Plan Review Details - Permit 08040011
Plan Review Stops For Permit 08040011
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-22 Cont ID  
Sent By btrobaug Date 2008-04-22 Time 09:51 Rev Time 0.00
Received By btrobaug Date 2008-04-22 Time 09:27 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 12:12 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 11:20 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 10:37 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 10:37 Sent To M
Notes
2009-01-26 10:38:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 09:35 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 09:35 Sent To M
Notes
2008-11-25 09:36:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 10:28 Sent To M
Notes
2008-10-15 10:28:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 10:40 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 10:40 Sent To E
Notes
2008-04-21 10:40:54TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-09 Cont ID  
Sent By tgordon Date 2008-04-09 Time 10:30 Rev Time 0.00
Received By tgordon Date 2008-04-01 Time 13:39 Sent To  
Notes
2008-04-01 13:39:55TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-01-29 Cont ID  
Sent By rregueir Date 2009-01-29 Time 08:01 Rev Time 0.00
Received By rregueir Date 2009-01-29 Time 08:00 Sent To PC
Notes
2009-01-29 08:01:30ROOFTOP INSTALLATION DETAIL

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-12-02 Cont ID  
Sent By rregueir Date 2008-12-02 Time 18:32 Rev Time 0.00
Received By rregueir Date 2008-12-02 Time 18:30 Sent To PC
Notes
2008-12-02 18:32:30REVISED M2.2, M4.2, ENGINEER LETTER AND WIND CALCS.
  
 AFFIDAVIT FROM SEIMENS REGARDING INSTALLATION OF DUCT
 STANDS NOT ACCEPTED AT THIS TIME. THE AFFIDAVIT IS
 SUBJECT TO THE FIELD INSPECTOR'S APPROVAL. IF THE
 INSPECTOR FINDS THE AFFIDAVIT ACCEPTABLE, HE WILL
 RETURN ONE COPY TO THIS OFFICE FOR FILING WITH PERMIT
 SET.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By tgordon Date 2008-10-21 Time 10:42 Rev Time 1.15
Received By tgordon Date 2008-10-21 Time 10:42 Sent To  
Notes
2008-10-21 10:47:13REVISION TO MECHANICAL PLANS M0.1, M0.2, M1.1, M2.1,
 M2.2, M4.2, M4.4 AND M5.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-22 Cont ID  
Sent By tgordon Date 2008-04-22 Time 11:18 Rev Time 0.40
Received By tgordon Date 2008-04-22 Time 11:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By tgordon Date 2008-04-09 Time 09:48 Rev Time 1.00
Received By tgordon Date 2008-04-09 Time 09:48 Sent To  
Notes
2008-04-09 10:22:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES 'THE
 LATEST EDITION' OF THE CODE, THE CITY OF W.P.B. HAS NOT
 ADOPTED THE 2007 CODE. PLEASE SHOW ON PLAN 2004 F.B.C.
  
 2) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES PALM
 BEACH COUNTY AMENDMENTS. AS THE PERMIT APPLIED FOR IS
 IN THE CITY OF W.P.B. PLEASE CORRECT TO THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 ALL PAGES IN THE PLANS, PER 2004 W.P.B AMEND. 106.1.3.
  
 4) PAGE M1.1 SHOWS A 28X20 EXHAUST DUCT PENETRATING THE
 WALL OF THE GENERATOR ROOM, AS 2002 NFPA 374.1.2.3
 REQUIRES ENGINE ROOMS TO BE RATED A FIRE DAMPER WILL BE
 NEEDED PER 2004 FBC/M 607.5.1. PLEASE CORRECT.
  
 5) PLEASE ADD A DETAIL TO THE PLANS SHOWING THE METHOD
 OF INSTALLATION FOR FIRE DAMPERS, PER 2004 FBC/M
 607.8.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]