQUIPMENT LIGHTING ETC. THE SCOPE OF
 WORK FOR EQUIPMENT ETC WILL NEED ELECTRICAL TO BE
 SHOWN.
  
 2) NOTE: PLEASE SEE PLANS NEED TO COMPLY WITH FBC
 CHAPTER 13, 13-415.2, 13-415.2.ABC.1.1, .1. AND .1.3.
 PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 3) NOTE: PLEASE SEE 210.8B2 AS GFI/GFI PROTECTION IS
 REQUIRED FOR ALL 15/20AMP 120VRECEPTACLES.
 PLEASE LIST/SHOW ALL CIRCUITS.
  
 4) NOTE:PLEASE SEE 700.12F FOR ANY EMERGENCY AND EXIT
 LIGHTS SHALL BE CIRCUITED TO LOCAL BRANCH CIRCUIT.
  
 5) NOTE: IF THE SCOPE OF WORK IS THAT OF OTHER RECENT
 KFC REMODELS FOR KITCHENS ETC, PLANS WILL NEED TO SHOW
 PANELS, LOADS, CIRCUITING ETC.
 ***PLEASE KEEP THIS IN MIND.
  
 6) NOTE: PLEASE SUBMIT TWO COMPLETE SETS FOR NEW SCOPE
 OF WORK.THREE SETS WERE SUBMITTED HOWEVER TWO OF
 THOSE WERE OLD WITH VOID STAMPS.
 106.1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 11:51 Rev Time 0.00
Received By mawillia Date 2008-04-24 Time 11:00 Sent To  
Notes
2008-04-24 11:32:31*****UNSAT*****
  
  
 1.THE ADDRESS SHOWN IN THE TITLE BLOCK OF SHEET T-1
 OF 4720 NORTH BROADWAY IS INCORRECT; SHOULD BE 4720
 BROADWAY.
  
 2.ON THE SITE PLAN (SHEET C-1) WHAT DOES FNA 7TH
 AVENUE IN PARENTHESES UNDER 47TH STREET PERTAINS TO.
  
 3.SHOW LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATISFY THE 75' TRAVEL DISTANCE.
  
 ATTENTION:PLAN SHEETS A-1.0, A--3.1, AND E-1.0 TO BE
 FIRE STAMPED WHEN THE ABOVE COMMENTS AS WELL AS THE
 OTHER REVIEWERS COMMENTS HAVE BEEN SATISFIED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 11:52 Rev Time 0.00
Received By mawillia Date 2008-04-03 Time 11:52 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By rkussner Date 2008-04-14 Time 13:32 Rev Time 0.00
Received By rkussner Date 2008-04-14 Time 13:32 Sent To  
Notes
2008-04-14 13:34:08PLANNING AND ZONING DEPARTMENT
 LANDSCAPE COMMENTS
 ***FAILED*** CONTACT ROBERT KUSSNER @ 822-1462.
  
 1. LIMIT THE AISLE WIDTH INTO THE SITE FROM BROADWAY TO
 20 FEET.REMOVE THE BALANCE OF PAVEMENT ON BOTH SIDES
 OF THE AISLE AND CONVERT INTO A LANDSCAPE AREA.THE
 HEDGE SHALL EXTEND ALONG THE INTERIOR PERIMETER OF THE
 LANDSCAPE STRIP WITH GROUND COVER PLANTED ON THE STREET
 SIDE OF THE HEDGE.
  
 2. PROVIDE SOD AND IRRIGATION IN THE RIGHT-OF-WAY,
 ADJACENT TO 47TH STREET. ALL EXISTING TREES TO REMAIN
 IN THE RIGHT-OF-WAY OR ANYTHING TO BE PLANTED NEEDS
 APPROVAL FROM THE CITY ENGINEERING DEPARTMENT.
  
 3. THE SYMBOL ?SEA? WAS USED ON THE PLAN BUT THERE WAS
 NO REFERENCE TO IT ON THE PLANT LIST.PLEASE CLARIFY.
  
 4. ALL EXISTING TREES AND PLANT MATERIAL TO BE SAVED OR
 RELOCATED SHALL BE FLORIDA NUMBER 1 GRADE OR BETTER.
 OTHERWISE, IT SHALL BE REPLACED.
  
 5. VISION OBSCURING GATES ARE REQUIRED FOR THE DUMPSTER
 ENCLOSURE.ALL OTHER MECHANICAL EQUIPMENT IS REQUIRED
 TO BE SCREENED.
  
 6. IN KEEPING WITH ?XERISCAPE? STANDARDS, PLEASE
 CONSIDER THE USE OF GROUND COVER INSTEAD OF SOD TO BE
 PLANTED BETWEEN THE PARKING LOT OR SIDEWALK AND THE
 PERIMETER HEDGE.THIS WILL REDUCE MAINTENANCE AND
 WATER.
  
 7. SIX INCH CONCRETE, NON-MOUNTABLE CURBING KNOWN AS
 ?TYPE D? IS REQUIRED TO SEPARATE ALL LANDSCAPED AREAS
 FROM ADJACENT VEHICULAR USE AREAS.
  
 8. SITE LIGHTING AND OTHER UTILITIES SHALL NOT BE IN
 CONFLICT WITH PROPOSED LANDSCAPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By kstevens Date 2008-04-17 Time 08:14 Rev Time 0.00
Received By kstevens Date 2008-04-17 Time 08:14 Sent To  
Notes
2008-04-17 09:06:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT L-2 INDICATES IRRIGATION WORK. NO IRRIGATION
 WORK IS INDICATED ON THE PERMIT APPLICATION. PLEASE
 INDICATE THE EXTENT OF THE INTENDED IRRIGATION WORK.
 WILL THIS BE A NEW SYSTEM? WILL THE SYSTEM, IF
 EXISTING, BE ENLARGED, ALTERED, MOVED OR DEMO'D? PLEASE
 CLARIFY. IF THE SYSTEM IS NEW, PLEASE SHOW THE LOCATION
 OF THE WATER SOURCE, (METER OR WELL), THE BACKFLOW
 PREVENTER IF CITY WATER, THE CONTROLLER & THE RAIN
 SENSOR. SECTIONS 105.1, 106.1.1, 106.1.2, 608 & FS
 373.62.
  
 2. SHT A1.0 BOTH TOILET ROOMS SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTIONS 1104.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS FOR BOTH TOILET ROOMS.
 SECTION 11-4.1.6(1)(B). (DOOR SHALL NOT SWING OPEN INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SECTION
 11-4.22.2(1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By adavila Date 2008-04-14 Time 13:10 Rev Time 0.00
Received By adavila Date 2008-04-07 Time 18:11 Sent To L
Notes
2008-04-14 13:11:54PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT - PROVIDE A PHOTOMETRIC PLAN SHOWING
 GLARE DIMENSIONS AT AND BEYOND THE EAST PROPERTY LINE.
 PLEASE NOTE THAT PER SECTION 94-310(D), GLARE SHALL NOT
 EXCEED 0.5 FOOT CANDLE AT OR BEYOND THE EASTERN
 PORTION.
  
 2. REPEAT COMMENT - PURSUANT TO FIGURE XIV-2, WHEEL
 STOPS SHALL BE 2 FEET FROM THE CURB TO THE BACK OF THE
 WHEEL STOP.THE SITE PLAN STILL SHOWS 2 FEET FROM THE
 CURB TO THE FRONT OF THE WHEEL STOP.
  
 3. (PARTIAL COMMENT) - A LANDSCAPE PLAN PREPARED,
 SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT,
 AND MEETING THE LANDSCAPE PROVISIONS SER OUT IN ARTICLE
 XIV OF THE ZLDRS, SHALL BE PROVIDED.
  
 A. REPEAT COMMENT - PURSUANT TO SECTIONS 94-443(A), (B)
 AND (C)(2), A MINIMUM 5 FOOT LANDSCAPE BUFFER SHALL BE
 INSTALLED AND MAINTAINED ALONG THE PERIMETER OF THE
 PROPERTY, WITH SHADE OR FLOWERING TREES PLANTED AT
 30-FOOT INTERVALS.SHADE OR FLOWERING TREES SHALL BE
 PLANTED ALONG THE NORTH AND WEST PROPERTY LINES.PER
 THE APRIL 11, 2008 MEETING, A WAIVER FROM THIS
 REQUIREMENT MAY BE APPLIED FOR THE NORTH PROPERTY LINE.
 A WAIVER MAY NOT BE APPLIED FOR THE REQUIRED
 LANDSCAPING ALONG THE WEST PROPERTY LINE.
  
