| 2008-04-02 15:20:37 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON ELECTRICAL AS WELL AS ARCHITECTURAL SHEETS. SOME OF |
| | THESE ARE ALREADY LISTED HOWEVER SOME CHANGES ARE |
| | NEEDED. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2002 NFPA-72 (IF FIRE ALARM SYSTEM IS PRESENT) |
| | PLANS DO CALL FOR FA SYSTEM. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-400.3.A, |
| | 13-400.3.B, 13-400.3.C, 13-101.1.2 AND .1.3. |
| | PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| | CALCULATIONS.13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | FIRST ITEM IS THE METHOD SUBMITTED FOR ENERGY |
| | CALCULATIONS IS THAT OF METHOD *A* WHICH IS FOR WHOLE |
| | BUILDING COMPLIANCE. THIS IS NOT A WHOLE BUILDING; THIS |
| | METHOD *A* IS NOT AN OPTION. |
| | PLEASE ALSO SEE THAT IN ANY CASE THE VERSION MUST BE |
| | THE ADOPTED VERSION PER THE FBC. THE VERSION 2.11 |
| | SUBMITTED WAS UNDER THE OLDER 2004 CODE. THE VERSION |
| | CHANGED ON DEC 8TH, 2006 WHICH IS ALMOST ONE AND HALF |
| | YEARS AGO. |
| | PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE INPUT |
| | DATA REPORT. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR LIGHTING WHICH STATES ONLY ONE |
| | FIXTURE TYPE WHICH IS 26W EACH HOWEVER THE PLANS |
| | CONTAINS NUMEROUS OTHER FIXTURES WHICH ARE NOT PART OF |
| | THE IDR. HOW IS THIS POSSIBLE? PLEASE BE SURE ALL ON |
| | PLANS COORDINATES WITH THE CALCULATIONS. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE LIGHTING CALCULATIONS ON PLANS WHICH |
| | CONTAIN MANY MORE FIXTURES. EXTERIOR IS BLANK ON THE |
| | IDR? |
| | PLEASE SEE THE PRINTING OF THE OWNER AGENT AS A COMPANY |
| | IS NOT ACCEPTABLE. THIS REQUIRES A SIGNATURE FROM THE |
| | OWNER AGENT. |
| | |
| | 2) NOTE: PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 AND |
| | PLACE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 3) NOTE: PLEASE GIVE THE MAXIMUM TIMES ON THE OCCUPANCY |
| | DEVICES. 13-415.1.ABC.1.1, .1.2. |
| | |
| | 4) NOTE: PLEASE COMPLETE ALL LOCATIONS FOR DEVICES PER |
| | THE PROPOSED FA SYSTEM PER FBC ADA REQUIREMENTS |
| | 11-4.28.1,.2 AND .3(4). MINIMUM LOCATIONS AND MINIMUM |
| | LEVELS FOR DEVICES ARE NEEDED. |
| | |
| | 5) NOTE: PLEASE SEE NOTE #1 ABOVE WITH RESPECT TO |
| | LIGHTING ON PLANS AND ALSO COMPLETE INFORMATION FOR |
| | ITEMS WHICH ARE SHOWN AS J-BOXES IN CALCULATIONS FOR |
| | PERFORMANCE LEVELS. 13-415.2. |
| | |
| | 6) NOTE: PLANS/PANEL SCHEDULE INDICATES A SMOKE ALARM |
| | CIRCUIT. WHAT IS THIS? SEE NFPA-72 DEFINITIONS AND |
| | NOTES ABOVE WITH RESPECT TO ANY MINIMUM DESIGNS |
| | REQUIRED. |
| | PLEASE ALSO COORDINATE THE LOAD ON PANEL WITH THAT OF |
| | THE LOAD SHOWN ON LOAD CALCULATIONS FOR THIS SAME |
| | CIRCUIT. |
| | |
| | 7) NOTE: PLEASE VERIFY ROOF-TOP GFI PER 210.8B, 210.63. |
| | |
| | PLANS INDICATE A GFI LOCATED ABOVE THE CEILING OF |
| | BATHROOM FOR THE AHU, HOWEVER THIS IS NOTED ON PANEL |
| | SCHEDULE AS ROOF-TOP? |
| | |
| | 8) NOTE: PLEASE ALSO SUBMIT DETAIL/INFORMATION FOR THE |
| | REQUIRED DISCONNECT FOR THE CU. 440.11. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |