Plan Review Details - Permit 08030525
Plan Review Stops For Permit 08030525
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-02-18 Cont ID  
Sent By rmcdouga Date 2009-02-18 Time 14:44 Rev Time 0.00
Received By rmcdouga Date 2009-02-18 Time 14:44 Sent To  
Notes
2009-02-18 14:51:12PROVISO ITEM FOR ROOFING HAS BEEN ADRESSED. RAS 117
 CALCULATIONS FOR NOA 03-0716.05 MULE-HIDE SELF-ADHERING
 BITUMEN ROOF SYSTEM ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-29 Cont ID  
Sent By rmcdouga Date 2009-01-29 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2009-01-29 Time 15:46 Sent To  
Notes
2009-01-29 15:53:14REVISION TO CHANGE FROM TAMKO MODIFIED ROOFING TO
 MULE-HIDE SELF-ADHERING ROOFING IS OK WITH THE
 FOLLOWING PROVISO.
  
 PROVISO
  
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT THE
 CORNERS FROM AN ARCHITECT, ENGINEER OR REGISTERED ROOF
 CONSULTANT IS REQUIRED TO BE SUBMITTED FOR APPROVAL PER
 LIMITATION #7 ON PAGE 43 OF THE NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-05 Cont ID  
Sent By rmcdouga Date 2008-08-05 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2008-08-05 Time 13:27 Sent To  
Notes
2008-08-05 14:09:19BUILDING PROVISO
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS
 REQUIRED AT FIRST INSPECTION. FS 713
  
 2) PRODUCT APPROVAL FOR TAMKO MODIFIED ROOF SYSTEM NOA
 07-0111.03 WAS SUBMITTED. THE ROOFING CONTRACTOR IS TO
 SPECIFY THE ASSEMBLY, FASTENING OPTION, DESIGN PRESSURE
 AND ENHANCED FASTENING AT PERIMETER AND CORNER AREAS
 CALCULATED IN ACCORDANCE WITH RAS 117.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-18 Cont ID  
Sent By rmcdouga Date 2008-06-18 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2008-06-18 Time 16:53 Sent To  
Notes
2008-06-18 16:28:122004 FBC W/2007
 ENCLOSE GARAGE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED TO BE SUBMITTED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 3) SUBMIT TWO COPIES OF AN ENERGY CALCULATION FORM AS
 REQUIRED BY FBC CHAPTER 13-600. NOTE: THE OWNER/AGENT
 IS REQUIRED TO SIGN AND DATE THE FORM.
  
 4)SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF COVERING
 MATERIAL, THE NEW SINGLE HUNG WINDOWS, THE HARDIE PANEL
 SIDING AND THE SIMPSON CONNECTORS AS REQUIRED BY DCA
 RULE 9B-72.
  
 5) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRE-FAB FIREPLACE AND CHIMNEY.
 FBC R1002 AND R1004.
  
 7) SPECIFY THE ROOF SHEATHING FASTENING ON THE PLANS.
 SPECIFY THE FASTENER SPACING FOR THE 8D RING SHANK
 NAILS FOR THE ROOF SHEATHING FASTENING ON SHEET S-1 AS
 REQUIRED BY SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By rmcdouga Date 2008-03-25 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2008-03-25 Time 07:00 Sent To  
Notes
2008-03-25 11:16:342004 FBC W/2007
 ENCLOSE GARAGE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED TO BE SUBMITTED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. (561)233-5025
  
 3) SUBMIT TWO COPIES OF AN ENERGY CALCULATION FORM AS
 REQUIRED BY FBC CHAPTER 13-600. NOTE: THE OWNER/AGENT
 IS REQUIRED TO SIGN AND DATE THE FORM.
  
 4) THE ADDRESS AND TELEPHONE NUMBER LISTED IN THE TITLE
 BLOCK ON THE LAST SHEET IS DIFFERENT FROM THE OTHER
 SHEETS, WHICH ARE THE ONES LISTED WITH THE DBPR. PLEASE
 CORRECT. FAC 61G1- 16.004.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE ROOF COVERING
 MATERIAL. DCA RULE 9B-72. IF THE WALL COVERING IS A
 MANUFACTURED PRODUCT SUCH AS HARDIPLANK OR VINYL
 SIDING, SUBMIT PRODUCT APPROVALS.
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS AND
 LISTING FOR THE PRE-FAB FIREPLACE AND CHIMNEY. FBC
 R1002 AND R1004.
  
 8) PROVIDE DETAILS OF THE PRE-FAB FIREPLACE ENCLOSURE
 CONSTRUCTION. FBC 106.1.1* CITY AMENDMENTS.
  
 9) SPECIFY THE ROOF PITCH FOR THE NEW ROOF AT THE
 ENCLOSED GARAGE. FBC 106.1.1* CITY AMENDMENTS.
  
 10) SPECIFY THE OVERHANG DIMENSIONS AT THE NEW ROOF.
 SHOW COMPLIANCE WITH R320.7 GUTTERS WITH DOWNSPOUTS ARE
 REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES (152 MM) HORIZONTAL PROJECTION EXCEPT FOR GABLE
 END RAKES OR ON A ROOF ABOVE ANOTHER ROOF.
  
 11) PROVIDE A WALL SECTION THROUGH THE ENCLOSED GARAGE
 SHOW THE EXISTING WALL CONSTRUCTION, FURRING, WALL AND
 ATTIC INSULATION, ATTIC VENTS, WOOD CONNECTORS,
 EXTERIOR AND INTERIOR FINISHES, ETC. FBC 106.1* CITY
 AMENDMENTS.
  
 12) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. SPECIFY THE SIZE AND SPACING OF ATTIC VENTS.
  
 13) SUBMIT 2 COPIES OF A SURVEY/SITE PLAN INDICATING
 THE DISTANCES TO PROPERTY LINES. FBC R302
  
 14) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. IN
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. SPECIFY SIZE AND LOCATION.
  
 15) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
  
 16) SHOW COMPLIANCE WITH SECTION R319 PROTECTION
 AGAINST DECAY. R319.1 LOCATION REQUIRED. IN AREAS
 SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE
 R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. 5.WOOD SIDING, SHEATHING AND
 WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND.
  
 17) PROVIDE DETAILS OF THE BEAM AND COLUMNS WHERE THE
 LOAD BEARING WALL WILL BE REMOVED BETWEEN THE EXISTING
 FAMILY ROOM AND THE ENCLOSED GARAGE. SPECIFY THE SIZE
 OF THE LAMINATED BEAM. SHOW THE CONTINUOUS LOAD PATH
 FROM SECOND STORY WALL TO THE FOUNDATION. SPECIFY ALL
 CONNECTORS. SPECIFY THE REQUIRED FOUNDATION FOR THE
 COLUMNS SUPPORTING THIS BEAM. SEE R301.1.
  
 18) SPECIFY THE SPACING OF THE BOTTOM PLATE ANCHORS ON
 THE KNEE WALL DETAIL ON THE LAST SHEET. SEE R301.1.
  
 19) THE KNEE WALL AND GABLE END DETAILS ON THE LAST
 SHEET SPECIFY LATH AND STUCCO FOR THE EXTERIOR WALL
 COVERING. THE ELEVATIONS SPECIFY SIDING PLEASE
 CORRECT.
  
 20) SPECIFY 8 D RING SHANK NAILS ON THE ROOF NAILING
 PATTERN NOTES ON THE LAST SHEET. SEE SECTION R803.2.3.1
 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL CODE.
  
 21) SHOW COMPLIANCE WITH R313.1.1 ALTERATIONS, REPAIRS
 AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.
 EXCEPTIONS:
 1.SMOKE ALARMS IN EXISTING AREAS SHALL NOT BE
 REQUIRED TO BE INTERCONNECTED AND HARD WIRED WHERE THE
 ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF
 INTERIOR WALL OR CEILING FINISHES EXPOSING THE
 STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE, OR
 BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD
 WIRING AND INTERCONNECTION WITHOUT THE REMOVAL OF
 INTERIOR FINISHES.
 2.REPAIRS TO THE EXTERIOR SURFACES OF DWELLINGS
 ARE EXEMPT FROM THE REQUIREMENTS OF THIS SECTION.
  
 22) IN ORDER TO AVOID CONFUSION PLEASE NUMBER THE LAST
 SHEET OF THE DRAWINGS. FBC 106.1.3* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By btrobaug Date 2008-06-16 Time 11:48 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 11:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By btrobaug Date 2008-03-26 Time 11:53 Rev Time 0.00
Received By btrobaug Date 2008-03-26 Time 09:54 Sent To Z
Notes
2008-03-26 10:56:03 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER1 AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE APPLICATION INDICATES "GARAGE CONVERSION INTO
 LIVING ROOM", SHEETS P1, P2, AND P3 INDICATE THREE
 ROOMS AS LIVING ROOMS, TWO OF THEM AS NEW, CORRELATE
 SAME.
  
 2} INDICATE IF THE ELECTRICAL SHOWN ON THE ABOVE NAMED
 SHEETS IS TO BE INSTALLED OR IF IT'S EXISTING, OR A
 COMBINATION OF BOTH. THE APPLICATION DOES NOT INDICATE
 IF ADDITIONAL ELECTRICAL WORK IS TO BE DONE OUTSIDE THE
 SCOPE OF THE NEW LIVING ROOM, AND NO ELECTRICAL PERMIT
 WAS APPLIED FOR.
  
 3} THE DESIGNER HAS DIFFERENT TITLE BLOCKS ON DIFFERENT
 SHEETS, CORRELATE SAME PER DBPR RECORDS.THE LAST SHEET
 , TITLED "DETAIL SHEET", IS NOT LISTED ON THE COVER
 SHEET AND IS NOT NUMBERED.
  
 MORE COMMENTS MAY BE FORTHCOMING AFTER THE SCOPE OF
 WORK IS DECLARED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 08:43 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 08:42 Sent To B
Notes
2009-02-18 08:42:58TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-28 Cont ID  
Sent By adarroug Date 2009-01-28 Time 10:02 Rev Time 0.00
Received By adarroug Date 2009-01-28 Time 10:02 Sent To B
Notes
2009-01-28 10:03:08TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 08:41 Sent To Z
Notes
2008-07-24 08:42:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-12 Cont ID  
Sent By adarroug Date 2008-06-12 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-06-12 Time 10:45 Sent To Z
Notes
2008-06-12 10:46:06TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-03-26 Time   Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 11:39 Sent To  
Notes
2008-03-24 11:39:46TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 12:15 Rev Time 0.25
Received By tgordon Date 2008-03-26 Time 12:15 Sent To Z
Notes
2008-03-26 12:16:26NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-04 Cont ID  
Sent By mcruz Date 2008-08-04 Time 10:13 Rev Time 0.00
Received By mcruz Date 2008-08-04 Time 10:13 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-13 Cont ID  
Sent By choops Date 2008-06-13 Time 13:51 Rev Time 0.00
Received By choops Date 2008-06-13 Time 13:51 Sent To E
Notes
2008-06-13 13:52:02***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE PROPOSED WORK WITH SETBACK
 DIMENSIONS TO ALL PROPERTY LINES.THE SURVEYS WERE
 SUBMITTED BUT THEY DO NOT SHOW SETBACK DIMENSIONS FROM
 THE ADDITION TO ALL ADJACENT PROPERTY LINES.
  
 4)ELEVATION SHEETS SHALL SHOW HEIGHT DIMENSION OF
 PROPOSED FROM GRADE TO THE MIDPOINT OF THE ROOF'S
 PITCH.IF IT IS A FLAT ROOF, THE DIMENSION SHALL BE
 SHOWN TO THE TOP OF THE ROOF.NOTE:SHALL NOT EXCEED
 30' IN HEIGHT.
  
  
 NEW COMMENTS:
  
 1)INDICATE THE HEIGHT DIMENSION FROM GRADE TO THE
 UPPERMOST POINT OF THE CHIMNEY.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 15:56 Rev Time 0.00
Received By choops Date 2008-03-26 Time 15:56 Sent To  
Notes
2008-03-26 16:00:08***FAILED***
  
  
 1)CLARIFY SCOPE OF WORK.APPLICATION INDICATES
 GARAGE CONVERSION INTO LIVING ROOM.ELEVATION PLANS
 SHOW A SECOND FLOOR ADDITION.PLEASE CLARIFY AND
 CLEARLY SHOW WHAT IS EXISTING AND WHAT IS PROPOSED.
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE PROPOSED WORK WITH SETBACK
 DIMENSIONS TO ALL PROPERTY LINES.
  
 3)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED OR
 RELOCATED A/C EQUIPMENT (IF ANY) TO ALL PROPERTY LINES.
 AS PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 4)ELEVATION SHEETS SHALL SHOW HEIGHT DIMENSION OF
 PROPOSED FROM GRADE TO THE MIDPOINT OF THE ROOF'S
 PITCH.NOTE:SHALL NOT EXCEED 30' IN HEIGHT.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720