Plan Review Details - Permit 08030667
Plan Review Stops For Permit 08030667
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 08:04 Rev Time 0.77
Received By jwitmer Date 2008-10-08 Time 08:04 Sent To  
Notes
2008-10-08 08:05:37REVISION "E" SHEET A-1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By jwitmer Date 2008-06-16 Time 11:46 Rev Time 2.22
Received By jwitmer Date 2008-06-16 Time 11:46 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-22 Cont ID  
Sent By jwitmer Date 2008-04-22 Time 06:59 Rev Time 1.33
Received By jwitmer Date 2008-04-22 Time 06:59 Sent To  
Notes
2008-04-22 07:38:24BUILDING PLAN REVIEW
 PERMIT: 08030667
 ADD: 701 NORTHPOINT PARKWAYSUITES 200& 215
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS NOT
 THE 2006 SUPPLEMENTS.
 PLEASE MAKE CORRECTION.
  
 2) SHEET E2 INDICATES EMERGENCY BACK UP LIGHTS AND EXIT
 LIGHT LOCATED IN THE STORAGE ROOM. PLEASE SEE 1013.2
 EGRESS THROUGH INTERVENING SPACES. EGRESS SHALL NOT
 PASS THROUGH STORAGE ROOMS.
  
 3) SHEET A-1 INDICATES THE DEMO- WALLS AND THE NEW
 FLOOR PLAN. THE PLANS INDICATE THIS IS A FULLY
 SPRINKLERED BUILDING BUT THERE ARE NO FIRE SPRINKLER
 PLAN FOR EXISTING LAYOPUT OR NEW HEADS TO BE ADDED,
 PLEASE PROVIDE ADDITIONAL INFORMATION 106.1.2., AND
 604.2 EXISTING BUILDING CODE 604.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 14:12 Sent To PC
Notes
2008-11-10 14:13:08REV #5 ON LAYOTU
 REV# 3 ON RISER, ADD SUB PANEL.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 13:30 Sent To  
Notes
2008-10-06 13:31:15REV#4 E-1

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 13:30 Sent To  
Notes
2008-10-06 13:30:54REV #3

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-08-26 Cont ID  
Sent By dpalmer Date 2008-08-26 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2008-08-26 Time 15:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-08-04 Cont ID  
Sent By dpalmer Date 2008-08-04 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2008-08-04 Time 09:31 Sent To M
Notes
2008-08-04 09:32:08 
 **DENIED4TH REVIEW**
  
 ** COMMENT FROM PREVIOUS REVIEW IS STILL IN NEED OF
 ATTENTION ALONG WITH SEVERAL NEW COMMENTS BASED ON
 CHANGE OF USE IN SOME ROOMS.
  
  
 1) NOTE: PLEASE COORDINATE ALL SHEETS IN SETS. PLEASE
 SEE NOTES FROM PREVIOUS REVIEW WHICH REQUEST TO REMOVE
 ALL SHEETS AND ONLY INSERT NEW SHEETS INTO THE
 COMPLETED SETS. THE NEW PLANS SUBMITTED HAVE SHEETS
 FROM PREVIOUS REVIEW DATED BACK TO PLANS SIGNED AND
 SEALED IN MARCH.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2,
 13-415.2.B.1.
 PLEASE PROVIDE THE CORRECT USE ON INPUT DATA REPORT AND
 SUMMARY SHEETS. IF MEDICAL THEN MEDICAL USE SHOULD BE
 STATED IN THOSE AREAS.
  
 3) NOTE: IT IS THE UNDERSTANDING OF THIS OFFICE THAT
 SOME MEDICAL PROCEDURES WILL BE IN SOME LOCATIONS IN
 THIS BUILD OUT. PLEASE SEE IN FACT THE LIGHTING PLANS
 HAVE NOW BEEN UPDATED TO INCLUDE A NOTE FOR WIRING OF
 LIGHTS AND ALSO A NEW UPS FOR BACK UP AS REQUIRED PER
 NEC 517.45. IN FACT THE PLANS ALSO NOTE TO SEE E-1 FOR
 DETAILS HOWEVER E-1 SHEETS ARE THE SAME SHEETS
 PREVIOUSLY SUBMITTED THROUGH OUT PROJECT WITH NO NEW
 DESIGNS.
 THE RISER AND BRANCH CIRCUITS ON PANELS DO NOT INDICATE
 ANY UPS SYSTEM FOR BACK UP POWER.
 THE PLANS DO NOT INCLUDE ANY INFORMATION FOR TIME OF
 BACK UP.
 THE PLANS DO NOT INDICATE ANY LOCATIONS FOR EQUIPMENT
 OR WIRING OF SYSTEMS.
 THE PLANS DO NOT INDICATE THE REDUNDANT GROUNDING AS
 REQUIRED PER 517.10
 PLEASE SEE 517 FOR ALL AREAS WHICH ARE SPECIFIC TO
 MEDICAL USE.
  
 4) NOTE: PLANS WILL BE ROUTED TO ALL OTHER TRADES FOR
 REVIEW OF ROOMS FOR MEDICAL PROCEDURES.
  
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-09 Cont ID  
Sent By dpalmer Date 2008-07-09 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2008-07-09 Time 13:16 Sent To  
Notes
2008-07-09 13:16:49** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE NOTES FROM PREVIOUS REVIEW.
 THIS OCCUPANCY IS NOT A HOSPITAL WITH OPERATING ROOMS
 ETC. IF THIS IS GOING TO CONTAIN OPERATING ROOMS AND
 ANY USE WHICH FALLS UNDER THE DEFINITIONS OF A HOSPITAL
 THEN ALL PLANS FOR ALL TRADES INCLUDING BUILDING,
 MECHANICAL AND PLUMING NEED TO BE REVISED ACCORDINGLY
 TO MEET REQUIREMENTS OF A HOSPITAL.
 AS THIS IS NOT A HOSPITAL, MAY NOT USE ALLOWANCES FOR A
 HOSPITAL, OPERATING ROOMS ETC. PLEASE ADJUST.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND TABLE
 13-415.2.B.
 PLEASE BE SURE ALL OTHER COMPONENTS ARE FILLED OUT IN
 THE INPUT DATA REPORT.
 WHERE IS PIPING?
 WHERE IS HOT WATER HEATING?
 ** THESE ARE SOME ITEMS WHICH ARE MOST CERTAINLY
 REQUIRED BY CODE AS WELL AS SHOWN ON PLANS.
 13-411, 13-412 ETC
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-12 Cont ID  
Sent By dpalmer Date 2008-06-12 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2008-06-12 Time 14:58 Sent To  
Notes
2008-06-12 14:58:57** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE TABLE 13-415.2.C WHICH ALLOWS 1.0
 WATTS PER SQ FT BASED ON THIS OCCUPANCY. THIS IS NOT A
 HOSPITAL.
 THE SQ FT AREA IS 3467 AND BASED ON OFFICE USE, THE
 ALLOWANCE FOR GENERAL LIGHTING PER THE TABLE IS 1.0 W
 PER SQ FT.
 IF THIS OCCUPANCY IS OR WAS DESIGNATED AS A HOSPITAL
 SEVERAL OTHER CODE REQUIREMENTS WOULD BE IMPLEMENTED.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 FOR REQUIRED
 LIGHTING CONTROLS. THE NEW DETAIL PROVIDED ONLY
 INDICATES ONE OCCUPANCY SENSOR WALL SWITCH. THE ISSUE
 IS WHERE AND WHAT CONTROLS ARE SWITCHES GOING TO
 OPERATE AUTOMATICALLY?
 NONE OF THOSE OTHER DEVICES SHOW ANY AUTOMATED CONTROL.
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 13:37 Rev Time 0.00
Received By dpalmer Date 2008-04-02 Time 18:02 Sent To  
Notes
2008-04-03 13:37:39** DENIED**
  
 1) NOTE: PLEASE SHOW THE LIGHTING CONTROLS FOR NEW
 BEING INSTALLED PER 13-415.1.ABC.1.1 AND .1.2.
 PLEASE SEE SOME SWITCHES DO NOT SHOW WHAT THESE ARE:
 FOR EXAMPLE:
 PLEASE SEE THE DOUBLE SS AND THE DOUBLE SS IN SQUARE
 BOXES. WHAT ARE THESE?
 PLEASE SEE THE SYMBOL LEGEND THESE COULD NOT BE
 LOCATED.
  
 2) NOTE: PLEASE BE SURE THE CERTIFICATION SHEET ON THE
 SUBMITTED CALCULATIONS IS SIGNED, DATED AND SEALED.
 THE FIRST/COVER SHEET WAS DONE HOWEVER NEED THE CERT
 SHEET. PLEASE BE SURE THE OWNER AGENT IS ALSO SIGNED.
 FBC 13-103.1, FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE THE PANEL HC MAY NOT BE LOCATED IN
 THE STORAGE ROOM. PLEASE RE-LOCATE. 408.17,240.24 AND
 110.26
  
 4) NOTE: PLEASE SEE THE CONDUIT TO NEW PANEL HC IS NOT
 LARGE ENOUGH FOR THE AMOUNT AND THE SIZE OF THE
 CONDUCTORS. A 3/4 INCH CONDUIT WILL NOT PERMIT 5-#6 AND
 1-10#. PLEASE SEE TABLES IN CHAPTER 9 FOR CONDUIT
 FILL.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-04-02 18:02:30IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 09:40 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 09:40 Sent To  
Notes
2008-10-21 09:40:59REVISION DATED 9/12/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-20 Cont ID  
Sent By mawillia Date 2008-06-20 Time 14:47 Rev Time 0.00
Received By mawillia Date 2008-06-20 Time 14:18 Sent To  
Notes
2008-06-20 14:42:05*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS A-1, A-4, F-1, & E-2 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2008-04-28 Time 10:38 Sent To  
Notes
2008-04-28 10:57:21***DENIED***
  
 1) THE PLANS INDICATE AN OCCUPANT LOAD OF 52 UNDER
 PROJECT DATA. NFPA 101, 2003 SECTION 7.2.1.4.2 REQUIRES
 EGRESS DOORS TO SWING IN THE DIRECTION OF TRAVEL.
 PLEASE ADVISE IF EXCEPTION HAS BEEN MET.
  
 2) PLEASE SEE BUILDING COMMENT #2 REGARDING EXITING
 THROUGH A STORAGE AREA.
  
 3) PLANS INDICATE FIRE ALARM EQUIPMENT. PLEASE ADD TO
 ELECTRICAL LEGEND TO VERIFY SPECIFIC EQUIPMENT.
  
 4) PLANS DO NOT ILLUSTRATE FIRE SPRINKLER LAYOUT.
 SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 BOTH FIRE SPRINKLER AND FIRE ALARM REMODEL WHEN
 APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 16:47 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 16:47 Sent To M
Notes
2008-11-19 16:48:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 13:35 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 13:35 Sent To E
Notes
2008-11-05 13:36:10TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 14:31 Sent To E
Notes
2008-09-30 14:31:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 10:33 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 10:33 Sent To  
Notes
2008-09-23 10:36:42TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 08:50 Sent To M
Notes
2008-09-03 08:51:08TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 14:38 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 14:37 Sent To  
Notes
2008-08-15 14:39:46TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 09:06 Sent To E
Notes
2008-07-30 09:06:29TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 15:24 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 15:24 Sent To E
Notes
2008-06-24 15:25:31TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 14:27 Sent To  
Notes
2008-05-19 14:31:34TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 11:00 Rev Time 0.00
Received By mwennerg Date 2008-03-28 Time 14:33 Sent To  
Notes
2008-03-28 14:35:20TO "COMM" BD#13

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-11-24 Cont ID  
Sent By rregueir Date 2008-11-24 Time 20:36 Rev Time 0.00
Received By rregueir Date 2008-11-24 Time 20:35 Sent To PC
Notes
2008-11-24 20:36:11REVISED M1

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 12:15 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 12:15 Sent To  
Notes
2008-10-18 12:15:48REVISED M-1

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-09-04 Cont ID  
Sent By rregueir Date 2008-09-04 Time 10:56 Rev Time 0.00
Received By rregueir Date 2008-09-04 Time 10:39 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 14:06 Rev Time 0.00
Received By rregueir Date 2008-08-27 Time 13:55 Sent To PC
Notes
2008-08-27 14:05:46PREVIOUS REVIEW COMMENTS DATED 8/11/08 HAVE NOT BEEN
 ADDRESSED (ATTACHED TO THESE COMMENTS FOR REFERENCE).
 PLEASE NOTE THAT PREVIOUSLY STAMPED PAGES HAVE BEEN
 VOIDED AS A RESULT OF THE CHANGES MADE AFTER THE PLANS
 PASSED REVIEW ON 6/4/08. PLEASE REPLACE THE VOIDED
 PAGES AND MAKE THE NECESSARY CORRECTIONS FROM THE LAST
 REVIEW AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-08-11 Cont ID  
Sent By rregueir Date 2008-08-11 Time 16:08 Rev Time 0.00
Received By rregueir Date 2008-08-11 Time 15:55 Sent To PC
Notes
2008-08-11 16:07:43REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 SOME ROOMS WITHIN THIS TENANT SPACE HAVE BEEN
 RECLASSIFIED TO "PROCEDURE" ROOMS, RATHER THAN THE
 OFFICE OCCUPANCY PREVIOUSLY USED IN THE OUTSIDE AIR
 CALCULATIONS ON PAGE M-3. THE VENTILATION REQUIREMENTS
 FOR MEDICAL PROCEDURE ROOMS SHALL BE DETERMINED IN
 ACCORDANCE WITH TABLE E-1 OF APPENDIX E OF ASHRAE
 62.1-2004 PER NOTE 7 OF TABLE 6.1. THIS REQUIRES AN
 OCCUPANT LOAD OF 20 PPL PER 1000 SQ FT. AND A
 VENTILATION RATE OF 15 CFM PER PERSON. PLEASE CORRECT
 THE OUTSIDE AIR CALCULATIONS AND SHOW HOW THE INCREASED
 VENTILATION RATES WILL BE PROVIDED FOR THESE ROOMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-04 Cont ID  
Sent By rregueir Date 2008-06-04 Time 14:10 Rev Time 0.00
Received By rregueir Date 2008-06-04 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-12 Cont ID  
Sent By rregueir Date 2008-04-12 Time 11:24 Rev Time 0.00
Received By rregueir Date 2008-04-11 Time 16:22 Sent To  
Notes
2008-04-12 11:24:02REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M-1: STORAGE ROOM 100 SHOWS AN AIR TRANSFER
 OPENING WITH FIRE DAMPER TO REMAIN IN THE WALL AT
 CORRIDOR. PG A-1 SHOWS A DOUBLE DOOR BEING DEMOLISHED
 AND A NEW RATED WALL BEING BUILT AT THIS LOCATION. IS
 THIS FIRE DAMPER TO BE REMOVED AND REINSTALLED,
 REPLACED, OR IS IT EXPECTED TO BE UNDISTURBED DURING
 THIS WALL RECONFIGURATION? PLEASE CLARIFY. FBCM 607.1
 AND FBCB 106.1.1
  
 2. PG M-1: DUCT SMOKE DETECTOR FOR AHU-1 SHALL BE TIED
 INTO THE BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH
 FBCM 606.4.1.
  
 3. PG M-1: KEYNOTE #12 CALLS FOR REFRIGERANT LINES TO
 PENETRATE THE FLOOR/CEILING ASSEMBLY TO THE FIRST
 FLOOR. PROVIDE A THROUGH-PENETRATION FIRESTOP SYSTEM
 ASSEMBLY DETAIL TO SHOW HOW THESE PENETRATIONS ARE TO
 BE PROTECTED IN ACCORDANCE WITH FBCB 712.4.
  
 4. PG M-1 AND M-2: ALL RECONFIGURED SPACES INTENDED FOR
 OCCUPANCY SHALL BE PROVIDED WITH NATURAL OR MECHANICAL
 VENTILATION OR EXHAUST IN ACCORDANCE WITH FBCEB 609.1
 AND FBCM 401.2. AS NATURAL VENTILATION IS NOT BEING
 PROPOSED, PROVIDE OUTDOOR AIR CALCULATIONS IN
 ACCORDANCE WITH FBCM TABLE 403.3 OR SECTION 403.4.
 DECLARE ON PLANS WHICH METHOD IS BEING USED FOR THESE
 CALCULATIONS.
  
 5. PG M-2: FAN SCHEDULE CALLS FOR EF-10 AND EF-12 TO
 RUN CONTINUOUSLY, INTERLOCKED WITH AHU-1 FAN. HOWEVER,
 PG E-2 SHOWS THESE FANS BEING CONTROLLED BY WALL
 SWITCHES. COORDINATE PLANS, SCHEDULES AND NOTES TO SHOW
 ACTUAL DESIGN INTENT. FBCM 401.1, FBCB 106.1.1.
  
 6. PG M-1: NOTE #17 CALLS FOR EXHAUST DUCT IN PLENUM TO
 BE ENCLOSED IN A DUCT. THE EXHAUST DUCT SHALL BE
 ISOLATED FROM THE PLENUM BY PLENUM CONSTRUCTION USING
 AN APPROVED PLENUM/AIR BARRIER IN ACCORDANCE WITH FBCM
 603.8 TO BE CONSIDERED OUTSIDE THE PLENUM SPACE. ANY
 OTHER METHOD OF ISOLATION FROM THE PLENUM SPACE SHALL
 BE SUBMITTED TO THE BUILDING OFFICIAL IN WRITING UNDER
 THE PROVISIONS OF FBCB 104.11 FOR ALTERNATE MATERIALS
 AND METHODS.
  
 7. ENERGY CALCULATIONS: MECHANICAL PORTIONS OK. PLEASE
 SEE ELECTRICAL COMMENT #2 REGARDING SIGNATURE AND SEAL
 ON THE CERTIFICATION PAGE.
  
 NOTE: PLEASE RESPOND TO EACH REVIEW COMMENT IN WRITING
 TO SPEED THE RESUBMITTAL PROCESS. REMOVE ALL OLD/VOIDED
 SHEETS FROM RESUBMITTED PLANS AND RETURN ONE OLD SET
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-04 Cont ID  
Sent By kstevens Date 2008-06-04 Time 16:18 Rev Time 0.00
Received By kstevens Date 2008-06-04 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 13:47 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 13:47 Sent To  
Notes
2008-04-12 13:56:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE CITY WPB
  
 1. SHT A-1 DETAIL #1 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. DEMO'D PIPING SHALL BE REMOVED BACK TO THE
 BRANCH LINE OR BLDG DRAIN.
  
 2. SHT A-3 THE FLUSH CONTROLS OF THE W/C SHALL BE ON
 THE WIDE SIDE OF THE W/C. SECTION 11-4.16.5. (SHOWN ON
 THE WALL SIDE).
  
 3. SHT P-1 WATER HEATER PIPING DIAGRAM. THE EXPANSION
 RELIEF VALVE SHALL DRAIN INTO THE HUB DRAIN WITH AN AIR
 GAP, OR THE WATER HEATER SHALL BE RAISED ABOVE THE PAN
 DRAIN OPENING.
  
 4. SHT P-1 KEY NOTES #11 INDICATE THE TERMINATION POINT
 FOR THE CONDENSATE FROM THE AHU. CONDENSATE SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM, BUT SHALL CONNECT TO A
 DEDICATED CONDENSATE RISER OR SHALL DRAIN SEPARATELY
 FROM THE BUILDING. ARTICLE III SECTION 90-125(B)(5).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  