| 2008-06-10 14:17:38 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | NOTE: THERE WAS NO COMMENT RESPONSE FROM THE |
| | DESIGNER. |
| | |
| | 1. "OK" COMMENT ADDRESSED. |
| | |
| | 2. SHEET A2 SANITARY PLUMBING RISER: THE WASHING |
| | MACHINE MUST DRAIN DOWNSTREAM OF THE BATHROOM.PER |
| | FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | **THE RESUBMITTED SANITARY PLUMBING RISER IS STILL |
| | INDICATING THE WASHING MACHINE DRAINING INTO THE WET |
| | VENTED BATHROOM. THE WASHING MACHINE MUST DRAIN |
| | DOWNSTREAM OF THE WET VENTED BATHROOM. PER SECTION |
| | 909.1 WET VENT PERMITTED. |
| | |
| | 3. SHEET A2 SANITARY PLUMBING RISER: THE FOLLOWING IS |
| | REQUIRED FOR THE WASHING MACHINE. |
| | |
| | (A) "OK" COMMENT ADDRESSED. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | *CLEARLY INDICATE THE REQUIRED STANDPIPE ON |
| | RESUBMITTED DRAWINGS. |
| | |
| | **THE RESUBMITTED SANITARY PLUMBING RISER IS |
| | INCORRECTLY INDICATING THE STANDPIPE MINIMUM OF 18 |
| | INCHES LOCATION FOR THE WASHING MACHINE. PER SECTION |
| | 802.4 STANPIPES. |
| | |
| | (C) "OK" COMMENT ADDRESSED. |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | *CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT 4' |
| | A.F.F. |
| | |
| | **THE RESUBMITTED SANITARY PLUMBING RISER IS NOT |
| | INDICATING THE CLEANOUT FOR THE WASHING MACHINE TO BE |
| | AT 4 FEET ABOVE FINNISH FLOOR (4' A.F.F.) AND IS |
| | INCORRECTLY INDICATING THE CLEANOUT AS BEING A TRAP. |
| | PER SECTION 708.1 ACCESS AND SECTION 701.1 SCOPE. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS DUE TO THE SANITARY |
| | PLUMBING RISER BEING REVISED. |
| | |
| | 4. SHEET A2 SANITARY PLUMBING RISER: CLEANOUT FOR THE |
| | LAVATORY BEING INDICATED IN THE WRONG PLACE AND AND |
| | MSILABELED AS BEING A TRAP. CLEANOUT TO BE LOCATED AT |
| | THE BASE OF THE STACK AND CORRECTLY IDENTIFIED AS A |
| | CLEANOUT. PER FBC-PLUMBING SECTION 708.3.4 BASE OF |
| | STACK. |
| | NOTE: PER FBC-PLUMBING SECTION 708.7 MINIMUM SIZE |
| | EXCEPTIONS:(1) A CLEANOUT FOR THIS STACK IS NOT |
| | REQUIRED WITH THE SINK TRAP BEING INDICATED AS BEING 2 |
| | INCH. |
| | |
| | 5. SHEET A2 SANITARY PLUMBING RISER: DELETE THE 4 INCH |
| | CLEANOUT BETWEEN THE WATER CLOSET AND LAVATORY IT IS |
| | NOT REQUIRED. PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| | |
| | 6. SHEET A2 SANITARY PLUMBING RISER: THE RESUBMITTED |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET |
| | A1. PLEASE PROVIDE A FLAT LINE DRAWING OF THE |
| | UNDERGROUND PLUMBING ON SHEET A1 FLOOR PLAN. AT A |
| | MINIMUM THE SANITARY ISOMETRIC RISER DIAGRAM SHALL |
| | REFLECT THE FLOOR PLAN. THE RESUBMITTED DRAWING IS |
| | EITHER INDICATNG THE BATHROOM LAVATORY OUT OF THE |
| | BUILDING OR THE WASHING MACHINE IN THE WRONG PLACE. PER |
| | FBC- PLUMBING SECTION 701.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |