| Plan Review Stops For Permit 08030519 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-06-25 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-06-25 |
Time |
18:13 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-06-14 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-06-14 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-06-14 |
Time |
09:46 |
Sent To |
PC |
|
| Notes |
| 2008-06-14 09:47:38 | | | | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE | | | FIRST REVIEW | | | | | | 1)RESIDENTIAL GENERATORS REQUIRE THE FOLLOWING | | | INFORMATION | | | A) PROVIDE INFORMATION FOR ANCHORAGE OF UNIT, TO MEET | | | THE REQUIREMENTS OF 1609.1.3 FBC FOR UPLIFT, | | | OVERTURNING AND SLIDING | | | B) PROVIDE INFORMATION ON SIZE OF SLAB, SHALL MEET THE | | | MIN REQUIREMENTS FOR EQUIPMENT PAD PER 304.9 FBC MECH. | | | | | | 2)THE CLAIMED VALUATION ON THE PERMITAPPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | *********INCLUDES COST OF EQUIPMENT, PAD, LABOR, | | | PERMIT, ETC. **********GENERATOR ALONE RETAILS FOR | | | APPROX $6,000.00 | | | | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-04-05 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-04-05 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-04-05 |
Time |
14:26 |
Sent To |
PC |
|
| Notes |
| 2008-04-05 14:30:45 | | | | | | | DENIED | | | | | | 1)RESIDENTIAL GENERATORS REQUIRE THE FOLLOWING | | | INFORMATION | | | A) PROVIDE INFORMATION FOR ANCHORAGE OF UNIT, TO MEET | | | THE REQUIREMENTS OF 1609.1.3 FBC FOR UPLIFT, | | | OVERTURNING AND SLIDING | | | B) PROVIDE INFORMATION ON SIZE OF SLAB, SHALL MEET THE | | | MIN REQUIREMENTS FOR EQUIPMENT PAD PER 304.9 FBC MECH. | | | | | | 2)THE CLAIMED VALUATION ON THE PERMITAPPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | *********INCLUDES COST OF EQUIPMENT, PAD, LABOR, | | | PERMIT, ETC. ********** | | | | | | 3)SUBMIT A COPY OF THE RECORDED NOTICE OF | | | COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-11 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-11 |
Time |
12:39 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-26 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-26 |
Time |
14:44 |
Sent To |
M |
|
| Notes |
| 2008-03-26 15:31:47 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | 1) PROVIDE A RISER DIAGRAM SHOWING LOCATIONS OF ALL | | | EQUIPMENT ELECTRICALLY. 215.5. | | | | | | 2) PROVIDE A SITE PLAN INDICATING THE PHYSICAL LOCATION | | | OF THE EQUIPMENT WITH REGARD TO THE SERVICE AND | | | SEPARATE STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE | | | SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER | | | SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING | | | MEANS. ALSO 110.9 FOR AIC RATING. | | | | | | 3) IDENTIFY LOADS TO BE SERVED, PANEL SCHEDULE FOR | | | GENERATOR PANEL. LOADS MUST NOT EXCEED GENERATOR | | | OUTPUT.702.5 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-25 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-25 |
Time |
13:20 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-11 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-11 |
Time |
16:37 |
Sent To |
M |
|
| Notes |
| 2008-06-11 16:59:04 | GAS PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REQUIRED | | | RESUBMITTED GAS ISOMETRIC AND MANUFACTURER SUBMITTAL | | | SHEETS DUE TO HAVING APPLIED FOR A GAS PERMIT THAT IS | | | ATTACHED TO THE GEN/RES PERMIT. | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | **THE RESUBMITTED GEN/RES PERMIT APPLICATION DID NOT | | | HAVE THE REQUIRED GAS ISOMETRIC. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | **SEE COMMENT #1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | **SEE COMMENT #1. | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | **SEE COMMENT #1. | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | **SEE COMMENT #1. | | | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | **SEE COMMENT #1. | | | | | | 7. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | **SEE COMMENT #1. | | | | | | 8. "OK" COMMENT ADDRESSED. | | | | | | 9. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | **SEE COMMENTS #1 AND #3. | | | | | | 10. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | **SEE COMMENTS #1 AND #3. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-27 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-27 |
Time |
16:29 |
Sent To |
B |
|
| Notes |
| 2008-03-27 16:43:19 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REQUIRED | | | RESUBMITTED GAS ISOMETRIC AND MANUFACTURER SUBMITTAL | | | SHEETS. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 7. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | *THE SUBMITTED MANUFACTURER'S SHEETS DO NOT INDICATE | | | THE BTU LOAD OF THE PROPOSED GENERATOR. | | | | | | 9. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 10. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-23 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-23 |
Time |
08:49 |
Sent To |
G |
|
| Notes |
| 2008-06-23 08:49:46 | TO "G" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-05 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-05 |
Time |
16:48 |
Sent To |
Z |
|
| Notes |
| 2008-06-05 16:48:31 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-04-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-24 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2008-03-24 09:14:27 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-06-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-12 |
Time |
08:44 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-06-12 |
Time |
08:44 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-27 |
Time |
08:03 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-03-27 |
Time |
08:03 |
Sent To |
G |
|
| Notes |
| 2008-03-27 08:05:01 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT | | | PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL | | | COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA | | | 37.NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES | | | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT | | | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES | | | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT | | | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-06-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-10 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-10 |
Time |
09:30 |
Sent To |
E |
|
| Notes |
| 2008-06-10 09:32:23 | ***APPROVED - RESUB #1 (RESTAMPED PLANS)*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-26 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-26 |
Time |
11:56 |
Sent To |
E |
|
| Notes |
| 2008-03-26 11:56:50 | ***APPROVED*** | | | | | | | | | | | | SENT TO "E" - GEN. RES. BOX |
|
|