Plan Review Details - Permit 08040069
Plan Review Stops For Permit 08040069
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 16:29 Rev Time 1.22
Received By jwitmer Date 2008-11-20 Time 16:29 Sent To  
Notes
2008-11-20 16:30:08BUILDING PROVISO:
 1) NOTE AWNINGS REQUIRE A SEPERATE PERMIT. A LETTER
 FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY ALL FABRIC
 OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.3105.4.2.1THE WIND DESIGN LOADS FOR
 ANY FABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 2) BUILDING PROVISO: SIGNS TO BE BY SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-18 Cont ID  
Sent By jwitmer Date 2008-06-18 Time 15:53 Rev Time 1.33
Received By jwitmer Date 2008-06-18 Time 15:53 Sent To  
Notes
2008-06-18 16:00:01BUILDING PLAN REVIEW
 PERMIT: 08040069
 ADD: 1105 N DIXIE HWY
 CONT: VENTURA CONSTRUCTION CORP
 TEL: (561)937-1850
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A-1D) COMPLIED.I
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS SHEET A0 APPLICABLE
 CODES
 INDICATES 2006 PLEASE UPDATE.
  
 1F- 1J) COMPLIED.
  
 2) COMPLIED.
  
 3) SECOND REQUEST, PLANS INDICATE THIS BUILDING TO BE
 LOCATED ON LOT# 9 BUT THE BUILDING APPEARS TO BE AS
 WIDE AS THE LOT. PLEASE PROVIDE A COPY OF A RECORDED
 UNITY OF TITLE OR SEE ZONING ON THE 5TH FLOOR FOR A
 COPY OF THE UNITY OF TITLE FORM AND RECORD IT AT THE
 CLERK OF THE COURT, UNIFYING LOTS 7, 9 & 11. UNITY OF
 TITLE. THE PROPOSED BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED
 AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE. SEE ATTACHED SHEETS FROM PAPA.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: NOTE AWNINGS REQUIRE A SEPERATE
 PERMIT. A LETTER FROM THE OWNER (NOT TENANT) IS TO
 ACCOMPANY ALL FABRIC OR MEMBRANE-COVERED STRUCTURE
 DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR
 FABRIC TO ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE
 AWNING COVER REMOVED PRIOR TO ANY WIND EVENT WITH
 PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER
 MUST BE SIGNED BY THE OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 6) BUILDING PROVISO: SIGNS TO BE BY SEPERATE PERMIT.
  
 7A) COMPLIED.
  
 7B) SECOND REQUEST, NEW PARAPET WORK, NOT INDICATING
 WIND DESIGN, PLEASE PROVIDE THE FOLLOWING WIND
 INFORMATION IF THIS IS A NEW FEATURE :
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 8) COMPLIED
  
 9) DEPENDING ON THE LAST OCCUPANCY MAY REQUIRE IMPACT
 FEE REVIEW: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-22 Cont ID  
Sent By jwitmer Date 2008-04-22 Time 08:42 Rev Time 1.55
Received By jwitmer Date 2008-04-22 Time 08:42 Sent To  
Notes
2008-04-22 09:29:38BUILDING PLAN REVIEW
 PERMIT: 08040069
 ADD: 1105 N DIXIE HWY
 CONT: VENTURA CONSTRUCTION CORP
 TEL: (561)937-1850
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS SHEET A0 APPLICABLE
 CODES
 INDICATES 2006 PLEASE UPDATE.
  
 1F) SHEET A0 APPLICABLE CODES THE FLORIDA ENERGY
 EFFICIENTY CODE IS CHAPTER 13 NOT 11, PLEASE CORRECT.
  
 1G) CHAPTER 11 IS THE FLORIDA ACCESSIBILITY CODE,
 PLEASE CORRECT.
  
 1H) SHEET A0 UNDER PROJECT SUMMARY OCCUPANCY
 CLASSIFICATION REFERENCES3051 PLEASE CORRECT.
  
 1I) SHEET A0 GENERAL NOTE 13 ALL INTRUSION PREVENTING
 DEVICES SHALL CONFORM TO CHAPTER 36 OF THE FBC, CHAPTER
 36 IS THE REFERENCE TO THE FIRE PREVENTION CODE, PLEASE
 EXPLAIN, ADDITIONAL INFORMATION REQUIED, 106.1.2.
  
 1J) SHEET A0 GENERAL NOTE 24 IMPERVIOUS MATERIALS AS
 PER SECTION 1408.2 (B) FBC, SECTION 1408.2 DEALS WITH
 THE HIGH VELOCITY HURRICANE ZONESASPHALT SHINGLES FOR
 DADE AND BROWARD COUNTIES, PLEASE CORRECT CODE
 SECTION.
  
 2) SHEET A0 PROJECT SUMMARY DECLARES THIS AS A TYPE IIA
 BUILDING AND WILL BE REVIEWED AS SUCH, THE MINIMUM
 BUILDING TYPE PER THE FBC WOULD BE 5B WITHOUT THE FIRE
 SPRINKLERS.
  
 3)PLANS INDICATE THIS BUILDING TO BE LOCATED ON LOT#
 9 BUT THE BUILDING APPEARS TO BE AS WIDE AS THE LOT.
 PLEASE PROVIDE A COPY OF A RECORDED UNITY OF TITLE OR
 SEE ZONING ON THE 5TH FLOOR
 FOR A COPY OF THE UNITY OF TITLE FORM AND RECORD IT AT
 THE CLERK OF THE COURT, UNIFYING LOTS 7, 9 & 11. UNITY
 OF TITLE. THE PROPOSED BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'.A 'UNITY OF TITLE' SHALL BE RECORDED
 AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE. SEE ATTACHED SHEETS FROM PAPA.
  
 4)PLANS INDICATE THIS BUILDING IS FIRE SPRINKLERED,
 PLEASE PROVIDE THE LAY OUT PLAN. 106.3.5(4) MINIMUM
 PLAN REVIEW CRITERIA.
  
 5)NOTE AWNINGS REQUIRE A SEPERATE PERMIT.A LETTER
 FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY ALLFABRIC
 OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 6) SIGNS TO BE BY SEPERATE PERMIT.
  
 7)SHEET A-8DETAIL# 11 IS NOT DEPICTED ON ANY FLOOR
 PLAN LAYOUT, IS THIS THE NEW DECROTIVE SOFFIT THAT THE
 PERMIT APPLICATION IS INDICATED AS NEW WORK TO BE
 COMPLETED UNDER THIS PERMIT?
 THIS SECTION MAKES IT APPEAR THIS IS A NEW FEATURE, IF
 SO PLEASE PROVIDE WHAT TYPE OF MATERIALS THIS AREA WILL
 BE CONSTRUCTED WITH. NOTE TYPEIIA NON COMBUSTIBLE
 MATERIALS. PLEASE PROVIDE THE FOLLOWING WIND
 INFORMATION IF THIS IS A NEW FEATURE :
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 8) SHEET A-8 NOTE INDICATES USE OF PLYWOOD ON THE
 INTERIOR WALLS, PLEASE REVIEW 603 NONCOMBUSTIBLES IN
 TYPE IAND II BUILDINGS.
  
 9) DEPENDING ON THE LAST OCCUPANCY MAY REQUIRE IMPACT
 FEE REVIEW: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-16 Cont ID  
Sent By dpalmer Date 2009-01-16 Time 07:58 Rev Time 0.00
Received By dpalmer Date 2009-01-16 Time 07:58 Sent To  
Notes
2009-01-16 07:58:31** REDLINED PLANS**
  
  
 1) NOTE: LIGHTING ON SHEET A-3 WAS NOT REVISED TO
 COORDINATE WITH THE ELECTRICAL PLANS FOR EXTERIOR
 LIGHTS. THE ELECTRICAL PLANS GOVERN INSTALLATION UNLESS
 REVISIONS ARE MADE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-11-18 Cont ID  
Sent By dpalmer Date 2008-11-18 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2008-11-18 Time 16:56 Sent To  
Notes
2008-11-18 16:57:08 
  
  
 ** FAILED 3RD REVIEW **
  
 ** PLEASE SEE NOTES BELOW.
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOT IN
 COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1, .1.2,
 .1.3.
 NONE SUBMITTED FOR EXTERIOR AS SHOWN ON ARCHITECTURAL
 PLANS AS WELL AS THE FIXTURE LEGEND ON THE ELECTRICAL
 PLANS.
 PLEASE SEE THE INTERIOR CALCULATIONS AS SUBMITTED ARE
 ALSO IN QUESTION. THE ALLOWANCES INCLUDING ALL FIXTURE
 VA RATINGS NEED COORDINATING. PLEASE SEE FOR EXAMPLE
 THE ELIPTIPAR FIXTURE PER THE MANUFACTURE WEBSITE
 CONTAINS 2-28W BULBS PER FIXTURE. THIS WOULD BE A TOTAL
 OF 56 VA PER FIXTURE AND PLANS SHOW A TOTAL OF TWO OF
 THESE FIXTURES. HOWEVER THE PLANS SHOW A TOTAL WATTAGE
 OF 56 FOR BOTH. THIS IS NOT POSSIBLE.
  
