Plan Review Details - Permit 08040089
Plan Review Stops For Permit 08040089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-12 Cont ID  
Sent By shill Date 2008-05-07 Time 13:51 Rev Time 0.00
Received By shill Date 2008-05-07 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By shill Date 2008-04-21 Time 08:34 Rev Time 0.00
Received By shill Date 2008-04-21 Time 08:34 Sent To P
Notes
2008-04-21 08:38:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE ARCHITECTURAL QUALITY PLANS, TO SCALE, WITH
 ALL APPLICABLE DIMENSIONS, SHOWING THE SCOPE OF WORK.
 THIS SHOULD, AT A MINIMUM, INCLUDE AN OVERALL PLAN
 (SHOWING LOCATION OF PROPOSED IMPROVEMENT IN RELATION
 TO THE STRUCTURE), FLOOR PLAN, EXTERIOR ELEVATIONS.
 PROVIDE A DEMO PLAN AND PROPOSED PLAN.FBC*106.
  
 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.PROVIDE TWO SETS.
 THE INFORMATION PROVIDED IS INCOMPLETE; IT WAS A LIST
 OF PRODUCTS APPROVED BY THAT MANUFACTURER.PRINT THE
 SPECIFIC PRODUCT APPROVAL FOR THE PRODUCT YOU PROPOSE
 TO USE, ALONG WITH THE EVALUATION REPORT/INSTALLATION
 INSTRUCTIONS.
  
 3.DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA,
 FBC301.THIS SHOULD INCLUDE, AT A MINIMUM, WIND ZONE
 AND EXPOSURE CLASSIFICATION.
  
 4.IS THE EXISTING AREA UNDER AIR?SEE FBC R 303.1;
 COMPLIANCE WITH LIGHT AND VENTILATION REQUIREMENTS ARE
 NOT CLEAR BASED ON THE INFORMATION PROVIDED.
  
 5.PROVIDE INFORMATION REGARDING THE EXISTING HOUSE;
 EXISTING SQUARE FOOT AREA UNDER AIR, TOTAL SQUARE FOOT
 AREA (INCLUDING NON A/C SPACE), PROPOSED SQUARE FOOT
 AREA UNDER AIR AFTER RENOVATION, TOTAL SQUARE FOOT AREA
 AFTER RENOVATION.
  
 5.PROVIDE THE NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN ON THE PLAN.
  
 6.HOW IS ELECTRIC AFFECTED BY THIS RENOVATION?THE
 PLAN SHOULD SHOW PROPOSED ROOM DESIGNATION.
  
 7.ON THE PROPOSED PLAN, SHOW THE DOOR DIMENSION
 FBC11-11.1.OTHER INFORMATION ABOUT THE EXISTING
 BATHROOM DOORS MAY BE REQUIRED.
  
 8.PROVIDE INFORMATION ABOUT THE EXISTING WALL
 COVERING AND PROPOSED WALL COVERING.SEE FBC R702.NO
 INFORMATION WAS PROVIDED.
  
 9.PROVIDE A SITE PLAN.THE SITE PLAN SHOULD SHOW
 LOCATION OF IMPROVEMENT IN RELATION TO THE PROPERTY
 LINE.ZONING REVIEW MAY BE REQUIRED.
 10. A PREINSPECT WILL BE REQUIRED.OTHER PLAN REVIEW
 REQUIREMENTS MAY ARISE.
  
 11. PLEASE NOTE THAT ONE PURPOSE OF THE PLAN REVIEW
 CHECKLIST IS TO ASSIST IN AVOIDING DELAYS AND ISSUES IN
 THE FIELD.IT IS MY GOAL THAT ANY MAJOR CODE ISSUES
 ARISE NOW, DURING THE PLAN REVIEW/DESIGN PROCESS, TO
 ASSIST IN A CODE COMPLIANT JOB.
  
