| | DENIED |
| | |
| | 1) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THATIS RELEVANT PER 9B-72. |
| | THESE SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS THE SYSTEM |
| | COMPONENTS/ FASTENER LIST PAGES. ALL CAN BE FOUND ON |
| | WWW.FLORIDABUILDING.ORG ******ONLY ONE COPY OF |
| | PRODUCT APPROVAL WAS SUBMITTED*********** |
| | |
| | 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST. OUR |
| | VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND |
| | MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC********OUR COST SHEETS VALUE BAHAMA |
| | SHUTTERS AT $30 + PER SQUARE FOOT********* |
| | |
| | 3)SHUTTER PERMIT APPLICATIONS REQUIRE 2 COPIES OF A |
| | KEY PLAN (WITH EGRESS AND OPENING SIZES SHOWN), SHUTTER |
| | SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS |
| | SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE |
| | AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT |
| | INFORMATION SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, |
| | MOUNTING CONNECTION METHOD, ANCHOR TYPE, SHUTTER SPAN |
| | (VERTICAL OR HORIZONTAL), ETC.) ******* PLEASE SEE THE |
| | ATTACHED MEMO AND SCHEDULE.******* |
| | |
| | BLDG PLAN REVIEW |