Plan Review Details - Permit 08040068
Plan Review Stops For Permit 08040068
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 15:16 Sent To P
Notes
2008-04-17 15:16:37TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-04 Cont ID  
Sent By mperson Date 2008-04-04 Time 16:03 Rev Time 0.00
Received By mperson Date 2008-04-02 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-18 Cont ID  
Sent By mperson Date 2008-04-18 Time 10:34 Rev Time 0.00
Received By mperson Date 2008-04-18 Time 10:34 Sent To PC
Notes
2008-04-18 10:38:06****************PROVISO****************
 NOTE: PLANS WERE SUBMITTED FOR PLUMBING PERMIT ONLY.
 ELECTRICAL HAS BEEN DELETED FROM SHEET PE1.0.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-04 Cont ID  
Sent By mperson Date 2008-04-04 Time 14:07 Rev Time 0.00
Received By mperson Date 2008-04-04 Time 14:07 Sent To PC
Notes
2008-04-04 16:03:19PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. NOTE: THE PLUMBING PERMIT BEING APPLIED FOR
 REFERENCES MASTER PERMIT NUMBER 08030319. PLEASE KNOW
 THAT THERE WAS NO PLUMBING PLAN REVIEW OR APPROVAL FOR
 THE PLUMBING BEING DEMOED ON MASTER PERMIT NUMBER
 08030319. PLEASE KNOW THAT THIS PLUMBING REVIEW IS
 BEING DONE ON PLANS SUBMITTED FOR PERMIT NUMBER
 08030319 AND THAT THE FOLLOWING ARE CONCERNS WITH THE
 PLUMBING DEMO.
  
 A} WHAT IS THE SQUARE FOOTAGE, USE AND OCCUPANCY LOAD
 FOR THE 1ST FLOOR? PER FBC PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES. IT APPEARS THAT
 THIS IS A BUSSINESS. THE FOLLOWING ARE MINIMUM NUMBER
 OF PLUMBING FIXTURES REQUIRED FOR A BUSSINESS. WATER
 CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 FOR
 THE REMAINDER EXCEEDING 50. LAVATORIES = 1 PER 40 FOR
 THE FIRST 50 AND 1 PER 80 FOR THE REMAINDER EXCEEDING
 50. DRINKING FOUNTAIN = 1 PER 100. IT ALSO APPEARS THE
 THAT REQUIRED DRINKING FOUNTAIN IS BEING DEMOED. PLEASE
 CLARIFY THESE ISSUES.
  
 B} IT APPEARS THAT THE BATHROOMS BEING DEMOED ARE MORE
 ADA ACCESSIBLE THAN THE EXISTING BATHROOMS. PER
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS. (1)
 GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND
 FACILITIES SHALL COMPLY WITH THE FOLLOWING. (A) NO
 ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES OR HAS
 THE EFFECT OF DECREASING ACCESSIBILITY OR USABILITY OF
 A BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF ALTERATION.
  
 C} IS THE SANITARY PLUMBING DEMO OF THE FIRST FLOOR
 GOING TO AFFECT THE SANITARY PLUMBING TO THE UPPER
 FLOORS OF THIS BUILDING? PER FBC PLUMBING SECTION 701.1
 SCOPE.
  
 D} PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]