 B. REPEAT COMMENT - PURSUANT TO SECTION
 94-443(C)(5)(A), LANDSCAPE AREAS SHALL BE SEPARATED
 FROM VEHICULAR USE AREAS BY NONMOUNTABLE, CONCRETE
 CURBING OF THE TYPE CHARACTERIZED AS ?TYPE D,? OR
 CURBING OF COMPARABLE DURABILITY.THIS REQUIREMENT
 DOES NOT APPLY TO AREAS WHERE THERE IS A WHEEL STOP
 BETWEEN THE PARKING SPACES AND THE LANDSCAPED AREAS.
 LABEL/IDENTIFY ALL EXISTING, AND PROPOSED, CURBS.
  
 C. PURSUANT TO SECTION 94-443(C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN 5 FEET IN WIDTH AND NOT LESS
 THAN THE LENGTH OF THE ADJACENT PARKING STALL.THE
 LANDSCAPED ISLANDS SHALL CONTAIN AT LEAST 1 SHADE OR
 FLOWERING TREE.THE PARKING ROW IN THE MIDDLE OF THE
 LOT, AND ALONG THE SOUTH PROPERTY LINE, SHALL BE
 TERMINATED WITH A LANDSCAPED ISLAND.PER THE APRIL 11,
 2008 MEETING, A WAIVER MAY BE APPLIED FOR THE MIDDLE
 PARKING ROW.
  
 D. PURSUANT TO SECTION 94-443(C)(3)(B), ONE INTERIOR
 LANDSCAPED ISLAND SHALL BE PROVIDED FOR EVERY 10
 PARKING SPACES OR PORTION THEREOF.INTERIOR LANDSCAPED
 ISLANDS SHALL CONTAIN AT LEAST ONE SHADE OR FLOWERING
 TREE.AN INTERIOR LANDSCAPED ISLAND SHALL BE PROVIDED
 ON THE PARKING ROW ALONG THE SOUTH PROPERTY LINE.PER
 THE APRIL 11, 2008 MEETING, A WAIVER MAY BE APPLIED FOR
 THIS REQUIREMENT.
  
 E. PURSUANT TO SECTION 94-443(E), AT LEAST 30 PERCENT
 OF THE LINEAR FEET AROUND THE EXTERIOR OF ALL
 COMMERCIAL STRUCTURES SHALL BE PLANTED WITH TREES,
 SHRUBS OR HEDGES.FOUNDATION PLANTING SHALL BE
 PROVIDED AROUND THE BUILDING.PER THE APRIL 11, 2008
 MEETING, A WAIVER MAY BE APPLIED FOR THIS REQUIREMENT.
  
 4. PURSUANT TO SECTION 94-221(B)(6), SIDEWALKS ALONG
 BROADWAY SHALL BE A MINIMUM OF 8 FEET IN CLEAR WIDTH.
 EXISTING SIDEWALK SHALL BE EXTENDED ONTO THE PROPERTY
 ALONG THE WEST PROPERTY LINE TO MEET THAT 8 FOOT
 MINIMUM.AN ACCESS EASEMENT SHALL BE RECORDED PRIOR TO
 OBTAINING A CERTIFICATE OF OCCUPANCY (CO).A MODEL
 ACCESS EASEMENT IS AVAILABLE FROM VINCE NOEL, CITY
 SURVEYOR.
  
 5. PROVIDE SETBACKS, DRIVEWAYS, DRIVE AISLE WIDTHS,
 PARKING SPACES WITH AND DEPTH DIMENSIONS ON THE SITE
 PLAN.
  
 6. PLEASE NOTE THE AWNING ON THE NORTH BUILDING FA?ADE
 PROJECTS OVER THE 47TH STREET ROW.APPROVAL FROM THE
 ENGINEERING SERVICES DEPARTMENT SHALL BE OBTAINED FOR
 THIS AWNING PRIOR TO SUBMITTING A BUILDING PERMIT
 APPLICATION FOR THE AWNING.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.