Plan Review Details - Permit 08030574
Plan Review Stops For Permit 08030574
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By kconrad Date 2008-04-10 Time 17:00 Rev Time 0.00
Received By kconrad Date 2008-04-10 Time 16:00 Sent To  
Notes
2008-04-10 16:52:33PROJECT: 1369 OLD OKEECHOBEE ROAD/#08030574
  
 PROJECT DETAIL: INSTALL 45' FLAGPOLE
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION
  
 STATUS: DENIED.
  
 COMMENTS:
  
 1) PROVIDE CALCULATIONS AS PER EXCEPTION #5:
  
 1609.1.1 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE 7. WIND
 SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION
 AND WIND PRESSURES SHALL BE ASSUMED TO ACT NORMAL TO
 THE SURFACE CONSIDERED.
 EXCEPTIONS:
 1. PROVISIONS OF SECTION 1609.6 SHALL BE PERMITTED FOR
 BUILDINGS 60 FEET (18.3 M) HIGH OR LESS.
 2. WIND TUNNEL TESTS TOGETHER WITH APPLICABLE SECTIONS
 OF 1609.6.
 3. SUBJECT TO THE LIMITATIONS OF SECTIONS 1609.1.1.1,
 1609.1.4, AND 1609.3, THE PROVISIONS OF IBHS GUIDELINE
 FOR HURRICANE RESISTANT RESIDENTIAL CONSTRUCTION SHALL
 BE PERMITTED FOR APPLICABLE GROUP R2 AND R3 BUILDINGS
 FOR A BASIC WIND SPEED OF 140 MPH (63 M/S) OR LESS IN
 EXPOSURE B IN ACCORDANCE WITH FIGURE 1609 AND SECTION
 1609.4. PROVISIONS FOR DESIGN WIND SPEEDS OF 140 MPH
 (63 M/S) IN THE GUIDELINE FOR HURRICANE RESISTANT
 RESIDENTIAL CONSTRUCTION SHALL ALSO BE PERMITTED FOR
 BUILDINGS FOR A BASIC WIND SPEED OF 120 MPH (54 M/S) OR
 LESS IN EXPOSURE C IN ACCORDANCE WITH FIGURE 1609 AND
 SECTION 1609.4, AND PROVISIONS FOR DESIGN WIND SPEEDS
 OF 120 MPH (54 M/S) IN THE GUIDELINE FOR HURRICANE
 RESISTANT RESIDENTIAL CONSTRUCTION SHALL BE PERMITTED
 FOR BUILDINGS FOR A BASIC WIND SPEED OF 100 MPH (45
 M/S) OR LESS IN EXPOSURE C IN ACCORDANCE WITH FIGURE
 1609 AND SECTION 1609.4.
 4. SUBJECT TO THE LIMITATIONS OF SECTIONS 1609.1.1.1,
 1609.1.4, AND 1609.3, PROVISIONS OF ANSI/AF&PA WFCM,
 WOOD FRAME CONSTRUCTION MANUAL FOR ONE- AND TWO-FAMILY
 DWELLINGS SHALL BE PERMITTED FOR APPLICABLE WOOD FRAME
 BUILDINGS OF GROUP R3 OCCUPANCY FOR A BASIC WIND SPEED
 OF 150 MPH OR LESS IN ACCORDANCE WITH FIGURE 1609 AND
 SECTION 1609.4.
 5. DESIGNS USING NAAMM FP-1001 SPECIFICATION FOR DESIGN
 LOADS OF METAL FLAGPOLES.
  
 2)PLEASE INDICATE GRADE AND SIZE OF REINFORCING STEEL
 ANG WWF GAGE.
  
 3) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS.
  
 4) PLEASE INDICATE THE CONCRETE DESIGN/COMPRESSIVE
 STRENGTH.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-10 Cont ID  
Sent By kconrad Date 2008-04-10 Time 17:33 Rev Time 0.00
Received By kconrad Date 2008-03-25 Time 15:04 Sent To  
Notes
2008-03-25 15:05:02TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-28 Cont ID  
Sent By choops Date 2008-03-28 Time 11:23 Rev Time 0.00
Received By choops Date 2008-03-28 Time 11:23 Sent To I
Notes
2008-03-28 11:23:23***APPROVED***
  
  
  
  
 SENT TO "B" - MISC. 2