 12. BASIC PLUMBING INFORMATION MAY BE REQUIRED AS SOME
 STRUCTURAL WORK (REMOVAL AND POURING OF CONCRETE) MAY
 BE REQUIRED.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2008-05-12 Cont ID  
Sent By shill Date 2008-05-07 Time 17:35 Rev Time 0.00
Received By shill Date 2008-05-07 Time 17:35 Sent To  
Notes
2008-05-12 13:52:08THIS STOP OPENED IN ERROR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-02 Cont ID  
Sent By btrobaug Date 2008-07-02 Time 07:16 Rev Time 0.00
Received By btrobaug Date 2008-07-02 Time 07:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By btrobaug Date 2008-05-05 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2008-05-05 Time 11:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-04-21 Time 10:28 Rev Time 0.00
Received By btrobaug Date 2008-04-21 Time 10:20 Sent To M
Notes
2008-04-21 10:28:06 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).PLANS INDICATING THE SCOPE
 OF WORK MUST BE SUBMITTED WITH THE APPLICATION. 106.1
 FBC AS AMENDED.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 COMPLIANCE ON THE PLAN.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 13:27 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 13:27 Sent To P
Notes
2008-05-12 13:27:51TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 08:35 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 08:35 Sent To E
Notes
2008-05-05 08:36:29TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By shill Date 2008-04-21 Time 08:38 Rev Time 0.00
Received By shill Date 2008-04-17 Time 09:20 Sent To  
Notes
2008-04-17 09:21:02TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-06 Cont ID  
Sent By tgordon Date 2008-05-06 Time 09:02 Rev Time 0.25
Received By tgordon Date 2008-05-06 Time 09:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By tgordon Date 2008-04-21 Time 11:02 Rev Time 0.25
Received By tgordon Date 2008-04-21 Time 11:02 Sent To  
Notes
2008-04-21 11:10:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) 2004 FBC/R 303.3 REQUIRES VENTILATION FOR ALL
 BATHROOMS, PLEASE SHOW ON THE PLAN HOW THIS BATHROOM
 WILL BE VENTILATED.
  
 *** 2004 FBC/R R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M 2 ),
 ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM
 ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50
 CFM (23.6 L/S) FOR INTERMITTENT VENTILATION OR 20 CFM
 (9.4 L/S) FOR CONTINUOUS VENTILATION. VENTILATION AIR
 FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTSIDE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-14 Cont ID  
Sent By mperson Date 2008-05-14 Time 15:46 Rev Time 0.00
Received By mperson Date 2008-05-14 Time 15:45 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-05 Cont ID  
Sent By mperson Date 2008-05-05 Time 14:42 Rev Time 0.00
Received By mperson Date 2008-05-05 Time 14:42 Sent To M
Notes
2008-05-05 15:18:52PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY. NEW COMMENTS WILL BE SO NOTED FOLLOWING
 THE PREVIOUS REVIEW COMMENTS.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM OF THE
 PROPOSED BATHROOM CLEARLY INDICATING THE FIXTURES WITH
 ALL WASTE, VENTS, TRAP SIZES AND CLEANOUT LOCATIONS.
 **THE RESUBMITTED ISOMETRIC IS NOT CODE COMPLIANT AND
 DOES NOT REFLECT THE FLOOR PLAN OF THE PROPOSED
 BATHROOM. PLEASE REFERENCE THE SANITARY ISOMETRIC RISER
 DIAGRAM ATTACHED TO THESE PLUMBING COMMENTS THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. THE
 FOLLOWING ITEMS ARE NOT CODE COMPLIANT ON THE
 RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM.
  
 A} HORIZONTAL DRY VENTS ARE NOT ALLOWED. PLEASE
 REFERENCE THE YELLOW HIGH LIGHTED AREAS INDICATING
 HORIZONTAL DRY VENTS ON THE RESUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM. PER FBC-2004 PLUMBING SECTION
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 B} THE TEE FITTING ON THE WASHING MACHINE STANDPIPE
 CONNECTING TO THE 3 INCH VENT IS NOT COMPLIANT DUE TO
 THE FACT IT IS ABOVE THE WATER-SEAL OF THE TRAP AND
 WILL ALLOW SEWER GAS TO ENTER THE ROOM WHERE THE
 WASHING MACHINE IS LOCATED. PLEASE REFERENCE THE RED
 CIRCLED YELLOW HIGH LIGHTED AREA INDICATING THIS
 PROPLEM. PER FBC-2004 PLUMBING SECTION 1002.1 FIXTURE
 TRAPS.
  
 C} FLOOR PLAN IS INDICATING THE SINK FOR THE BATHROOM
 AS EXISTING. HOW IS THIS SINK EXISTING WHEN THE PERMIT
 APPLICATION STATES CONVERT UTILITY ROOM TO BATHROOM?
 THE RESUBMITTED SANITARY ISOMETRIC IS MISSING THE
 LAVATORY FOR THE PROPOSED BATHROOM. PER FBC-2004
 PLUMBING SECTION 701.1 SCOPE.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By mperson Date 2008-04-21 Time 10:00 Rev Time 0.00
Received By mperson Date 2008-04-21 Time 09:59 Sent To E
Notes
2008-04-21 10:11:12PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE TWO COPIES OF THE EXISTING AND PROPOSED
 FLOOR PLAN AND LAYOUT MINIMUM 1/8 INCH SCALE. PER
 (W.P.B.) SECTION 106 CONSTRUCTION DOCUMENTS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM OF THE
 PROPOSED BATHROOM CLEARLY INDICATING THE FIXTURES WITH
 ALL WASTE, VENTS, TRAP SIZES AND CLEANOUT LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]