Plan Review Details - Permit 08030710
Plan Review Stops For Permit 08030710
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-17 Cont ID  
Sent By rmcdouga Date 2008-06-17 Time 14:22 Rev Time 0.00
Received By rmcdouga Date 2008-06-17 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By rmcdouga Date 2008-04-10 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2008-04-09 Time 15:11 Sent To  
Notes
2008-04-10 06:56:222004 FBC W/2007 REVISIONS
 R-3ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN THAT
 SPECIFIES THE DISTANCES FROM THE PROPOSED ADDITION TO
 THE PROPERTY LINES.
  
 4) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC
 13-600.
  
 5) THE MINIMUM INSULATION FOR 2 X 6 FRAME WALLS IS
 R-19. THE MINIMUM INSULATION FOR RAISED WOOD FLOORS IS
 R-11. REVISE WALL SECTION ON A1. SEE FBC 13-602 AND
 13-605.
  
 6) SPECIFY THE TERMITE TREATMENT THAT WILL BE USED ON
 THE PLAN AS REQUIRED BY FBC R320.1.
  
 7) SHOW COMPLIANCE WITH FBC R408.1 VENTILATION. THE
 UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF UNDER
 -FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING SHALL
 BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING.
  
 8) SHOW COMPLIANCE WITH R408.3 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER -FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24
 INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE
 THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT
 LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM)
 SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE
 BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL
 ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO
 THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS
 WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 9) THE EXTERIOR WALL SECTION ON A1 DOES NOT APPEAR TO
 PROVIDE A SIX INCH CLEARANCE FOR TERMITE INSPECTION.
 SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 10) PROVIDE A DETAIL INDICATING THE ATTACHMENT OF THE
 NEW FOUNDATION AND FRAME WALLS TO THE EXISTING
 STRUCTURE.
  
 11) THE ATTIC VENTS SPECIFIED ON THE EXTERIOR WALL
 SECTION WILL HAVE TO BE CONTINUOUS IN ORDER TO PROVIDE
 VENTILATION TO THE SINGLE ASSEMBLY ROOF SYSTEM. SEE
 R806.1.
  
 12) SPECIFY THE WINDOW TYPE AND SIZE FOR THE LAUNDRY
 ROOM WINDOW. FBC 106.1.1* CITY AMENDMENTS.
  
 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING IN THE STEM WALL.
  
 14) SPECIFY THE SIZE OF THE HORIZONTAL REINFORCING IN
 THE BOND BEAM FOR THE STEM WALL.
  
 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE FRAME WALL TO THE FLOOR JOIST AS REQUIRED FOR A
 CONTINUOUS LOAD PATH. R301.1
  
 16) THE WALL SECTION ON A1 SPECIFIES 2 X 12 PT FLOOR
 JOISTS @ 16" OC WITH A 2 X 10 BAND. THE FLOOR FRAMING
 PLAN ON A1 SPECIFIES 2 X 10 JOISTS @ 16" OC. PLEASE
 CORRECT.
  
 17) THE INFORMATION ON THE DIAPHRAGM SCHEDULE ON A1
 CONFLICTS WITH THE NOTES ON THE EXTERIOR WALL SECTION
 FO THE ROOF AND WALL SHEATHING FASTENING.
  
 18) THE EXTERIOR WALL SECTION ON A1 SPECIFIES A SIMPSON
 METAM 24. THIS CONNECTOR WAS NOT LISTED IN THE 2008
 SIMPSON CATALOG OR WEBSITE. SUBMIT PRODUCT APPROVALS
 FOR THIS CONNECTOR.
  
 19) IN THE WIND INFORMATION ON SHEET A1 WALL ZONE 5 IS
 INCORRECTLY SPECIFIED AS AN INTERIOR ZONE. FIGURE
 R301.2(8)
  
 20) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS ARE EXPIRED. SUBMIT CURRENT ONES. DCA RULE
 9B-72.
  
 21) SPECIFY WHICH ONE OF THE BUR ROOFING SYSTEMS LISTED
 IN THE PRODUCT APPROVALS WILL BE USED. CIRCLE THE
 FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED.
 SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING.
  
 22) SPECIFY THE FASTENERS THAT WILL BE USED TO INSTALL
 THE STORM PANELS. CIRCLE THE APPROPRIATE ONE ON THE
 PRODUCT APPROVALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-10 Cont ID  
Sent By dpalmer Date 2008-06-10 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2008-06-10 Time 11:13 Sent To P
Notes
2008-06-10 11:13:49** PROVISO**
  
  
 1) NOTE:PLEASE SEE PANEL SCHEDULE IS SHOWING THE
 WASHER AND DRYER AS ONE CIRCUIT YET PLANS CLEARLY SHOW
 THESE AS TWO SEPARATE APPLIANCES.
 PLEASE INCLUDE REQUIRED DEDICATED CIRCUIT FOR WASHER
 AND REVISE PANEL SCHEDULE. 210.11C2.
  
 2) NOTE: PLEASE SEE SMOKE DETECTION DEVICES ARE TO BE
 SHOWN AS SA FOR SMOKE ALARMS UNLESS SYSTEM IS A LOW
 VOLTAGE FIRE ALARM SYSTEM WITH FIRE ALARM PANEL, HORNS
 ETC.
 NFPA-72
  
 3) NOTE: PLEASE VERIFY NEW OR EXISTING REAR OF DWELLING
 RECEPTACLE AS REQUIRED PER 210.52E. SHALL BE GFP AND
 WEATHER PROOF AS REQUIRED PER 210.8A3, 406.8B
  
  
 ** PLEASE REVISE PLANS WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-01 Cont ID  
Sent By dpalmer Date 2008-04-01 Time 12:51 Rev Time 0.00
Received By dpalmer Date 2008-04-01 Time 12:51 Sent To M
Notes
2008-04-01 12:51:41** DENIED**
  
  
 1) NOTE: PLEASE SUBMIT A LAYOUT FOR REQUIRED SMOKE
 ALARMS FOR EXISTING MEETING CURRENT CODE OR FOR NEW TO
 BE INSTALLED. PLEASE SEE FBC R313, NFPA-72 11.5.1.1,
 11.8.3.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE 210.8A1, 210.52D AND 210.11C3 FOR
 MISSING BATHROOM CIRCUIT AND GFI.
 MUST BE 20AMP AND #12.
  
 4) NOTE: PLEASE SEE THE RISER SHOWS A NEW ELECTRICAL
 SERVICE. PLEASE SUBMIT THE FOLLOWING:
 AIC RATING OF NEW MAIN. 110.9
 EQUIPMENT GROUNDING CONDUCTOR MISSING FROM MAIN TO
 SUB-PANEL. 250.110, 250.122 ETC
 MINIMUM OF 20FT OF FOOTER STEEL NOT 9FT AS STATED ON
 PLANS. 250.50.
 LOCATION OF ALL EQUIPMENT, PANEL, DISCONNECT ETC.
 240.24, 408.7, 110.26 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SUBMIT A PANEL SCHEDULE SHOWING THE
 EXISTING AND NEW CIRCUITS.
 408.4, 240.4, 310.16
 FBC 106.3.5.4
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 15:29 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 15:29 Sent To P
Notes
2008-07-09 15:29:52TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 10:29 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 10:29 Sent To Z
Notes
2008-06-04 10:29:34TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-10 Cont ID  
Sent By rmcdouga Date 2008-04-10 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2008-03-31 Time 16:03 Sent To  
Notes
2008-03-31 16:04:02TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-11 Cont ID  
Sent By tgordon Date 2008-07-11 Time 14:48 Rev Time 0.30
Received By tgordon Date 2008-07-11 Time 14:48 Sent To B
Notes
2008-07-11 15:01:50FOR BATH EXHAUST FAN & DRYER VENT ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-04-02 Cont ID  
Sent By tgordon Date 2008-04-02 Time 16:13 Rev Time 0.20
Received By tgordon Date 2008-04-02 Time 16:13 Sent To P
Notes
2008-04-02 16:16:11*** PROVISO ***
 1) A MECHANICAL PERMIT WILL BE REQUIRED FOR THE CLOTHES
 DRYER VENT AND BATH EXHAUST FAN.
  
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-11 Cont ID  
Sent By mperson Date 2008-07-11 Time 14:04 Rev Time 0.00
Received By mperson Date 2008-07-11 Time 14:04 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By mperson Date 2008-06-10 Time 13:28 Rev Time 0.00
Received By mperson Date 2008-06-10 Time 13:28 Sent To B
Notes
2008-06-10 14:17:38PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WAS NO COMMENT RESPONSE FROM THE
 DESIGNER.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. SHEET A2 SANITARY PLUMBING RISER: THE WASHING
 MACHINE MUST DRAIN DOWNSTREAM OF THE BATHROOM.PER
 FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 **THE RESUBMITTED SANITARY PLUMBING RISER IS STILL
 INDICATING THE WASHING MACHINE DRAINING INTO THE WET
 VENTED BATHROOM. THE WASHING MACHINE MUST DRAIN
 DOWNSTREAM OF THE WET VENTED BATHROOM. PER SECTION
 909.1 WET VENT PERMITTED.
  
 3. SHEET A2 SANITARY PLUMBING RISER: THE FOLLOWING IS
 REQUIRED FOR THE WASHING MACHINE.
  
 (A) "OK" COMMENT ADDRESSED.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 *CLEARLY INDICATE THE REQUIRED STANDPIPE ON
 RESUBMITTED DRAWINGS.
  
 **THE RESUBMITTED SANITARY PLUMBING RISER IS
 INCORRECTLY INDICATING THE STANDPIPE MINIMUM OF 18
 INCHES LOCATION FOR THE WASHING MACHINE. PER SECTION
 802.4 STANPIPES.
  
 (C) "OK" COMMENT ADDRESSED.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 *CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT 4'
 A.F.F.
  
 **THE RESUBMITTED SANITARY PLUMBING RISER IS NOT
 INDICATING THE CLEANOUT FOR THE WASHING MACHINE TO BE
 AT 4 FEET ABOVE FINNISH FLOOR (4' A.F.F.) AND IS
 INCORRECTLY INDICATING THE CLEANOUT AS BEING A TRAP.
 PER SECTION 708.1 ACCESS AND SECTION 701.1 SCOPE.
  
 **THE FOLLOWING ARE NEW COMMENTS DUE TO THE SANITARY
 PLUMBING RISER BEING REVISED.
  
 4. SHEET A2 SANITARY PLUMBING RISER: CLEANOUT FOR THE
 LAVATORY BEING INDICATED IN THE WRONG PLACE AND AND
 MSILABELED AS BEING A TRAP. CLEANOUT TO BE LOCATED AT
 THE BASE OF THE STACK AND CORRECTLY IDENTIFIED AS A
 CLEANOUT. PER FBC-PLUMBING SECTION 708.3.4 BASE OF
 STACK.
 NOTE: PER FBC-PLUMBING SECTION 708.7 MINIMUM SIZE
 EXCEPTIONS:(1) A CLEANOUT FOR THIS STACK IS NOT
 REQUIRED WITH THE SINK TRAP BEING INDICATED AS BEING 2
 INCH.
  
 5. SHEET A2 SANITARY PLUMBING RISER: DELETE THE 4 INCH
 CLEANOUT BETWEEN THE WATER CLOSET AND LAVATORY IT IS
 NOT REQUIRED. PER FBC- PLUMBING SECTION 701.1 SCOPE.
  
 6. SHEET A2 SANITARY PLUMBING RISER: THE RESUBMITTED
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET
 A1. PLEASE PROVIDE A FLAT LINE DRAWING OF THE
 UNDERGROUND PLUMBING ON SHEET A1 FLOOR PLAN. AT A
 MINIMUM THE SANITARY ISOMETRIC RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN. THE RESUBMITTED DRAWING IS
 EITHER INDICATNG THE BATHROOM LAVATORY OUT OF THE
 BUILDING OR THE WASHING MACHINE IN THE WRONG PLACE. PER
 FBC- PLUMBING SECTION 701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-07 Cont ID  
Sent By mperson Date 2008-04-07 Time 09:59 Rev Time 0.00
Received By mperson Date 2008-04-07 Time 09:59 Sent To B
Notes
2008-04-07 11:18:07PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A2 SANITARY PLUMBING RISER: VENT REQUIRED FOR
 THE LAVATORY AND WATER CLOSET. PER FBC-2004 PLUMBING
 SECTION 901.1.2 VENTING REQUIRED.
  
 2. SHEET A2 SANITARY PLUMBING RISER: THE WASHING
 MACHINE MUST DRAIN DOWNSTREAM OF THE BATHROOM.PER
 FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 3. SHEET A2 SANITARY PLUMBING RISER: THE FOLLOWING IS
 REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 *WASHING MACHINE BRANCH DRAIN AND STACK SHALL BE 3".
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 *CLEARLY INDICATE THE REQUIRED STANDPIPE ON
 RESUBMITTED DRAWINGS.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 *CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 *CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT 4'
 A.F.F.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By choops Date 2008-06-09 Time 10:39 Rev Time 0.00
Received By choops Date 2008-06-09 Time 10:39 Sent To E
Notes
2008-06-09 10:40:41***APPROVED - RESUB #1***
  
 PROVISO:ADDITION MUST MAINTAIN A MINIMUM SEPARATION
 DISTANCE OF 6' FROM THE EXISTING ACCESSORY STRUCTURE.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-01 Cont ID  
Sent By choops Date 2008-04-01 Time 08:36 Rev Time 0.00
Received By choops Date 2008-04-01 Time 08:36 Sent To E
Notes
2008-04-01 08:41:55***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY THAT
 ACCURATELY REFLECTS THE IMPROVEMENTS ON THE SITE.THE
 SUBMITTED SURVEY DOES NOT APPEAR TO BE ACCURATE.
  
 2)INDICATE SEPARATION DISTANCE FROM PROPOSED
 ADDITION TO THE EXISTING ACCESSORY STRUCTURE.ALSO
 INDICATE THE SETBACK DIMENSIONS OF THE EXISTING
 ACCESSORY STRUCTURE FROM THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK