Plan Review Details - Permit 08030519
Plan Review Stops For Permit 08030519
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By amorse Date 2008-06-25 Time 18:13 Rev Time 0.00
Received By amorse Date 2008-06-25 Time 18:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-14 Cont ID  
Sent By amorse Date 2008-06-14 Time 09:46 Rev Time 0.00
Received By amorse Date 2008-06-14 Time 09:46 Sent To PC
Notes
2008-06-14 09:47:38 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 FIRST REVIEW
  
 1)RESIDENTIAL GENERATORS REQUIRE THE FOLLOWING
 INFORMATION
 A) PROVIDE INFORMATION FOR ANCHORAGE OF UNIT, TO MEET
 THE REQUIREMENTS OF 1609.1.3 FBC FOR UPLIFT,
 OVERTURNING AND SLIDING
 B) PROVIDE INFORMATION ON SIZE OF SLAB, SHALL MEET THE
 MIN REQUIREMENTS FOR EQUIPMENT PAD PER 304.9 FBC MECH.
  
 2)THE CLAIMED VALUATION ON THE PERMITAPPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 *********INCLUDES COST OF EQUIPMENT, PAD, LABOR,
 PERMIT, ETC. **********GENERATOR ALONE RETAILS FOR
 APPROX $6,000.00
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-05 Cont ID  
Sent By amorse Date 2008-04-05 Time 14:26 Rev Time 0.00
Received By amorse Date 2008-04-05 Time 14:26 Sent To PC
Notes
2008-04-05 14:30:45 
  
 DENIED
  
 1)RESIDENTIAL GENERATORS REQUIRE THE FOLLOWING
 INFORMATION
 A) PROVIDE INFORMATION FOR ANCHORAGE OF UNIT, TO MEET
 THE REQUIREMENTS OF 1609.1.3 FBC FOR UPLIFT,
 OVERTURNING AND SLIDING
 B) PROVIDE INFORMATION ON SIZE OF SLAB, SHALL MEET THE
 MIN REQUIREMENTS FOR EQUIPMENT PAD PER 304.9 FBC MECH.
  
 2)THE CLAIMED VALUATION ON THE PERMITAPPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 *********INCLUDES COST OF EQUIPMENT, PAD, LABOR,
 PERMIT, ETC. **********
  
 3)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 13:15 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 12:39 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By btrobaug Date 2008-03-26 Time 15:59 Rev Time 0.00
Received By btrobaug Date 2008-03-26 Time 14:44 Sent To M
Notes
2008-03-26 15:31:47 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1) PROVIDE A RISER DIAGRAM SHOWING LOCATIONS OF ALL
 EQUIPMENT ELECTRICALLY. 215.5.
  
 2) PROVIDE A SITE PLAN INDICATING THE PHYSICAL LOCATION
 OF THE EQUIPMENT WITH REGARD TO THE SERVICE AND
 SEPARATE STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE
 SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER
 SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING
 MEANS. ALSO 110.9 FOR AIC RATING.
  
 3) IDENTIFY LOADS TO BE SERVED, PANEL SCHEDULE FOR
 GENERATOR PANEL. LOADS MUST NOT EXCEED GENERATOR
 OUTPUT.702.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By mperson Date 2008-06-25 Time 13:20 Rev Time 0.00
Received By mperson Date 2008-06-25 Time 13:20 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By mperson Date 2008-06-11 Time 16:37 Rev Time 0.00
Received By mperson Date 2008-06-11 Time 16:37 Sent To M
Notes
2008-06-11 16:59:04GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REQUIRED
 RESUBMITTED GAS ISOMETRIC AND MANUFACTURER SUBMITTAL
 SHEETS DUE TO HAVING APPLIED FOR A GAS PERMIT THAT IS
 ATTACHED TO THE GEN/RES PERMIT.
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 **THE RESUBMITTED GEN/RES PERMIT APPLICATION DID NOT
 HAVE THE REQUIRED GAS ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 **SEE COMMENT #1.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 **SEE COMMENT #1.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 **SEE COMMENT #1.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 **SEE COMMENT #1.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 **SEE COMMENT #1.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 **SEE COMMENT #1.
  
 8. "OK" COMMENT ADDRESSED.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 **SEE COMMENTS #1 AND #3.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 **SEE COMMENTS #1 AND #3.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-27 Cont ID  
Sent By mperson Date 2008-03-27 Time 16:29 Rev Time 0.00
Received By mperson Date 2008-03-27 Time 16:29 Sent To B
Notes
2008-03-27 16:43:19GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REQUIRED
 RESUBMITTED GAS ISOMETRIC AND MANUFACTURER SUBMITTAL
 SHEETS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *THE SUBMITTED MANUFACTURER'S SHEETS DO NOT INDICATE
 THE BTU LOAD OF THE PROPOSED GENERATOR.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-23 Cont ID  
Sent By adarroug Date 2008-06-23 Time 08:49 Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 08:49 Sent To G
Notes
2008-06-23 08:49:46TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 16:48 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 16:48 Sent To Z
Notes
2008-06-05 16:48:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-04-05 Time   Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 09:14 Sent To  
Notes
2008-03-24 09:14:27TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-12 Cont ID  
Sent By tgordon Date 2008-06-12 Time 08:44 Rev Time 0.20
Received By tgordon Date 2008-06-12 Time 08:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-27 Cont ID  
Sent By tgordon Date 2008-03-27 Time 08:03 Rev Time 0.25
Received By tgordon Date 2008-03-27 Time 08:03 Sent To G
Notes
2008-03-27 08:05:01*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-10 Cont ID  
Sent By choops Date 2008-06-10 Time 09:30 Rev Time 0.00
Received By choops Date 2008-06-10 Time 09:30 Sent To E
Notes
2008-06-10 09:32:23***APPROVED - RESUB #1 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 11:56 Rev Time 0.00
Received By choops Date 2008-03-26 Time 11:56 Sent To E
Notes
2008-03-26 11:56:50***APPROVED***
  
  
  
 SENT TO "E" - GEN. RES. BOX