 ** PLEASE GO OVER ALL LIGHTING AND LIGHTING
 CALCULATIONS. BASED ON THE PLANS SUBMITTED THE DESIGN
 WATTAGES AS SUBMITTED AND SHOWN IS OVER THE ALLOWANCE
 PER THE FLORIDA BUILDING CODE SECTIONS AS GIVEN ABOVE.
 AS NO LIGHTING CALCULATIONS WERE SUBMITTED FOR REVIEW
 ONCE AGAIN FOR THE EXTERIOR LIGHTING, NO REVIEW FOR
 CODE COMPLIANCE OF THOSE ITEMS COULD BE DONE.
 PLEASE CALL TO GO OVER ANY OF THESE.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B). AS A STATUTORY
 REQUIREMENT WHEN PLANS HAVE REPEAT COMMENTS FOR CODE
 COMPLIANCE WITH THE SAME SPECIFIC CODE SECTION GIVEN
 THREE OR MORE TIMES. THE STATUTE AS STATED REQUIRES A
 4X FEE FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT
 FEE TO BE ASSESSED. THIS FEE IS NOT AN OPTIONAL FEE OF
 THE BUILDING OFFICIAL TO BE ASSESSED, IT IS A REQUIRED.
 THE BASE PERMIT FEE NOT INCLUDING FIRE REVIEW, TRAINING
 SURCHARGE FEE ETC IS $1,050. THE PLAN REVIEW PORTION OF
 THIS BASE FEE IS 30% (PERCENT) TIMES FOUR AS REQUIRED
 PER SECTION OF STATUTE GIVEN. THIS IS $315.00 TIMES
 FOUR WHICH IS $1,250.
  
 ** THE 10 PERCENT RE-SUBMITTAL FEE WILL NOT BE
 REQUIRED.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 16:29 Sent To  
Notes
2008-06-20 16:29:45** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED SETS OF PLANS ARE
 INCOMPLETE FOR FULL CODE COMPLIANT REVIEW. PLEASE SEE
 SHEET E-2 IS MISSING FROM ALL THREE SETS SUBMITTED.
 FBC 106.1
  
 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS SUBMITTED DO NOT MEET 13-412.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE TO GO OVER ALL LIGHT FIXTURES INSIDE AND
 OUTSIDE BUILDING AND SUBMIT IN THE LIGHTING PERFORMANCE
 CALCULATIONS. PLEASE BE SURE TO SEE THE SECTION ABOVE
 AND TAKE A LOOK AT REQUIREMENTS FOR HID FIXTURES,
 INCANDESCENT, AND TRACK LIGHTING ALLOWANCE AND MINIMUM
 REQUIRED TO BE FIGURED.
 PLEASE BE SURE LIGHTING ON CALCULATIONS FOR WATTAGES,
 TYPES, NUMBERS ETC COORDINATES WITH PLANS AND WITH THE
 LIGHTING FIXTURE LEGEND.
  
 3) NOTE: IT IS UNCLEAR IF OTHER PERMIT HAS BEEN VOIDED
 AT THIS TIME WHICH HAD APPLIED FOR SAME SCOPE OF WORK.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By dpalmer Date 2008-04-09 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2008-04-09 Time 09:03 Sent To  
Notes
2008-04-09 09:03:36** DENIED REVIEW**
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 PLEASE SEE COVER SHEET MENTIONS FLORIDA ENERGY CODE PER
 CHAPTER 11 AND 13. CHAPTER 11 OF THE FBC IS FOR
 ACCESSIBILITY/ ADA.
 FBC 106.1.2, 106.3.5, FS 553.73 FOR INFORMATION
 REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE PLANS NEED TO COMPLY WITH FBC
 CHAPTER 13, 13-415.2, 13-415.2.ABC.1.1, .1. AND .1.3.
 PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS.THE LIGHTING CALCULATIONS SUBMITTED ARE
 NOT CODE COMPLIANT AND ARE NOT POSSIBLE AS SHOWN.
 FOR EXAMPLE: PLEASE SEE TABLE SHOWS 38-32W FIXTURES.
 HOW IS THIS POSSIBLE WHEN SEVERAL FIXTURES ARE 96VA OR
 MORE? PLEASE SEE FIXTURES A1, A1PP ETC.
 PLEASE SPECIFICALLY SEE SECTION 13-415.2.ABC.1.1 AS
 NOTED ABOVE FOR TRACK LIGHTING ALSO.
  
 ** THE EXAMPLE ABOVE IS ONE EXAMPLE AND IS IN NO WAY
 ALL ITEMS WHICH NEED TO BE ADDRESS WITH RESPECT TO
 LIGHTING PERFORMANCE CALCULATIONS AND IS NOT AN
 EXHAUSTED LIST.
  
 3) NOTE: PLEASE SEE 210.8B2 AS GFI/GFI PROTECTION IS
 REQUIRED FOR ALL 15/20AMP 120VRECEPTACLES.
 PLEASE LIST/SHOW ALL CIRCUITS.
  
 4) NOTE: PLEASE VERIFY SERVICE AS THE PANELS ARE
 SHOWING THESE AS 5-PHASE BASED ON PANELS SHOWN ON RISER
 DIAGRAM. THIS IS NOT POSSIBLE AND MUST BE SOME SORT OF
 MIS-PRINT.
 PLEASE ALSO CLARIFY OTHER DESIGNATIONS SHOWN ON THE
 PANELS ON RISER.
  
 5) NOTE: PLEASE KNOW THAT AN APPLICATION WAS MADE FOR
 SIMILAR SCOPE OF WORK ON 2007. ONCE PLANS ARE FOUND TO
 BE CODE COMPLIANT AND BEFORE ISSUANCE OF PERMIT THE
 PREVIOUS PERMIT #07100632PERMIT NEEDS TO BE VOIDED.
 PLEASE BE SURE LETTER IS ORIGINAL, COMPANY LETTER HEAD
 AND NOTARIZED CORRECTLY PER FS 117.05.
  
 6) NOTE: PLEASE SEE 700.12F AS THE EMERGENCY AND EXIT
 LIGHTS SHALL BE CIRCUITED TO LOCAL BRANCH CIRCUIT.
 THERE IS A * NOTE* ONPLANS WHICH MENTIONS THIS
 HOWEVER THERE IS ALSO A CONTRADICTING NOTE #8 WHICH
 SPECIFICALLY STATES TO CONNECT THESE SAME LIGHTS TO AN
 *EMERGENCY CIRCUIT WITH A LOCK ON DEVICE*.
 THIS DOES NOT MEET THE MINIMUM REQUIRED BY CODE. PLEASE
 ADJUST PLANS. PLEASE ALSO SEE NEXT NOTE:
  
 7) NOTE: PLANS ONLY INDICATE ONE EXIT SIGN AT ENTRANCE.
 PLEASE SEE NFPA-101 FOR MINIMUM FOR EXIT AND EMERGENCY
 LIGHTING REQUIRED. PLEASE SEE 7.8.1 AND 7.10
 THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULES.
 408.4.
 FBC 106.3.5.1.2
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-24 Cont ID  
Sent By mwennerg Date 2008-11-24 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2008-11-24 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-03 Cont ID  
Sent By mwennerg Date 2008-07-03 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 15:18 Sent To  
Notes
2008-07-03 15:30:04***DENIED***
  
  
 NO COMMENTS WERE ADDRESSED FROM FIRST FIRE REVIEW. THE
 FOLLOWING COMMENTS ARE TAKEN DIRECTLY FROM THAT
 REVIEW:
  
 1) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241. ADD NFPA 241TO
 APPLICABLE CODES ON SHEET A-0.
  
 2) ON SHEET A-0 UNDER THE APPLICABLE CODES, BE ADVISED
 THAT NFPA 72 IS A FIRE ALARM CODE. UNDER TYPE, CHANGE
 FROM FIRE PREVENTION TO FIRE ALARM.
  
 3) SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE STRUCTURE
 OF EXTERIOR ELEVATION WHICH FRONTS NORTH DIXIE HIGHWAY.
 AS PER WEST PALM BEACH REQUIREMENTS, THE NUMBERS SHALL
 BE NOT LESS THAN 6" IN HEIGHT, 1" IN WIDTH AND
 CONTRASTING WITH BACKGROUND. PLEASE BE ADVISED THAT
 AWNINGS, SIGNS AND /OR SECURITY SHUTTERS SHALL NOT
 OBSTRUCT VISIBILITY OF THE ADDRESS NUMBERS.
  
 4) ON SHEET A-0 IT IS STATED THAT TWO EXITS ARE
 PROVIDED, HOWEVER ONLY ONE EXIT ON THE NORTH ELEVATION
 IS SHOWN ON A-6/ LIFE SAFETY PLAN SHEET. SHOW THE
 LOCATION OF THE SECOND EXIT.
  
 5) PLEASE EXPLAIN HOW ACCESS IS MADE TO THE RECTANGULAR
 PORTION LOCATED AT THE SOUTHWEST CORNER OF THE
 STRUCTURE BEHIND THE COOLATTA/ESPRESSO STATION.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, IT WOULD BE
 HELPFUL TO PROVIDE A RESPONSE LETTER INDICATING HOW AND
 WHERE ON THE PLANS THE COMMENT WAS ADDRESSED.
  
  
 MICHAEL R. WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE ZPREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 14:49 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 13:54 Sent To  
Notes
2008-05-06 14:40:40*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO APPLICABLE CODES ON SHEET A-0
  
 2.ON SHEET A-0 UNDER THE APPLICABLE CODES, BE ADVISED
 THAT NFPA 72 IS A FIRE ALARM CODE.UNDER TYPE CHANGE
 FROM FIRE PREVENTION TO FIRE ALARM
  
 3.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE STRUCTURE
 OF EXTERIOR ELEVATION WHICH FRONTS NORTH DIXIE HIGHWAY.
 AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.PLEASE BE ADVISED THAT AWNINGS, SIGNS,
 AND/OR SECURITY SHUTTERS SHALL NOT OBSTRUCT VISIBILITY
 OF THE ADDRESS NUMBERS.
  
 4.ON SHEET A-0 IT IS STATED THAT TWO EXITS ARE
 PROVIDED, HOWEVER ONLY ONE EXIT (ON THE NORTH
 ELEVATION) IS SHOWN ON A-6/LIFE SAFETY PLAN SHEET. SHOW
 THE LOCATION OF THE SECOND EXIT
  
 5.PLEASE EXPLAIN HOW ACCESS IS MADE TO THE
 RECTANGULAR PORTION LOCATED AT THE SOUTHWEST CORNER OF
 THE STRUCTURE BEHIND THE COOLATTA/EXPRESSO STATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 15:46 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 15:46 Sent To  
Notes
2008-11-05 15:56:44TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 16:14 Sent To  
Notes
2008-05-30 16:14:43TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 09:20 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 09:20 Sent To  
Notes
2008-04-04 09:20:35SUBMITAL ROUTED TO "COMM" BD#17 W/ORIGINAL SET

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 13:56 Rev Time 0.00
Received By mawillia Date 2008-04-02 Time 17:01 Sent To  
Notes
2008-04-02 17:01:22TO "COMM" BD#17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-06-20 Cont ID  
Sent By rregueir Date 2008-06-20 Time 15:46 Rev Time 0.00
Received By rregueir Date 2008-06-20 Time 15:46 Sent To  
Notes
2008-06-20 15:47:07SCOPE OF WORK DESCRIPTION NO LONGER COVERS GRILLS OR
 DIFFUSERS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By rregueir Date 2008-04-25 Time 11:18 Rev Time 0.00
Received By rregueir Date 2008-04-25 Time 10:12 Sent To  
Notes
2008-04-25 11:17:59REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 INDICATES THAT AIR DIFFUSERS WILL BE REPLACED. PROVIDE
 A DETAIL FOR INSTALLATION OF NEW DIFFUSERS TO
 DEMONSTRATE COMPLIANCE WITH FBCM 603.5.6 AND FBCB
 13-410.1.ABC.3.3 IN ACCORDANCE WITH FBCEB 611.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-16 Cont ID  
Sent By kstevens Date 2009-01-16 Time 17:54 Rev Time 0.00
Received By kstevens Date 2009-01-16 Time 17:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-12-02 Cont ID  
Sent By kstevens Date 2008-12-02 Time 08:10 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 17:00 Sent To  
Notes
2008-12-02 08:43:44DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 SHOWS NEW HUB DRAINS, NEW FLOOR DRAIN, A NEW
 FIXTURE AND NEW VENT THRU ROOF. PLEASE SUBMIT A
 SANITARY RISER DIAGRAM AND IF RUN, A NEW WATER RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN FOR THE NEW
 FIXTURES. IDENTIFY ALL FIXTURES TO BE DRAINED INTO THE
 HUB DRAINS. SECTION 106.3.5.1.3.
  
 2. SHT P-1 SHOW THE PIPING TO THE LAV ON THE FLOOR PLAN
 FOR IN THE NORTHERN MOST TOILET ROOM THAT REFLECTS THE
 SANITARY RISER DIAGRAM. SECTIONS 106.1.2 & 701.1.
  
 3. SHT P-1 THE EXISTING FLOOR PLAN SHOWS 2 MOP SINKS
 AND A WATER HEATER, BUT THE NEW FLOOR PLAN DOES NOT.
 WERE THE MOP SINKS AND THE WATER HEATER DELETED? MORE
 INFORMATION IS REQUIRED. SECTION 106.1.2. IF THESE
 FIXTURES HAVE NOT BEEN DELETED, THEN PLEASE SHOW THEM
 ON THE NEW FLOOR PLAN. SECTION 106.1.1.
  
 4. SHT P-1 P TRAPS ARE REQUIRED FOR EACH OF THE HUB
 TRAPS AND THEY SHALL CONNECT DIRECTLY TO THE VENTED
 LINE. SECTIONS 802.2 & 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-02 Cont ID  
Sent By kstevens Date 2008-07-02 Time 15:39 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 15:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By kstevens Date 2008-04-16 Time 18:56 Rev Time 0.00
Received By kstevens Date 2008-04-16 Time 18:56 Sent To  
Notes
2008-04-16 18:59:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-0 APPLICABLE CODE TO REFERENCE FBC-2004
 PLUMBING.
  
 2. ALL SHEETS. THE CERTIFICATE OF AUTHORIZATION, (FIRM
 LICENSE), SHALL BE INDICATED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-07 Cont ID  
Sent By mflis Date 2008-11-07 Time 13:51 Rev Time 0.00
Received By mflis Date 2008-11-07 Time 13:51 Sent To  
Notes
2008-11-07 14:01:49ZONING REVIEW: PASSED
  
 ** SIGNAGE AND AWNINGS SHALL BE REVIEWED UNDER SEPARATE
 PERMIT AND ARE NOT INCLUDED IN THIS APPROVAL.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-14 Cont ID  
Sent By astelly Date 2008-06-14 Time 09:20 Rev Time 0.00
Received By astelly Date 2008-06-14 Time 09:20 Sent To  
Notes
2008-06-14 09:28:21AMY STELLY
 URBAN DESIGN
 822-1440
  
 REPEAT COMMENT : PLEASE SUBMIT A SURVEYAND SITE PLAN
 WHICH INCLUDES LANDSCAPING FOR REVIEW.
 THE APPROVAL OF THIS PERMITWILL NOT EXTENDED TO
 SIGNAGE OR AWNINGS. PLEASE SECURE SEPARATE PERMITS FOR
 THOSE ITEMS.
  
 PARKING MUST ALSO BE SHOWN ON THE SITE PLAN.
  
 PLEASE SEE THE NOTEBELOW REGARDING THE PROPOSED MURAL
 FOR THE BUILDING.
  
 NOTE:
 SEC. 94-410.MURALS.
 (A)A MURAL MAY BE LOCATED ANYWHERE IN THE CITY
 PROVIDED IT IS FIRST APPROVED BY PERMIT ISSUED BY THE
 CITY BUILDING OFFICIAL IN ACCORDANCE WITH THE
 PROCEDURES AND CRITERIA LISTED IN THIS SECTION. (B)
 AN APPLICATION FOR A MURAL PERMIT SHALL BE FILED WITH
 THE CITY BUILDING AND ZONING DEPARTMENT AND SHALL
 INCLUDE:
 (1)THE NAME OF THE ARTIST;
 (2)EXAMPLES OF PREVIOUS WORKS DONE BY THE ARTIST
 WITH REFERENCES;
 (3)DESCRIPTION OF THE MATERIALS TO COMPRISE THE
 MURAL AND MANNER OF APPLICATION;
 (4)A STATEMENT REGARDING THE DURABILITY OF THE
 MATERIALS CONSIDERING THE LOCATION AND POSITIONING OF
 THE MURAL; AND
 (5)PLANS AND SPECIFICATION FOR THE PROPOSED MURAL
 INCLUDING AN EXACT PICTURE, GRAPHIC OR OTHER
 DESCRIPTION.
 (C)NOT LESS THAN 15 OR MORE THAN 30 DAYS AFTER
 SUBMITTAL OF A COMPLETE APPLICATION, THE CITY ART IN
 PUBLIC PLACES COMMITTEE SHALL MEET AND REVIEW THE
 APPLICATION. THE ART IN PUBLIC PLACES COMMITTEE SHALL
 RECOMMEND TO THE CITY BUILDING OFFICIAL THAT A MURAL
 PERMIT BE ISSUED UPON A FINDING THAT:
 (1)THE MURAL WILL ENHANCE THE AESTHETIC BEAUTY OF
 THE AREA OF ITS PROPOSED LOCATION;
 (2)THE ARTIST IS CAPABLE OF COMPLETING THE WORK IN
 ACCORDANCE WITH THE PLANS AND SPECIFICATION;
 (3)THE INFORMATION REGARDING DURABILITY AND EXPECTED
 MAINTENANCE REQUIREMENTS IS ACCURATE; AND
 (4)THE MATERIALS TO BE USED AND THE MANNER OF
 APPLICATION WILL NOT REQUIRE EXCESSIVE MAINTENANCE BY
 ITS OWNER.
 (D)IN MAKING ITS DETERMINATION, THE ART IN PUBLIC
 PLACES COMMITTEE MAY CONSIDER EVIDENCE OF PROPERTY
 VALUES AND THE OPINIONS OF THE OWNERS AND OCCUPANTS OF
 AFFECTED PROPERTIES. ABSENT FAVORABLE FINDINGS AS
 REQUIRED HEREBY, THE ART IN PUBLIC PLACES COMMITTEE
 SHALL RECOMMEND THAT A MURAL PERMIT NOT BE ISSUED BY
 THE CITY BUILDING OFFICIAL.
 (E)UPON A FAVORABLE RECOMMENDATION OF THE ART IN
 PUBLIC PLACES COMMITTEE, THE CITY BUILDING OFFICIAL
 SHALL REVIEW THE APPLICATION MATERIALS AND THE
 INFORMATION RECEIVED BY THE COMMITTEE AND SHALL, UPON A
 DETERMINATION THAT THE APPLICATION MATERIALS ARE
 COMPLETE AND ACCURATE AND THE FINDINGS OF THE COMMITTEE
 REASONABLE, ISSUE A MURAL PERMIT. ABSENT SUCH A
 DETERMINATION, THE BUILDING OFFICIAL SHALL DENY THE
 APPLICATION. UPON AN UNFAVORABLE RECOMMENDATION OF THE
 ART IN PUBLIC PLACES COMMITTEE, THE CITY BUILDING
 OFFICIAL SHALL NOT ISSUE A MURAL PERMIT.
 (F)WITHIN 15 DAYS OF THE MEETING OF THE ART IN
 PUBLIC PLACES COMMITTEE, THE BUILDING OFFICIAL SHALL
 DECIDE WHETHER OR NOT A MURAL PERMIT SHALL BE ISSUED.
 ANY PERSON AGGRIEVED BY THE DECISION OF THE BUILDING
 OFFICIAL MAY APPEAL SUCH DECISION WITHIN 15 DAYS
 THEREOF TO THE CITY COMMISSION WHICH SHALL APPLY THE
 STANDARDS SET FORTH IN THIS SECTION IN REVIEWING THE
 DECISION OF THE BUILDING OFFICIAL. THE CITY COMMISSION
 MAY AFFIRM, REVERSE OR REVERSE WITH MODIFICATIONS THE
 DECISION OF THE BUILDING OFFICIAL. THE DECISION OF THE
 CITY COMMISSION SHALL BE FINAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By astelly Date 2008-04-14 Time 16:23 Rev Time 0.00
Received By astelly Date 2008-04-14 Time 16:23 Sent To  
Notes
2008-04-14 14:07:45AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE SUBMIT A SURVEYAND SITE PLAN WHICH INCLUDES
 LANDSCAPING FOR REVIEW.
 THE APPROVAL OF THIS PERMITWILL NOT EXTENDED TO
 SIGNAGE OR AWNINGS. PLEASE SECURE SEPARATE PERMITS FOR
 THOSE ITEMS.