|
 |
 |
 |
 |
 |
Plan Review Details - Permit 08040035
| Plan Review Stops For Permit 08040035 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-10 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-10 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-10 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-02 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2008-04-02 09:44:08 | TO "BOB"#3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2008-04-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-04-07 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-04-07 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2008-04-07 14:10:36 | ****************PROVISO**************** | | | (A) SHEET 4 PLUMBING NOTE #16: AIR CHAMBERS ARE NOT | | | APPROVED BY FBC-2004. | | | PER FBC PLUMBING SECTION 604.9 WATER HAMMER. A | | | WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE | | | QUICK-CLOSING VALVES ARE UTILIZED. | | | | | | (B) SHEET 5 WATER ISOMETRIC RISER: THERMAL EXPANSION | | | CONTROL REQUIRED FOR THE WATER HEATER. | | | 607.3.2 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. | | | WHERE A BACKFLOW PREVENTION DEVICE, CHECK VALVE OR | | | OTHER DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM | | | UTILIZING STORAGE WATER HEATING EQUIPMENT SUCH THAT | | | THERMAL EXPANSION CAUSES AN INCREASE IN PRESSURE, A | | | DEVICE FOR CONTROLLING PRESSURE SHALL BE INSTALLED. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-04-02 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-04-02 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2008-04-02 10:37:29 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |