Plan Review Details - Permit 08030723
Plan Review Stops For Permit 08030723
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 13:31 Rev Time 0.77
Received By jwitmer Date 2008-09-30 Time 13:31 Sent To PC
Notes
2008-09-30 13:32:34REV# 1 SHEET S-2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By jwitmer Date 2008-09-04 Time 11:32 Rev Time 0.77
Received By jwitmer Date 2008-09-04 Time 11:32 Sent To PC
Notes
2008-09-04 11:33:26REVISION# 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 11:42 Rev Time 0.55
Received By jwitmer Date 2008-08-12 Time 11:42 Sent To PC
Notes
2008-08-12 11:43:18PLANS APPEAR TO BE CODE COMPLIANT WILL NEED IMPACT FEE
 ASSESSMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By jwitmer Date 2008-07-08 Time 07:53 Rev Time 2.22
Received By jwitmer Date 2008-07-08 Time 07:53 Sent To  
Notes
2008-07-08 07:55:05BUILDING, PLANS ARE CODE COMPLIANT REQUIRES IMPACT FEE
 ASSESSMENT BEFORE ISSUANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By jwitmer Date 2008-04-17 Time 07:19 Rev Time 5.50
Received By jwitmer Date 2008-04-17 Time 07:19 Sent To PC
Notes
2008-04-17 11:01:22BUILDING PLAN REVIEW
 PERMIT: 08030723
 ADD: 6910 S DIXIE HWY
 CONT: SULLIVAN BUILDERS
 TEL: (561)586-5353 (NEYITA)
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SHEET A-1 INDICATES TWO EXIT DOORS ONE ON EITHER
 SIDE OF THE BUILDING. BOTH EXIT DOORS INDICATE THE USE
 OF DOOR CLOSERS,AND WOULD HAVE SELF LATCHING
 DOORSBEING EXTERIOR EXIT DOORS.
 THE PLANS ARE MISSING THE REQUIRED 12" SIDE CLEARENCE
 ON THE LATCH SIDE OF THE DOOR, SEE11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 3) PRODUCT APPROVALS, PLEASE NOTE THAT THE TYPE OF
 GLAZING AND IF MULLIONS AND FRAMES REQUIRE REINFORCING,
 PLEASE SEE SHEET A-2 & S-1 THE WESTERN EXPOSURE,THE
 FRONT ENTRY IS DRAWN WITHOUT A TRANSOM BUT THE FRAMING
 MEMBERS OR BEAM THAT CARRIES THESE MEMBERS WOULD BE AT
 THE TALLEST WINDOWS. THE HORIZONTALL MULLION THAT WOULD
 BE CARRYING THE LOAD IS OVER 13'-6" LONG PLUS THE
 STUCCO LOADSAPPLIED TO THIS AREA. PLEASE VERIFY THE
 FRAMING CONDITIONS IN THIS AREA.AT THIS TIME UNABLE
 TO DO A REVIEW ON THE STOREFRONT PANEL WALL SYSTEM NOR
 DOORS DUE TO INSUFFICIENT INFORMATION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED, & TABLE
 1609.2.1.(2).
  
 4) PLEASE PROVIDE ADDITIONAL INFORMATION, SHEET A-3
 INDICATES THE USE OF R-19 ICYNENE, THE USE OF ICYNENE
 TO THE UNDER SIDE OF THE ROOF SHEATHING DECK. THE PLANS
 DO NOT INDICATE IF THE
 END GABLE WALLS ARE A CONTINUATION OF THE CBS WALLS OR
 IF THEY ARE WOOD STUD GABLE END WALLS? THIS INFORMATION
 WILL HELPIN THE PLAN REVIEW. NOTE ALSO INCLUDED IS A
 ICC LEGACY REPORT NER-420
 AND A INFORMAL CODE INTERPRETATION.IF THE GABLE END
 WALLS ARE WOOD WALLS PLEASETAKE NOTE TO THE ASSEMBLY
 1-4 AND COMMENTS TO VERTICAL SURFACES AND
 REQUIREMENTS.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2.
  
 5)ADDITONAL INFORMATION REQUIRED, 106.1.2. SHEET A-3
 INDICATES THE USE OF 1/2" DRYWALL BUT THE FINISH IS NOT
 KNOWN. PLEASE LOOK AT TABLE 2508.1 FOR GYPSUM BOARD
 APPLICATIONS GA-216 IS REFERENCED. THE APPLICATION OF
 WATER BASED TEXTURE MATERIALS ISA CONCERN EXSPECIALLY
 ON A NON VENTED VEILING. PLEASE SEE TABLE 1 AND THE
 APPENDIX A.2FOR THE CONCERNS AND REQUIREMENTS FOR
 FRAMING SPACING.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-18 Cont ID  
Sent By dpalmer Date 2008-08-18 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2008-08-18 Time 14:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-07 Cont ID  
Sent By dpalmer Date 2008-08-07 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2008-08-07 Time 16:55 Sent To  
Notes
2008-08-07 16:55:41 
 **DENIEDREVIEW**
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS REVISED ON PLANS
 WHICH WERE NOT PART OF PREVIOUS COMMENTS NOR WAS IT
 BROUGHT UP IN MEETING PREVIOUSLY HELD BEFORE PLANS WERE
 RESUBMITTED. IT IS UNCLEAR WHY THESE ITEMS WERE
 REVISED.
 THE PREVIOUS REVIEW NOTES DID HAVE COMMENTS FOR THE
 NEED OF REVISING LOAD CALCULATIONS WHICH WERE NOW DONE
 HOWEVER THESE HAVE NOW CHANGED WHICH WOULD REQUIRE THE
 EXISTING MAIN TO BE UPGRADED.
 THE FOLLOWING ITEMS ARE NOW NOTED.
  
  
 1) NOTE:THE FOLLOWING ARE EXAMPLES:
 PLEASE SEE THE FEEDERS SCHEDULE HAS NOW BEEN REVISED.
 PANEL *B* IS A 200AMP MCB PANEL NOW REVISED WITH TAPPED
 CONDUCTORS SHOWN AS 500MCM. THE 500MCM WILL NOT FIT
 INTO A 200AMP BREAKER.
 PLEASE SEE PANEL SCHEDULE FOR LA. THIS PANEL HAS NOW
 BEEN REVISED TO A 200AMP MCB WHICH IS OK.
 PLEASE SEE THE BREAKER IN PANEL *LB* WHICH IS SHOWING A
 3-POLE 60AMP BREAKER WITH 1/0 FEEDERS. THE 1/0 FEEDERS
 WILL NOT FIT UNDER A LUG OF A 60AMP BREAKER. IN ANY
 CASE PLEASE LOOK AT LOAD CALCULATIONS. THE LOAD NOW
 SHOWN FOR PANEL *LP* IS SHOWN AT 163AMPS YET THE
 BREAKER AS NOTED IS ONLY 60AMPS AND THE FEEDERS AS 1/0
 ARE ONLY RATED FOR 150AMPS.
 PLEASE SEE THE LOAD CALCULATIONS AS THE SERVICE LOAD IS
 NOW SHOWN AT 455AMPS ON A 400AMP MAIN.
 PLEASE SEE THE LOAD SHOWN ON PANEL *LB* FOR PANEL *LP*.
 THE LOAD ON SHEET E-4 FOR PANEL LP IS NOT THE SAME AS
 LOAD ON LB.
 ETC.
 220,240.4,310.16,,110.3
 NEITHER OF THESE TWO LOADS ARE THE SAME AS THE LOAD
 CALCULATIONS ON SHEET E-5.
 PLEASE CALL TO SET UP A MEETING AS SOON AS POSSIBLE TO
 GO OVER PLANS.
 PLACED CALLS TO ELECTRICAL CONTRACTOR, ARCHITECT AND
 EXPEDITOR.
 SPOKE TO CONTRACTOR AND THEY WERE NOT AWARE OF
 CHANGES.
 SPOKE WITH ARCHITECT AND A MEETING IS TO BE SET.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 17:13 Sent To  
Notes
2008-07-08 17:13:35** DENIED2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS WHICH
 ARE BASED ON REVISED PLANS OR INFORMATION NOW BEING
 SHOWN.
 ** PLEASE ALSO SEE THERE IS A NEW COMMENT WHICH WAS NOT
 ON PREVIOUS REVIEW EVEN AS PREVIOUS PLANS DID CONTAIN
 ERROR.
  
 1) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 .1.3 AND
 13-415.2. PLEASE KNOW ALLOWANCES FOR ADDITIONAL
 LIGHTING IN AREAS MAY NOT BE USED OR TAKEN INTO ACCOUNT
 IN CALCULATIONS UNLESS SPECIFICALLY INSTALLING LIGHTING
 ETC FOR THAT ADDITIONAL ALLOWANCE.
  
 FOR EXAMPLE:
 PLEASE SEE THE HALLWAY AREAS OUTSIDE THE BATHROOMS
 WHICH ARE TAKING AN ADDITIONAL 1W PER SQ FT FOR
 DECORATIVE LIGHTING YET NONE OF THESE TYPES OF FIXTURES
 ARE ON PLANS.
 ** THIS IS ONE EXAMPLE GIVEN. THIS IS NOT THE ONLY
 LOCATION. BASED ON THE ALLOWANCES PERMITTED IN THE CODE
 AND THE DESIGN WATTAGE TOTAL SHOWN THE TOTAL DESIGN
 WATTAGE IS OVER.
 PLEASE ADJUST.
 ** NOTED PREVIOUSLY
  
 2) NOTE: PLEASE SHOW THE SHOW WINDOW CALCULATIONS PER
 220.43A.
 ** AN EXAMPLE OF THIS IS CIRCUIT LA-1 WHICH SHOWS A 1.0
 KVA. HOW IS THIS POSSIBLE WHEN THE LINEAR FT OF WINDOW
 IS 13FT AND THE CODE REQUIRES A LOAD OF 200VA PER FT.
 THE LOAD FOR BRANCH CIRCUIT SIZING PER 220.14 AND
 SIZING FOR SERVICE PER 220.43 IS NOT THE SAME.
 PLEASE SHOW THESE FIGURES INTO REVISED LOAD
 CALCULATIONS FOR PANELS AND SERVICE.
 ** NOTED PREVIOUSLY
  
 3) NOTE: PLEASE SEE SECTION 220.43B FOR TRACK LIGHTING
 AND SHOW LOAD IN CALCULATIONS FOR PANELS AND SERVICE.
 ** NOTED PREVIOUSLY.
  
 4) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTS. BASED ON PLANS, FLOOR LAYOUT AND DESIGN MAY NOT
 USE EXCEPTION AND MUST CIRCUIT TO THE LOCAL LIGHTING
 BRANCH CIRCUIT IN ANY ONE AREA AHEAD OF ANY SWITCHING
 DEVICES INCLUDING LIGHTING CONTROL PANEL.
 ** THIS IS A NEW COMMENT EVEN THOUGH PLANS DO CONTAIN A
 NOTE #2 WHICH IS LABELED TO CONNECT AHEAD OF LOCAL
 CIRCUIT. AS THE PLANS SHOW THESE EMERGENCY LIGHT
 FIXTURES TO THEIR OWN CIRCUIT ON THE LIGHTING CONTROL
 PANEL AND TO EACH LOCAL CIRCUIT BY NOTE, THESE NEEDS TO
 BE ADDRESSED AND COORDINATED.
  
 5) NOTE: PLEASE COORDINATE THE FEEDERS FOR LIGHTING
 PANEL. RISER SHOWS A NOTE *D* WHICH NOTES #3 CONDUCTORS
 YET THE PANEL SCHEDULE RISER AND PANEL SCHEDULE *LB*
 STATES #6 FOR THE SAME FEEDERS.
 THIS IS A NEW COMMENT AS THE PREVIOUS PLANS SHOWED THE
 SAME.
 PLEASE COORDINATE. 310.16, 240.4, 408.4
 FBC 106.1.2, 106.1.1 FOR COORDINATION AND CLARITY OF
 PLANS.
 ** NEW COMMENT MISSED FROM NOTES IN PREVIOUS REVIEW.
  
 6) NOTE: PLEASE COMPLETE BAY NUMERICAL DESIGNATIONS ON
 POWER PLANS FOR COORDINATION OF CIRCUITING WITH PANEL
 SCHEDULES.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF RECORD
 PLANS.
 ** NOTED ON PREVIOUS REVIEW
  
 7) NOTE: PLEASE VERIFY ANY EXTERIOR LIGHTING AT THIS
 LOCATION. PLANS, PANELS, LOAD CALCULATIONS ETC DO NOT
 INDICATE ANY LIGHTING.
 SITE/SURVEY DOES INDICATE EXTERIOR LIGHTS SUCH AS LIGHT
 POLES HOWEVER NONE INCLUDED AS NOTED.
 PLEASE COMPLETE AND COORDINATE ALL ITEMS SUCH AS
 LIGHTING CONTROLS PER 13-415.1.ABC.1.4, LOADS PER NEC
 220, PANEL SCHEDULES PER NEC 408, CIRCUITING,
 CONDUCTORS BREAKERS ETC.
 ** THIS IS NEW BASED ON REVISED PLANS NOWSHOWING
 EXTERIOR LIGHTINGWHICH WAS NOT ON PREVIOUS PLANS.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-04 Cont ID  
Sent By dpalmer Date 2008-04-04 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 19:06 Sent To  
Notes
2008-04-04 11:01:31** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1.1.2 AND .1.3 FOR
 THE FOLLOWING ITEMS NEEDED.
 PLEASE PROVIDE MAXIMUM OVER RIDE TIMES FOR DEVICES.
 PLEASE SEE THAT WHEN OVER RIDES ARE LOCATED IN ANY
 BUILDING/SPACE THE OCCUPANT IS REQUIRED TO SEE ALL
 LIGHTING IN WHICH THEY ARE OVER RIDING OR MUST PROVIDE
 FOR THE EXCEPTION IN THE CODE. THE LOCATION ON PLANS
 DOES NOT PERMIT THE OCCUPANT TO SEE ALLLIGHTING AND
 NO INDICATORS AS REQUIRED COULD BE FOUND ON LIGHTING
 CONTROL RISER OR PLANS.
  
 3) NOTE: PLEASE PROVIDE COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SEE 13-400.3.B, 13-400.3.C, ETC.
 AS NO LIGHTING PERFORMANCE CALCULATIONS WERE SUBMITTED
 A REVIEW OF THESE COULD NOT BE DONE AT THIS TIME.
 PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH
 THE CALCULATIONS TO BE PROVIDED.
  
 4) NOTE: PLEASE SEE 600.5 FOR MISSING REQUIRED SIGN
 CIRCUIT. (PLEASE BE SURE TO ADD DEDICATED MINIMUM
 LOAD)
  
 5) NOTE: PLEASE VERIFY ALL REQUIRED CONTINUOUS LOADS.
 PANEL LB STATES CONTINUOUS LOADS WERE FIGURED AT 125%,
 HOWEVER PANEL LA DOES NOT SHOW OR INDICATE THESE
 REQUIRED CONTINUOUS LOADS,
 FOR EXAMPLE;
 LIGHTING, WATER HEATER, ETC.
 215.3, 230.42, 422.13 (2005 NEC) ETC.
 PLEASE ADJUST AND SHOW WHERE LOADS ARE FIGURED IN
 CALCULATIONS.
  
 6) NOTE: PLEASE SEE 220.43 AND PROVIDE LOADS ON SHOW
 WINDOWS AND HOW THEY WERE FIGURED INTO CALCULATIONS.
  
 7) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS
 ON ELECTRICAL PLANS.
 FBC 106.1.2
  
 8) NOTE: PLEASE CLARIFY THE SIZES OF THE PANELS AS
 THESE ARE SHOWN AS 125AMPS WITH 42CIRCUITS ON ONE AND
 THE OTHER AS 200AMP AND 24 CIRCUITS.
 PLEASE SEE 110.3, 90.7 AND VERIFY LISTING OF THIS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-04-03 19:06:592008-04-03 19:06:59
  
 IN ELECTRICAL FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-23 Cont ID  
Sent By mawillia Date 2008-07-23 Time 13:16 Rev Time 0.00
Received By mawillia Date 2008-07-23 Time 12:53 Sent To  
Notes
2008-07-23 13:13:46*****PARTIAL APPROVAL*****
  
  
 PLAN SHEETS LS-1, A-1, A-2, AND A-4 WERE STAMPED,
 INITIALED, AND DATED;HOWEVER SHEET E-2 TO BE
 FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S COMMENTS
 HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2008-04-28 Time 11:27 Sent To  
Notes
2008-04-28 11:29:09PLANS APPEAR TO BE CODE COMPLIANT, HOWEVER WILL REMAIN
 IN FAILED STATUS UNTIL CORRECTED AND RETURNED FOR OTHER
 REVIEW COMMENTS. PLEASE VERIFY THAT ELECTRICAL ROOM
 DOOR IS (2) HOUR RATED AND NOT 1 1/2 HOUR AS COMMONLY
 FOUND IN (2) HOUR ENCLOSURES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVNTION (561) 805-4756

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 08:52 Sent To M
Notes
2008-10-01 08:53:21TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 13:31 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 13:31 Sent To B
Notes
2008-09-15 13:31:35TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 13:47 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 13:47 Sent To B
Notes
2008-08-28 13:47:47TO "BUILD"JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 10:11 Sent To E
Notes
2008-08-14 10:11:30TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 15:40 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 15:40 Sent To  
Notes
2008-07-30 15:46:58TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 11:40 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 11:40 Sent To  
Notes
2008-06-19 11:41:49TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 09:44 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 09:44 Sent To  
Notes
2008-05-27 16:00:42TO "COMM" BD#6
2008-05-21 09:45:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 11:33 Rev Time 0.00
Received By mwennerg Date 2008-04-01 Time 10:59 Sent To  
Notes
2008-04-01 11:02:07TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-17 Cont ID  
Sent By rregueir Date 2008-10-17 Time 08:30 Rev Time 0.00
Received By rregueir Date 2008-10-17 Time 08:30 Sent To PC
Notes
2008-10-17 08:30:32MECH REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-08 Cont ID  
Sent By rregueir Date 2008-07-08 Time 10:46 Rev Time 0.00
Received By rregueir Date 2008-07-08 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By rregueir Date 2008-04-24 Time 16:54 Rev Time 0.00
Received By rregueir Date 2008-04-24 Time 08:42 Sent To  
Notes
2008-04-24 16:54:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS AND RESUBMIT:
  
 1. ELECTRICAL ROOM IS SHOWN ON PG A-1 TO BE ENCLOSED IN
 2-HOUR FIRE RESISTANCE RATED CONSTRUCTION. HVAC PLAN
 SHOWS A 6 INCH ROUND DUCT PENETRATING THE 2-HOUR WALL.
 SHOW HOW THIS DUCT PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.2 AND FBCM 607.8.
  
 2. HVAC PLAN NOTES CALL FOR ADJUSTABLE FRESH AIR
 INTAKE. MOTORIZED SHUTOFF DAMPER CONTROLS ARE REQUIRED
 FOR OUTDOOR AIR INTAKES IN ACCORDANCE WITH FBCEB 611.1
 AND FBCB 13-409.1.ABC.3.3.
  
 3. SUPPLY DUCT AND GRILL SERVING JANITOR?S CLOSET IS
 MISSING DUCT SIZE, CFM AND GRILL DESIGNATION. PROVIDE
 MISSING INFORMATION. FBCM 603.1, FBCB 106.1.1.
  
 4. PLAN IS NOT CLEAR AS TO WHETHER THE DUCT SHOWN ON
 PLANS IS TO BE ABOVE A CEILING OR EXPOSED BELOW THE
 CEILING. PLEASE CLARIFY. THIS INFORMATION AS WELL AS
 ADDITIONAL INFORMATION IS REQUIRED TO DEMONSTRATE
 ENERGY CODE COMPLIANCE FOR THE AIR DISTRIBUTION SYSTEM.
 SEE THE FOLLOWING SECTIONS: FBCB 13-410.1.ABC.2 AND
 13-410.1.ACB.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-08-06 Cont ID  
Sent By kstevens Date 2008-08-06 Time 07:07 Rev Time 0.00
Received By kstevens Date 2008-08-06 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-07-18 Cont ID  
Sent By kstevens Date 2008-07-18 Time 16:38 Rev Time 0.00
Received By kstevens Date 2008-07-18 Time 16:38 Sent To  
Notes
2008-07-18 16:51:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG
 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT
 DIMENSION TO THE CENTERLINE OF THE W/C'S. ****RESPONSE
 FROM ENGINEER STATES: "PLEASE REFER TO RESPONSE BY
 "ARCHITECT OF RECORD". NO RESPONSE FROM ARCHITECT OF
 RECORD. COMMENT NOT ADDRESSED.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE FROM ENGINEER STATES: "PLEASE REFER TO
 RESPONSE BY "ARCHITECT OF RECORD". NO RESPONSE FROM
 ARCHITECT OF RECORD. COMMENT NOT ADDRESSED.
 ******NO RESPONSE, COMMENT NOT ADDRESSED
  
 3. OK
  
 ***********NEW COMMENTS**********
 NEW SHEETS SUBMITTED
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. SEE ATTACHED SHEET CONCERNING FLORIDA STATUTE
 553.80(2)(B) AND THE DESIGN PROFESSIONALS. THIS IS
 GIVEN AS NOTICE ONLY AT THIS TIME.
  
 6B. ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE
 FOR POSSIBLE REVIEW BY THE ARCHITECTURAL, ENGINEER &
 SURVEY BOARDS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-05 Cont ID  
Sent By kstevens Date 2008-06-05 Time 09:43 Rev Time 0.00
Received By kstevens Date 2008-06-05 Time 09:43 Sent To  
Notes
2008-06-05 10:10:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG
 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT
 DIMENSION TO THE CENTERLINE OF THE W/C'S. ****RESPONSE
 FROM ENGINEER STATES: "PLEASE REFER TO RESPONSE BY
 "ARCHITECT OF RECORD". NO RESPONSE FROM ARCHITECT OF
 RECORD. COMMENT NOT ADDRESSED.
  
 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE FROM ENGINEER STATES: "PLEASE REFER TO
 RESPONSE BY "ARCHITECT OF RECORD". NO RESPONSE FROM
 ARCHITECT OF RECORD. COMMENT NOT ADDRESSED.
  
 3. OK
  
 ***********NEW COMMENTS**********
 NEW SHEETS SUBMITTED
  
 1B. SHT 90-038 SURVEY NOT SEALED OR DATED AS REQUIRED
 IN FS 472.025(1)
  
 2B. SHTS SP-1, A-1, A-2, A-3 & A-4 ARE NOT SIGNED,
 SEALED & DATED AS REQUIRED. FAC 61G1-16.003,
 61G16-004(5) AND FS 481.2055.
  
 3B. SHTS PL 1.00, PL 2.00 & PL 3.00 REQUIRES THE
 BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2)(6) &
 FS 481.306, 481.319.
  
 4B. LAST NEW SHEET HAS NO TITLE BLOCK AND IS NOT
 SIGNED, SEALED, DATED. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS
 OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART
 I, OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471,
 FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS AS
 REQUIRED BY FLORIDA STATUTES. SECTION 106.1.
  
 5B. SEE ATTACHED SHEET CONCERNING FLORIDA STATUTE
 553.80(2)(B) AND THE DESIGN PROFESSIONALS. THIS IS
 GIVEN AS NOTICE ONLY AT THIS TIME.
  
 6B. ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE
 FOR POSSIBLE REVIEW BY THE ARCHITECTURAL, ENGINEER &
 SURVEY BOARDS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 11:30 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 11:30 Sent To  
Notes
2008-04-12 11:38:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG
 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT
 DIMENSION TO THE CENTERLINE OF THE W/C'S.
  
 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 3. SHT P-4 ELECTRIC WATER HEATER DETAIL. SHOW
 COMPLIANCE WITH SECTION 607.3.2 THERMAL EXPANSION
 CONTROL. INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-24 Cont ID  
Sent By choops Date 2008-06-24 Time 14:50 Rev Time 0.00
Received By choops Date 2008-06-24 Time 14:50 Sent To  
Notes
2008-06-24 14:52:59***APPROVED - RESUB #1 (CONTRACTOR MISTAKENLY SUBMITTED
 PHASE II DRAWINGS (SCOPE OF WORK NOW AS ORIGINALLY
 SUBMITTED))***
  
 NOTE:ADA RAMP ENCROACHES REQUIRED SETBACK OF TWO (2)
 FEET, HOWEVER, OK PER AJV.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-09 Cont ID  
Sent By choops Date 2008-06-09 Time 08:06 Rev Time 0.00
Received By choops Date 2008-06-09 Time 08:06 Sent To  
Notes
2008-06-09 08:09:24***FAILED - RESUB #1 (SCOPE OF WORK INCREASED)***
  
  
 1)AS THE SCOPE OF WORK HAS BEEN INCREASED (ADDITION
 OF CANOPIES, PARKING, AND LANDSCAPING), THE DECLARED
 VALUE SHALL BE INCREASED TO ACCURATELY REFLECT THE
 WORK.ANY ADDITIONAL PEMIT FEES SHALL BE PAID
 ACCORDINGLY.
  
 2)ANY/ALL SIGNAGE SHALL BE PERMITTED SEPARATELY.
 COPY TO BE REMOVED FROM PLANS OR LABELED "TO BE
 PERMITTED SEPARATELY".
  
 3)PURSUANT TO SECTION 94-305(E) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS):VISIBILITY
 AT INTERSECTIONS.AT ANY ROAD INTERSECTIONS,
 VISIBILITY SHALL NOT BE OBSCURED BY THE CONSTRUCTION,
 PLACEMENT, OR MAINTENANCE OF A STRUCTURE WALL, SIGN,
 FENCE, BERM, PLANT MATERIAL, SHRUBS, OR ANY SIMILAR
 ITEM BETWEEN 18 INCHES OR EIGHT FEET IN HEIGHT WITHIN A
 TRIANGLE BEGINNING AT THE POINT WHERE PROPERTY LINES
 MEET AT THE CORNER, THEN 20 FEET ALONG THE FRONT
 PROPERTY LINE, THENCE DIAGONALLY TO A POINT ALONG THE
 SIDE PROPERTY LINE 20 FEET FROM THE POINT OF BEGINNING,
 AND THENCE TO THE POINT OF BEGINNING. IN THE EVENT THE
 CORNER OF AN INTERSECTION IS ROUNDED, THE MEASUREMENT
 SHALL BEGIN AT THE POINT THE PROPERTY LINES WOULD MEET
 WITHOUT ROUNDING. (SEE FIGURE X-1)
  
 NO PLANT MATERIAL SHALL ENCROACH THE VISIBILITY
 TRIANGLE AT THE CORNER OF DIXIE HIGHWAY AND MADDOCK
 STREET.REVISE PROPOSED PLANT MATERIAL TO A SIZE LESS
 THAN 18" IN HEIGHT AT MATURITY.NOTE: REQUIRED SHADE
 TREE AT LANDSCAPE TERMINAL ISLAND SHALL BE SHOWN
 OUTSIDE OF THE VISIBILITY TRIANGLE.
  
 4)PROPOSED LIGHTING SHALL BE SHOWN OUTSIDE OF THE
 VISIBILITY TRIANGLE (SECTION 94-305(E)) AND SHALL NOT
 INTERFERE WITH ANY REQUIRED LANDSCAPING MATERIAL.
  
 5)NORTH ARROW IS NOT CORRECT ON PLANTING PLAN (SHEET
 PL 1.00).REVISE.
  
 6)SITE PLAN (SHEET SP-1) AND PLANTING PLAN (SHEET PL
 1.00) DO NOT MATCH WITH RESPECT TO THE REQUIRED 5'
 LANDSCAPE BUFFER AT THE NORTH SIDE OF THE PROPERTY.
 REVISE SO ALL PLANS AND DIMENSIONS COORELATE.PLEASE
 SHOW ALL DIMENSIONS OF REQUIRED ISLANDS/BUFFERS.
  
 7)PURSUANT TO SECTION 94-443(B)(4) OF THE THE ZLDRS:
 AT LEAST ONE SHADE OR FLOWERING TREE SHALL BE PLANTED
 IN A REQUIRED BUFFER STRIP FOR EACH 30 LINEAR FEET OR
 PORTION THEREOF. PAVED AREAS USED FOR PEDESTRIAN
 CIRCULATION AND VEHICULAR ACCESS SHALL BE INCLUDED WHEN
 CALCULATING THE LENGTH OF THE BUFFER STRIP. TREES MAY
 BE CLUSTERED OR PLANTED IRREGULARLY AS DEEMED
 APPROPRIATE. CLUSTERING OF REQUIRED TREES SHALL BE
 SUBJECT TO CITY APPROVAL.
  
 PROVIDE SHADE TREES EVERY 30' ALONG DIXIE HIGHWAY
 FRONTAGE AS REQUIRED BY THIS SECTION.
  
 8)ALL REQUIRED LANDSCAPE ISLANDS/TERMINAL ISLANDS
 SHALL MEET THE MINIMUM REQUIRED 5' WIDTH, MEASURED FROM
 THE INSIDE OF THE CURBING.PLEASE REVISE/RECONFIGURE
 NORTHERN MOST INTERIOR ISLAND AND NORTH TERMINAL ISLAND
 (DIRECTLY WEST OF FRONT BUILDING FACADE) TO REFLECT THE
 MINIMUM WIDTH.
  
 9)AS THE WESTERN-MOST ROW OF PARKING ALONG DIXIE
 HIGHWAY EXCEEDS THE LENGTH OF 10 CONTIGUOUS PARKING
 SPACES, THE REQUIRED 5' INTERIOR ISLAND SHALL BE
 PROVIDED, OR THE ROW/TERMINAL ISLANDS SHALL BE
 RECONFIGURED SO-AS NOT TO EXCEED THE LENGTH OF 10
 STANDARD PARKING SPACES.
  
 10)TWO (2) DIFFERENT SITE PLANS HAVE BEEN SUBMITTED,
 ONLY ONE NEED BE SUBMITTED WITH THE PROPOSED SCOPE OF
 WORK ON IT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2008-04-14 Cont ID  
Sent By choops Date 2008-04-14 Time 15:14 Rev Time 0.00
Received By choops Date 2008-04-14 Time 15:14 Sent To  
Notes
2008-04-14 15:14:22***APPROVED***
  
 NOTE:ADA RAMP ENCROACHES REQUIRED SETBACK OF TWO (2)
 FEET, HOWEVER, OK PER AJV.