Plan Review Details - Permit 08040047
Plan Review Stops For Permit 08040047
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By jgomez Date 2008-04-04 Time 09:03 Rev Time 0.00
Received By jgomez Date 2008-04-04 Time 08:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By jgomez Date 2008-04-03 Time 18:14 Rev Time 0.00
Received By jgomez Date 2008-04-03 Time 18:14 Sent To PC
Notes
2008-04-03 18:32:10RESIDENTIAL WINDOWS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SPECIFYEXISTING TYPE OF WINDOW TO BE REPLACED TO
 VERIFY COMPLIANCE WITH SEC. 501.2 AND 505.1 OF 2004
 EXISTING BUILDING CODE.
 EGRESS OPENINGS CAN'T BE LESS THAN WHAT IT WAS BEFORE.
  
 2- STORM SHUTTERS INSTALLATION SCHEDULE:
 A)DESIGN PRESSURES SPECIFIED ON STORM SHUTTERS ARE
 TOO LOW. PROVIDE ACTUAL CALCULATIONS OR USE TABLE
 R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE AS A
 REFERENCE.
 ***NOTE: TAKE INTO CONSIDERATION THAT SOME OPENINGS ARE
 LOCATED ON END ZONE #5.
  
 B)SHUTTER SPANSHOWN ON COLUMN #6 IS SHOWN
 EXACTLY AS THE WINDOW OPENING HEIGHT.THIS NEEDS TO BE
 REVISED, BECAUSE NEED TO HAVE IN CONSIDERATION THE
 MINIMUM EDGE DISTANCESHOWN ON COLUMN #8. REVISE AS
 REQUIRED.
  
 C) OPENING #3 DOESN'T COMPLY WITH TABLE 2 NOTEON
 SHEET 6 OF 6 OF STORM SHUTTERS DRAWINGS SUBMITTED.
 MINIMUM PANEL LENGTH REQUIRED IS 30". OTHERWISE,
 ENGINEERING CALCULATIONS ARE REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-03 Cont ID  
Sent By jgomez Date 2008-04-03 Time 18:38 Rev Time 0.00
Received By jgomez Date 2008-04-02 Time 11:06 Sent To  
Notes
2008-04-02 11:07:01TO "MISC" BOX#1