| Plan Review Stops For Permit 08030509 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-06-16 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-06-16 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-05-28 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-05-28 |
Time |
10:51 |
Sent To |
P |
|
| Notes |
| 2008-05-28 14:08:16 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) THIS UNIT IS LOCATED IN A HIGH RISE BUILDING. THE | | | BUILDING IS REQUIRED TO BE TYPE 1A CONSTRUCTION. THE | | | FRAMING IN THE NON-BEARING PARTITION WALLS IS REQUIRED | | | TO BE FIRE-RETARDANT-TREATED WOOD OR NON-COMBUSTIBLE | | | MATERIAL. SEE FBC 603.1. | | | | | | 3) PROVIDE DETAILS OF THE RAISED PLATFORMS. SPECIFY | | | SIZE, HEIGHT AND MATERIALS THAT WILL BE USED TO | | | CONSTRUCT. FBC 106.1.2* CITY AMENDMENTS | | | | | | 4) SHOW COMPLIANCE WITH 410.4 PLATFORM CONSTRUCTION. | | | PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS | | | AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE | | | BUILDING IN WHICH THE PERMANENT PLATFORMS IS LOCATED. | | | PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF | | | FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV | | | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 | | | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN | | | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN | | | 3,000 SQUARE FEET (279 M 2 ) IN AREA. WHERE THE SPACE | | | BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR | | | ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR | | | PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN | | | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE | | | SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR | | | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE | | | PERMANENT PLATFORM NEED NOT BE PROTECTED. | | | | | | 5) PROVIDE FLOOR PLANS OF THE PROPOSED REMODEL WITH | | | DIMENSIONS, DOOR SIZES, ETC. SHOW LOCATIONS OF | | | PLATFORMS. SEE FBC 106.1.1* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-03-24 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-03-24 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2008-03-24 10:02:59 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) THE PLANS SHOW THE RELOCATION AND ADDITION OF | | | PLUMBING FIXTURES THAT WILL REQUIRE PENETRATIONS | | | THROUGH THE FIRE RATED FLOOR. THE PLANS ARE REQUIRED TO | | | BE SIGNED AND SEALED BY A FLORIDA LICENSED ARCHITECT OR | | | ENGINEER. FS 471 AND 481. | | | | | | 3) SHOW COMPLIANCE WITH 2004 FBC MECHANICAL SECTION | | | 402.3.1 FOR MECHANICAL VENTILATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-11 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-12-11 |
Time |
09:53 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-03 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-03 |
Time |
08:19 |
Sent To |
PC |
|
| Notes |
| 2008-07-03 08:19:36 | | | | | | | FOUND NEW SHEETS./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-06-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-24 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-24 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2008-06-24 13:46:42 | | | | | | | NO NEW SHEETS./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-11 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-11 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-05-20 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-05-20 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2008-05-20 08:36:04 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | | 210.52(A)(2). 2005 NEC. THERE ARE NO RECEPTACLES SHOWN | | | IN THE NEW PARTITIONS. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | | AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-24 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-24 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2008-03-24 11:43:15 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | 1} THE PLANS ARE EQUIRED TO BE SIGNED, DATED AND SEALED | | | BY AN ARCHITECT PER 481.229, OR AN ENGINEER PER 471, | | | FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-16 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-16 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2008-06-16 11:18:11 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS ID-1 & ID-2 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-05-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-23 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-23 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2008-05-23 14:52:11 | *****UNSAT***** | | | | | | *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PALN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO SHEET ID-1 | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.ADD NFPA 101 - 2003 EDITION TO SHEET ID-2 | | | | | | 4.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | | IN TERMS OF CLASS A, CLASS B, OR CLASS C.ADD YOUR | | | RESPONSE OF "NEW WALLS AND CEILING DRY WALL MATERIALS | | | CLASS A AND B" TO SHEET ID-2 | | | | | | *NEW COMMENT | | | | | | A.SMOKE ALARMS (SA) INSTEAD OF SMOKE DETECTORS (SD) | | | SHOULD BE LISTED ON SHEET ID-2.PLEASE BE ADVISED THAT | | | SMOKE DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM | | | SYSTEM WHEREAS SMOKE ALARMS ALERT THE OCCUPANT(S) | | | WITHIN THE INDIVIDUAL DWELLING UNIT ONLY. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-31 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2008-03-31 12:12:41 | *****UNSAT***** | | | | | | | | | 1. THE ADDRESS, INCLUDING SUITE NUMBER 2405, SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.NFPA 101, LIFE SAFETY CODE, SHALL BE REFERENCED. | | | | | | 4.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | | IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-11 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-11 |
Time |
08:22 |
Sent To |
E |
|
| Notes |
| 2008-12-11 08:22:59 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-23 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-23 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2008-06-23 14:19:13 | TO "BOB"#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-06 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-06 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2008-06-06 10:58:56 | TO "BOB"#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-12 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-05-12 16:41:57 | TO "BOB"#3 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
12:02 |
Rev Time |
|
| Received By |
mawillia |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2008-03-21 14:59:21 | TO "BOB"#3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-02 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-02 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2008-07-02 14:41:18 | ******PROVISO****** | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: REMOVAL | | | OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND AN | | | INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR TO | | | COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR | | | POURED CONCRETE SLABS. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-17 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-17 |
Time |
16:22 |
Sent To |
PC |
|
| Notes |
| 2008-06-17 16:37:50 | PLUMBING PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | NOTE: THERE WERE NO COMMENT RESPONSES FROM THE | | | DESIGNER. | | | | | | 1. PROVIDE SANITARY AND WATER ISOMETRIC RISER DIAGRAMS | | | OF THE PROPOSED NEW MASTER BATHROOM PLUMBING LAYOUT AND | | | NEW BAR SINK. PER (W.P.B. AS AMENDED) SECTION | | | 106.3.5.1.3 PLUMBING (3)(4)(10)(13). | | | | | | **NO COMMENT RESPONSE AND COMMENT WAS NOT ADDRESSED. | | | AN ISOMETRIC SANITARY AND WATER RISER DIAGRAMS ARE | | | STILL REQUIRED FOR THE PROPOSED NEW MASTER BATHROOM | | | PLUMBING LAYOUT. THE RESUBMITTED PLANS DO NOT INDICATE | | | A SINK IN THE NEW BAR AS IT WAS SHOWN IN THE LAST SET | | | OF PLANS. PLEASE CLARIFY IF THE BAR SINK IS BEING | | | DELETED. IF IT IS NOT BEING DELETED IT ALSO NEEDS TO BE | | | ON THE REQUIRED SANITARY AND WATER RISER DIAGRAMS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-05-28 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-05-28 |
Time |
16:15 |
Sent To |
PC |
|
| Notes |
| 2008-05-28 16:23:17 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. PROVIDE SANITARY AND WATER ISOMETRIC RISER DIAGRAMS | | | OF THE PROPOSED NEW MASTER BATHROOM PLUMBING LAYOUT AND | | | NEW BAR SINK. PER (W.P.B. AS AMENDED) SECTION | | | 106.3.5.1.3 PLUMBING (3)(4)(10)(13). | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-26 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-26 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2008-03-26 09:14:31 | *ZONING REVIEW NOT REQUIRED ? INTERIOR WORK ONLY, AND | | | THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|