Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-03 Cont ID  
Sent By mjacobs Date 2008-07-03 Time 07:29 Rev Time 0.00
Received By mjacobs Date 2008-07-03 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By mjacobs Date 2008-05-09 Time 18:59 Rev Time 0.00
Received By mjacobs Date 2008-05-09 Time 18:32 Sent To PC
Notes
2008-05-09 18:40:11BUILDING PROVISO:
 TO BE IN PLACE AT C.O:
  
 PRIVATE
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-04-05 Cont ID  
Sent By mjacobs Date 2008-04-05 Time 13:53 Rev Time 0.00
Received By mjacobs Date 2008-04-05 Time 13:26 Sent To PC
Notes
2008-05-09 18:39:40BUILDING PROVISO:
 TO BE IN PLACE AT C.O:
  
 PRIVATE
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
  
  
2008-04-05 13:53:23 
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-10 Cont ID  
Sent By btrobaug Date 2008-06-10 Time 09:51 Rev Time 0.00
Received By btrobaug Date 2008-06-10 Time 09:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By btrobaug Date 2008-05-09 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2008-05-09 Time 14:47 Sent To P
Notes
2008-05-09 15:11:00 
  
  
  
  
 PROVISO
  
 SUBMIT A LOAD CALCULATION INCLUDING THE ADDED HEAT PUMP
 LOAD TO VERIFY THE EXISTING SERVICE IS ADEQUATE FOR THE
 ADDED POOL EQUIPMENT LOAD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-02 Cont ID  
Sent By jleahy Date 2008-04-02 Time 16:47 Rev Time 0.45
Received By jleahy Date 2008-04-02 Time 16:47 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-05-09 Cont ID  
Sent By mperson Date 2008-05-09 Time 15:36 Rev Time 0.00
Received By mperson Date 2008-05-09 Time 15:36 Sent To B
Notes
2008-05-09 15:37:01NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-04-03 Cont ID  
Sent By mperson Date 2008-04-03 Time 13:35 Rev Time 0.00
Received By mperson Date 2008-04-03 Time 13:35 Sent To B
Notes
2008-04-03 13:36:03NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 14:58 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 14:58 Sent To Z
Notes
2008-06-30 14:58:43TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 12:42 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 12:42 Sent To E
Notes
2008-06-02 12:42:34TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 09:08 Sent To Z
Notes
2008-05-20 09:09:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 09:15 Rev Time 0.00
Received By adarroug Date 2008-04-25 Time 09:15 Sent To E
Notes
2008-04-25 09:16:12PLANS SUBMITTED BACK IN AFTER FEES WERE PAID,AND
 ROUTED TO "JLEAHY"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 15:48 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 15:48 Sent To Z
Notes
2008-04-21 15:48:38TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-04-05 Time   Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 13:19 Sent To  
Notes
2008-03-27 13:20:06TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By mperson Date 2008-05-09 Time 15:35 Rev Time 0.00
Received By mperson Date 2008-05-09 Time 15:35 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By mperson Date 2008-04-03 Time 11:48 Rev Time 0.00
Received By mperson Date 2008-04-03 Time 11:48 Sent To G
Notes
2008-04-03 13:35:07PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2, PIPING SCHEMATIC IS NOT INDICATING THE THE
 HEAT PUMP ON SHEET 1, POOL EQUIPMENT. AT A MINIMUM THE
 PIPING SCHEMATIC ON SHEET 2, SHALL REFLECT THE HEAT
 PUMP BEING INDICATED ON SHEET 1, POOL EQUIPMENT. PER
 FBC RESIDENTIAL CHAPTER 41, SECTION R4101.6 ENGINEERING
 DESIGN AND PER (W.P.B.) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE PROVIDE A DETAIL OR MANUFACTURER
 SPECIFICATIONS SHEET WITH THE MAKE AND MODEL NUMBER OF
 THE VACUUM FITTING COMPLIANT WITH THE FOLOWING.
 FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
  
 3. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-07-01 Cont ID  
Sent By choops Date 2008-07-01 Time 11:29 Rev Time 0.00
Received By choops Date 2008-07-01 Time 11:29 Sent To B
Notes
2008-07-01 11:29:48***APPROVED - REVISION #1 - ADDING FOOTER TO POOL
 DECK***
  
 PROVISO:FOOTER SHALL NOT ENCROACH THE PROPERTY LINE.
  
  
  
  
 SENT TO "B" - MJ

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By choops Date 2008-05-27 Time 09:21 Rev Time 0.00
Received By choops Date 2008-05-27 Time 09:21 Sent To PC
Notes
2008-05-27 09:22:12***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By choops Date 2008-04-23 Time 16:43 Rev Time 0.00
Received By choops Date 2008-04-23 Time 16:43 Sent To E
Notes
2008-04-23 16:49:54***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 3)PLEASE PROVIDE RIVERWALK ACC (ARCHITECTURAL
 CONTROL COMMITTEE) APPROVAL.
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-31 Cont ID  
Sent By choops Date 2008-03-31 Time 09:42 Rev Time 0.00
Received By choops Date 2008-03-31 Time 09:42 Sent To E
Notes
2008-03-31 09:45:03***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 3)PLEASE PROVIDE RIVERWALK ACC (ARCHITECTURAL
 CONTROL COMMITTEE) APPROVAL.
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - JL