| 2008-03-28 16:40:42 | REROOF FORR2 BUILDING.BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- THERE IS A NOTE ON PAGE 1 OF NOA 03-0501.02 THAT |
| | APPROVED ASSEMBLY TO BE USED IS ON PAGE 9 AND 10, WHICH |
| | IS ANINSULATEDASSEMBLY.BUT,ENGINEER |
| | CALCULATIONS FOR NAIL ENHANCING SPECIFIES SHEETS 26 AND |
| | 27 WHICH IS A NON-INSULATED ASSEMBLY.CONTRACTOR AND |
| | ENGINEERTO COORDINATE AND DECIDE WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. THEN PROVIDE CORRESPONDING |
| | INFORMATION THAT MATCHES. |
| | |
| | 3- RAS 117 CALCULATIONS FOR NAIL ENHANCING DONE BY R. |
| | N. SAILAPPAN, PE.NEED TO BE REVISED.ACCORDING TO |
| | CALCULATIONS SHOWN ABOVE THE RECOMMENDED BASE SHEET |
| | ATTACHMENT PATTERNTHE ANCHOR SPACING FOR 3 ROWS IN |
| | THE FIELD SHEET OF PERIMETER AREA IS 6"O.C.NOT 9". |
| | AND, THE ANCHOR SPACING FOR 3 ROWS IN THE FIELD OF |
| | CORNER AREAS IS 4"O.C.NOT 6". |
| | ***NOTE: ENGINEER TO COORDINATE WITH CONTRACTOR |
| | SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED.SEE ITEM |
| | ONE ABOVE. |
| | |
| | 4- OWES $37.65 FOR UPDATED VALUATION AS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |