Plan Review Details - Permit 08030509
Plan Review Stops For Permit 08030509
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By rmcdouga Date 2008-06-16 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2008-06-16 Time 14:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-28 Cont ID  
Sent By rmcdouga Date 2008-05-28 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2008-05-28 Time 10:51 Sent To P
Notes
2008-05-28 14:08:162004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THIS UNIT IS LOCATED IN A HIGH RISE BUILDING. THE
 BUILDING IS REQUIRED TO BE TYPE 1A CONSTRUCTION. THE
 FRAMING IN THE NON-BEARING PARTITION WALLS IS REQUIRED
 TO BE FIRE-RETARDANT-TREATED WOOD OR NON-COMBUSTIBLE
 MATERIAL. SEE FBC 603.1.
  
 3) PROVIDE DETAILS OF THE RAISED PLATFORMS. SPECIFY
 SIZE, HEIGHT AND MATERIALS THAT WILL BE USED TO
 CONSTRUCT. FBC 106.1.2* CITY AMENDMENTS
  
 4) SHOW COMPLIANCE WITH 410.4 PLATFORM CONSTRUCTION.
 PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS
 AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORMS IS LOCATED.
 PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M 2 ) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR
 PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE
 SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 5) PROVIDE FLOOR PLANS OF THE PROPOSED REMODEL WITH
 DIMENSIONS, DOOR SIZES, ETC. SHOW LOCATIONS OF
 PLATFORMS. SEE FBC 106.1.1* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By rmcdouga Date 2008-03-24 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2008-03-24 Time 09:15 Sent To  
Notes
2008-03-24 10:02:592004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE PLANS SHOW THE RELOCATION AND ADDITION OF
 PLUMBING FIXTURES THAT WILL REQUIRE PENETRATIONS
 THROUGH THE FIRE RATED FLOOR. THE PLANS ARE REQUIRED TO
 BE SIGNED AND SEALED BY A FLORIDA LICENSED ARCHITECT OR
 ENGINEER. FS 471 AND 481.
  
 3) SHOW COMPLIANCE WITH 2004 FBC MECHANICAL SECTION
 402.3.1 FOR MECHANICAL VENTILATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-12-11 Cont ID  
Sent By btrobaug Date 2008-12-11 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2008-12-11 Time 09:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-03 Cont ID  
Sent By btrobaug Date 2008-07-03 Time 08:34 Rev Time 0.00
Received By btrobaug Date 2008-07-03 Time 08:19 Sent To PC
Notes
2008-07-03 08:19:36 
  
 FOUND NEW SHEETS./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-24 Cont ID  
Sent By btrobaug Date 2008-06-24 Time 13:46 Rev Time 0.00
Received By btrobaug Date 2008-06-24 Time 13:24 Sent To  
Notes
2008-06-24 13:46:42 
  
 NO NEW SHEETS./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By btrobaug Date 2008-05-20 Time 08:38 Rev Time 0.00
Received By btrobaug Date 2008-05-20 Time 08:10 Sent To  
Notes
2008-05-20 08:36:04 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. THERE ARE NO RECEPTACLES SHOWN
 IN THE NEW PARTITIONS.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By btrobaug Date 2008-03-24 Time 11:43 Rev Time 0.00
Received By btrobaug Date 2008-03-24 Time 11:05 Sent To  
Notes
2008-03-24 11:43:15 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PLANS ARE EQUIRED TO BE SIGNED, DATED AND SEALED
 BY AN ARCHITECT PER 481.229, OR AN ENGINEER PER 471,
 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By mawillia Date 2008-06-16 Time 11:18 Rev Time 0.00
Received By mawillia Date 2008-06-16 Time 11:06 Sent To  
Notes
2008-06-16 11:18:11*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS ID-1 & ID-2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-23 Cont ID  
Sent By mawillia Date 2008-05-23 Time 14:52 Rev Time 0.00
Received By mawillia Date 2008-05-23 Time 14:34 Sent To  
Notes
2008-05-23 14:52:11*****UNSAT*****
  
 *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PALN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO SHEET ID-1
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.ADD NFPA 101 - 2003 EDITION TO SHEET ID-2
  
 4.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.ADD YOUR
 RESPONSE OF "NEW WALLS AND CEILING DRY WALL MATERIALS
 CLASS A AND B" TO SHEET ID-2
  
 *NEW COMMENT
  
 A.SMOKE ALARMS (SA) INSTEAD OF SMOKE DETECTORS (SD)
 SHOULD BE LISTED ON SHEET ID-2.PLEASE BE ADVISED THAT
 SMOKE DETECTORS ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM WHEREAS SMOKE ALARMS ALERT THE OCCUPANT(S)
 WITHIN THE INDIVIDUAL DWELLING UNIT ONLY.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 12:26 Rev Time 0.00
Received By mawillia Date 2008-03-31 Time 11:59 Sent To  
Notes
2008-03-31 12:12:41*****UNSAT*****
  
  
 1. THE ADDRESS, INCLUDING SUITE NUMBER 2405, SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.NFPA 101, LIFE SAFETY CODE, SHALL BE REFERENCED.
  
 4.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 08:22 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 08:22 Sent To E
Notes
2008-12-11 08:22:59TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-23 Cont ID  
Sent By adarroug Date 2008-06-23 Time 14:16 Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 14:16 Sent To  
Notes
2008-06-23 14:19:13TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 10:53 Sent To  
Notes
2008-06-06 10:58:56TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 16:34 Sent To  
Notes
2008-05-12 16:41:57TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 12:02 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
2008-03-21 14:59:21TO "BOB"#3

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-02 Cont ID  
Sent By mperson Date 2008-07-02 Time 14:39 Rev Time 0.00
Received By mperson Date 2008-07-02 Time 14:39 Sent To  
Notes
2008-07-02 14:41:18******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND AN
 INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR TO
 COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-17 Cont ID  
Sent By mperson Date 2008-06-17 Time 16:22 Rev Time 0.00
Received By mperson Date 2008-06-17 Time 16:22 Sent To PC
Notes
2008-06-17 16:37:50PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NOTE: THERE WERE NO COMMENT RESPONSES FROM THE
 DESIGNER.
  
 1. PROVIDE SANITARY AND WATER ISOMETRIC RISER DIAGRAMS
 OF THE PROPOSED NEW MASTER BATHROOM PLUMBING LAYOUT AND
 NEW BAR SINK. PER (W.P.B. AS AMENDED) SECTION
 106.3.5.1.3 PLUMBING (3)(4)(10)(13).
  
 **NO COMMENT RESPONSE AND COMMENT WAS NOT ADDRESSED.
 AN ISOMETRIC SANITARY AND WATER RISER DIAGRAMS ARE
 STILL REQUIRED FOR THE PROPOSED NEW MASTER BATHROOM
 PLUMBING LAYOUT. THE RESUBMITTED PLANS DO NOT INDICATE
 A SINK IN THE NEW BAR AS IT WAS SHOWN IN THE LAST SET
 OF PLANS. PLEASE CLARIFY IF THE BAR SINK IS BEING
 DELETED. IF IT IS NOT BEING DELETED IT ALSO NEEDS TO BE
 ON THE REQUIRED SANITARY AND WATER RISER DIAGRAMS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-28 Cont ID  
Sent By mperson Date 2008-05-28 Time 16:15 Rev Time 0.00
Received By mperson Date 2008-05-28 Time 16:15 Sent To PC
Notes
2008-05-28 16:23:17PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE SANITARY AND WATER ISOMETRIC RISER DIAGRAMS
 OF THE PROPOSED NEW MASTER BATHROOM PLUMBING LAYOUT AND
 NEW BAR SINK. PER (W.P.B. AS AMENDED) SECTION
 106.3.5.1.3 PLUMBING (3)(4)(10)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 09:14 Rev Time 0.00
Received By choops Date 2008-03-26 Time 09:14 Sent To  
Notes
2008-03-26 09:14:31*ZONING REVIEW NOT REQUIRED ? INTERIOR WORK ONLY, AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.