2008-07-03 12:04:08BUILDING PLAN REVIEW
 PERMIT: 08030500
 ADD: 915 N DIXIE HW
 CONT: GLACE & CO
 TEL: (561)585-5564
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A-1C) COMPLIED.
  
 1D ) FILED NOTICE OF COMMENCEMENT DATE 11-20-07 IS OUT
 OF DATE AND WILL NEED TO BE REFILLED.FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OF COMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 1E) COMPLIED.
  
 2-5)COMPLIED.
  
 6) BUILDING PROVISO; ELEVATORS AND CONVEYANCE SYSTEMS
 ARE BY DEFINITION 3001.6 AN ELEVATOR, DUMBWAAITER,
 ESCALATOR, MOVING SIDEWALK, PLATFORM LIFTS AND STAIRWAY
 LIFTS THAT ALL WILL NEED TO COMPLY WITH THE REFRENCED
 STANDARDS. PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS
 MEETING THE REFERENCED STANDARDS IN3001.2.THE
 DOCUMENTS SUBMITTED DO NOT INDICATE ANY OF THE
 REFERENCED STANDARDS LISTED UNDER THIS CODE SECTION.
  
 7) 2ND REQUEST, THE ORIGINAL SHEET A2.1 INDICATED USE
 OF A ENCLOSED PARKING GARAGE. THE RESUBMITTED PLANS
 INDICATE THIS SPACE TO BE FUTURE OFFICE. INDISCUSSING
 THIS ISSUE WITH ROBERT BROWN ASST BUILDING OFF. IF THE
 PLANS ARE GOING TO STATE FUTURE OFFICE THEN THE GARAGE
 ENTRY DOORS WOULD NEED TO BE REMOVED AND EITHER BLOCKED
 UP OR STOREFRONT INSTALLED TO SHOW INTENT OF A FUTURE
 OFFICE. THE OTHER ISSUE IS THAT YOUR PLANS WOULD NEED
 TO BE REVIEWED BY PALM BEACH COUNTY IMPACT FEE OFFICE
 FOR ADDITIONAL IMPACT FEE ASSESSMENT. SHEET A2.1
 INDICATES A WALL TYPE 11 THAT SEPERATES THE OFFICE AREA
 FROM AN ENCLOSED PARKING GARAGE. THIS WILL REQUIRE A
 2HR SEPERATION AS PER TABLE 302.3.2. WHERE AS THE WALL
 TYPE 11 IS INDICATED AS A INTERIOR NONRATED WALL.
 PLEASE INDICATE WHERE THE 2 HR FIRE RATED WALL WILL BE.
 ALSO OPENING PROTECTION TABLE 715.3.
  
 8) BUILDING PROVISO:NOTE CHAPTER 11 IS NOT ABOUT
 EGRESS REQUIREMENTS BUT ACCESSIBILITY. IF ENTRYS ARE
 NOT ACCESSIBLE THEN SIGNAGE IS REQUIRED INDICATING
 WHERE THE ACCESSIBLE ENTRY WOULD BE AND SIGNAGE
 INDICATING THAT THIS IS NOT AN ACCESSIBLE DOORWAY. REAR
 OF BUILDING, DOOR 111D & 111E, THE DOOR SCHEDULE
 INDICATES EACH OF THESE DOORS AS A PAIR OF BI-PASS DOOR
 WITH A CLEAR OPENING OF 2'-6", 11-4.13.5 DOORWAY MIN
 CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM CLEAR WIDTH
 OF 32" WITH THE DOOR OPEN 90-DEGREES, MEASURED BETWEEN
 THE FACE OF THE DOOR AND OPPOSITE STOP.
  
 9) COMPLIED.
  
 10) CHANGE IN OCCUPANCY THE GARAGE TO OFFICE PORTION OF
 THE PLANS WILL REQUIRE REVIEW FROM PALM BEACH COUNTY
 IMPACT FEE OFFICE.
  
 11) NEW COMMENT IN THE RESTROOM 127 THE HANDICAPPED
 SHOWER NEEDS TO CONFORM WITH FIGURE 35A, THE 48 INCH
 CLEAR FLOOR SPACE REQUIRES 1'-0" PAST THE OPPOSITE WALL
 OF THE SEAT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 7-08-08
 COMMENT NUMBER 6 & 8 CAN AND WILL BOTH BE BUILDING
 PROVISOS:

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By jwitmer Date 2008-04-14 Time 07:12 Rev Time 2.22
Received By jwitmer Date 2008-04-14 Time 07:11 Sent To  
Notes
2008-07-03 12:01:45 
2008-04-14 07:19:47BUILDING PLAN REVIEW
 PERMIT: 08030500
 ADD: 915 N DIXIE HW
 CONT: GLACE & CO
 TEL: (561)585-5564
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PLEASE SEE AERIAL VIEW,SEE ATTACHMENT. IT APPEARS
 THAT THE WORK IS TRANGRESSING THE PROPERTY LINE AND THE
 WRONG PROPERTY CONTROL NUMBER LISTED ON THE PERMIT
 APPLICATION.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3) PLEASE PROVIDE A SITE PLAN OF THE WHOLE BUIULDING
 SITE WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 THE LEVEL OF ALTERATION UNDER THE 2004 EXISTING
 BUILDING CODE.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) NUMBER OF FLOORS
 I ) SQ. FT. FOOTPRINT, FOOTPRINT
  
 4) PLANS INDICATE A MEZZANINE, PLEASE PROVIDE AREA
 CALCULATIONS AS PER THE DEFINITION OF A MEZZANINE.
 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED
 ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH
 THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING
 THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. PLEASE
 INDICATE WHAT AREAS OFT THE MEZZANINE ARE COMMUNICATING
 WITH OTHER ROOMS.
  
 5) ADDITIONAL INFORMATION REQUIRED, THE ELECTRICAL
 REVIEWERS COMMENET# 7IS NOT LIMITED TO BUT WILL
 INCLUDE THE IT ROOM FOUND ON SHEET A2.2. THIS ROOM IS
 NOT LISTED AS A IT ROOM ON E2.2.
 IF THIS IS A TRUE USE IT ROOM THIS COMMENT WILL APPEAR
 UNDER THE ELECTRICAL REVIEWERS COMMENTS NEXT REVIEW. IT
 ROOMS ARE REQUIRED BY NFPA 645.1-4 TO HAVE CERTAIN
 RATINGS. ONE THAT WILL PERTAIN TO BUILDING IS RATED
 WALLS, OPENING PROTECTION AND THROUGH WALL PENETRATIONS
 AND HORIZONTAL PENETRATIONS, TABLE 715.3, 712.3.1 &
 712.4.1.PLEASE PROVIDE ADDITIONAL INFORMATION
 ACCORDINGLY.
 THANK YOU.
  
 6) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 ELEVATOR, MINIMUM CAR PLAN DIMENSIONS,
 11-4.1.6(2)(3)(C) ELEVATORS (I)-(III).
  
 7)SHEET A2.1 INDICATES A WALL TYPE 11 THAT SEPERATES
 THE OFFICE AREA FROM AN ENCLOSED PARKING GARAGE. THIS
 WILL REQUIRE A 2HR SEPERATION AS PER TABLE 302.3.2.
 WHERE AS THE WALL TYPE 11 IS INDICATED AS A INTERIOR
 NONRATED WALL. PLEASE INDICATE WHERE THE 2 HR FIRE
 RATED WALL WILL BE. ALSO OPENING PROTECTION TABLE
 715.3.
  
 8) REAR OF BUILDING, DOOR 111D & 111E, THE DOOR
 SCHEDULE INDICATES EACH OF THESE DOORS AS A PAIR OF
 BI-PASS DOOR WITH A CLEAR OPENING OF 2'-6", 11-4.13.5
 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM
 CLEAR WIDTH OF 32" WITH THE DOOR OPEN 90-DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND OPPOSITE
 STOP.
  
 9) PLEASE PROVIDE INFORMATION WHY RESTROOMS 109 AND 110
 ARE NOT ACCESSIBLE? IF EXISTING PLEASE PROVIDE
 CALCULATIONS FOR DISPROPORTIONATE COST11-4.1.6(2)(A).
  
 10)IS THIS A CHANGE IN OCCUPANCY ENACTING IMPACT
 FEES?BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-10-02 Cont ID  
Sent By dpalmer Date 2008-10-02 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2008-10-02 Time 15:18 Sent To  
Notes
2008-10-02 15:18:58ADJUSTED NOTES ON ELECTRICAL SHEETS ALONG WITH REVISED
 FIXTURE LEGEND.
 ENERGY CALCS HAVE NO GROSS ERRORS AS NOTED IN FBC.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-01 Cont ID  
Sent By dpalmer Date 2008-10-01 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2008-10-01 Time 10:31 Sent To  
Notes
2008-10-01 10:32:00** DENIED REVIEW **
  
 ** CONTACT TO THE ARCHITECT WAS ATTEMPTED BY THIS
 OFFICE TO THE NUMBER LISTED ON TITLE BLOCKS HOWEVER THE
 PHONE NUMBER WAS * NO LONGER IN SERVICE*.
  
 1) NOTE: PLEASE SEE TIMER TYPE DEVICES MAY NOT BE USED
 PER FBC 11-4.27.4 FOR ANY AREAS WHICH ARE ADA
 ACCESSIBLE.
  
 2) NOTE: PLEASE SEE THE NEW CONTROLS SHOWN FOR EGRESS
 STAIRS NEED TO MEET FB C1006.1.2, NFPA-101 7.8.1.2.2.
 ALL OCCUPANCY DEVICES BEING USED FOR EGRESS SHALL BE
 *FAIL SAFE ON* AND SHALL BE ON FOR A MINIMUM OF 15MINS.
 PLEASE ADJUST PLANS.
  
 3) NOTE: PLEASE SEE THE FIXTURE LEGEND ON PLANS. AS THE
 FIXTURE LEGEND IS NOT COMPLETE WITH ALL WATTAGES MANY
 OF THESE CAN NOT BE CONFIRMED WITH THE SUBMITTED
 REVISED ENERGY CALCULATIONS.
 SOME EXAMPLES OF THIS WOULD BE C, D, DE, F, I ETC.
 THERE ARE OTHERS WHICH DO NOT INDICATE WATTAGES.
 13-415.2,13-415.2.ABC.1.1, .1.2, .1.3.
  
 4) NOTE: FOR INFORMATIONAL PURPOSE, THE RECORD NOTICE
 OF COMMENCEMENT IN THE PACKAGE IS EXPIRED PER FS
 713.13(2). THE RECORDING DATE WAS NOV OF 2007. WHEN
 WORK DOES NOT COMMENCE WITHIN 90DAYS OF RECORDING IT
 BECOMES VOID. THIS WILL ONLY NEED TO BE RE-RECORDED.
 THIS IS NOT AN ELECTRICAL PLAN REVIEW COMMENT AND ONLY
 MADE TO BENEFIT THE CONTRACTOR/OWNER.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-07 Cont ID  
Sent By dpalmer Date 2008-07-07 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2008-07-07 Time 17:02 Sent To  
Notes
2008-07-07 17:03:01** DENIED2ND REVIEW **
  
 ** PLEASE KNOW THERE ARE SEVERAL ITEMS STILL FROM
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 MANY OF THESE ARE THE EXACT SAME COMMENTS.
  
 ** IT IS IMPORTANT TO SEE NOTES FROM PREVIOUS REVIEW.
  
 ** AS STATED ON PREVIOUS REVIEW DUE TO THE FACT SOME
 INFORMATION IS STILL NOT YET SUBMITTED THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
 ** THERE ARE ALSO SOME NEW COMMENTS BASED ON DOCUMENTS
 AND INFORMATION NOW BEING SUBMITTED OR SHOWN WHICH WAS
 NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND
 SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 ** THIS IS THE SAME COMMENT AS ON PREVIOUS REVIEW.
 RESPONSE MENTIONS TO SEE LS PLANS YET THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN RELEVANT CODE
 REFERENCES.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS.
 THERE ARE MANY NEW DEVICES SHOWN ON PLANS YET MINIMUM
 REQUIRED FOR LIGHTING CONTROLS HAS NOT BEEN MET.
 THERE ARE NOW NEW TS (TIMED SWITCH) DEVICES IN MANY
 LOCATIONS HOWEVER AS THE DEVICE IS NOT SPECIFIC
 DETERMINATION FOR COMPLIANCE CAN NOT BE MADE.
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL SEVERAL STANDARD SINGLE POLE
 SWITCHES STILL BEING SHOWN FOR ACCENT LIGHTING.
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN FOR
 OTHER AREAS FOR GENERAL LIGHTING. (HALL OUTSIDE TOILET
 110)
  
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH THE
 LIGHTING CONTROLS ARE NOT LOCATED IN THE SEPARATE SPACE
 AS REQUIRED. THIS CAN BE CLEARLY SEEN ON THE UPPER
 LEVEL WHERE THE CONTROLS ARE LOCATED IN THE HALLWAY FOR
 CONTROLLING LIGHTING WHICH IS ACTUALLY LOCATED IN
 OFFICES/OR ROOMS.
  
 ** FOR EXAMPLE:
 CONTROL FOR OUTSIDE LIGHTING DOES NOT MEET
 13-415.1.ABC.1.4.
  
 ** FOR EXAMPLE:
 PLEASE CLARIFY THE LIGHTING CONTROLS NOTES WHICH
 MENTION *STORE*. THIS IS SUBMITTED AS A BUSINESS
 OCCUPANCY AND NOT A RETAIL STORE.
  
 ** THESE ARE ONLY A FEW EXAMPLES AND ARE NOT AN
 EXHAUSTED LIST OF MANY ITEMS WHICH NEED TO BE
 ADDRESSED.
 PLEASE LOOK AT OTHER COMMENTS BELOW AS THESE WILL
 AFFECT LIGHTING CONTROLS.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS MEETING THE MINIMUM REQUIRED BY THE LIFE
 SAFETY CODE.THIS WAS REQUESTED ON PREVIOUS REVIEW AND
 THERE ARE SOME SEPARATE SHEETS SHOWING SOME LEVELS
 HOWEVER THE LEVELS SHOWN DO NOT MEET THE MINIMUM
 REQUIRED.
 PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ARE
 REQUIRED TO BE 10FT CANDLES UNDER NORMAL. THE SEPARATE
 SHEETS SHOW 7.
 PLEASE SEE THE EMERGENCY LEVELS ARE PERMITTED TO GO
 DOWN TO 1FT CANDLE.
 7.9.2.1, 7.9.2.2
 THE LEVELS SHALL BE SHOWN AND PART OF THE RECORD SETS
 OF PLANS.
  
 4) NOTE: PLEASE SEE NFPA-101 2003 AND FBC 1006.1.2 FOR
 CONTROLS IN EGRESS AREAS. PLANS SHOW A STANDARD SINGLE
 POLE SWITCH AT THE BOTTOM OF STAIRS AND NO CONTROLS ON
 STAIRS OR AT THE TOP OF THE STAIRS.
 PLEASE SEE COMMENT #2 ABOVE WITH RESPECT TO LIGHTING IN
 BUILDINGS REQUIRED TO BE TURNED OFF.
 PLEASE ADDRESS.
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT
 SUBMITTING LIGHTING PERFORMANCE CALCULATIONS AND MAKING
 SURE ALL LIGHTING ON PLANS COORDINATES WITH THE INPUT
 DATA REPORT WHICH IS PART OF THE ENERGY CALCULATIONS.
 PLEASE SEE NOW A METHOD *A* IS BEING SUBMITTED WHICH
 CAN NOT BE USED AT THIS TIME. METHOD *A* IS FOR A WHOLE
 BUILDING WITH ALL KNOWN COMPONENTS. AS THIS BUILDING
 CONTAINS AREAS WHICH ARE SHOWN FOR *FUTURE BUILD OUT*
 THE *A* MAY NOT BE USED. PLEASE SEE 13-400.3.B,
 13-400.3.C, 13-101.1.6.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 ** THE SUBMITTED CALCULATIONS DO NOT COORDINATE WITH
 PLANS.
 SOME EXAMPLES OF THIS WILL BE NOTED BELOW HOWEVER THESE
 ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR.
  
 ** FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO EXTERIOR LIGHTING.
 HOW IS THIS POSSIBLE WHEN THE PLANS MOST CERTAINLY
 CONTAIN SEVERAL EXTERIOR LIGHTING FIXTURES?
  
 ** FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS ONE DOORS. HOW IS THIS
 POSSIBLE WHEN THE PLANS CERTAINLY CONTAIN DOORS FROM
 CONDITIONED SPACE TO UNCONDITIONED SPACE WHICH AS SHOWN
 EXCEED ONE?
  
 ** FOR EXAMPLE:
 PLEASE KNOW IF A METHOD *A* COULD BE USED ALL LIGHTING
 INCLUDING GARAGE AREA WOULD BE REQUIRED TO BE SHOWN IN
 THE IDR>
  
 ** FOR EXAMPLE:
 PLEASE VERIFY SOME LIGHTING CONTROLS NOTED * WITH
 DAYLIGHT ON/OFF*. WHERE ARE THESE ON PLANS?
  
 ** FOR EXAMPLE:
 NOT ALL FIXTURES ON PLANS ARE COMPLETED, SOME SHOWN AS
 *J* BOX ONLY.
  
 ** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT AND
 ARE NOT ALL ITEMS.
  
 6) NOTE: PLANS INDICATE SOME SORT OF TIMER SWITCH
 DEVICES YET AS THIS DEVICE IS NOT SPECIFIC AS NOTED
 ABOVE PLEASE SEE FBC 11-4.27 AND MORE SPECIFICALLY
 11-4.27.4 FOR TIME TYPE DEVICES.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE PROPOSED
 SERVICE. 110.26, 240.4, 230.70, 230.71, 230.72 ETC
 FBC106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY.
  
 8) NOTE: PLEASE SEE 645.10. THERE IS A SHUNT TRIP
 PUSHBUTTON ON POWER PLANS NOTED OUTSIDE *IT* ROOM YET
 THIS DOES NOT PROVIDE THE DISCONNECTING MEANS AS
 REQUIRED IN SECTION ABOVE. AS THERE ARE CIRCUITS FROM
 TWO SEPARATE SOURCES INCLUDING PANELS *A* AND *B* BOTH
 WOULD REQUIRE BREAKERS IN EACH CIRCUIT OR PANEL. AS THE
 PANELS DO NOT INDICATE ANY DEVICES FOR REQUIRED
 DISCONNECT THE SCENARIO AS SHOWN DOES NOT MEET THE
 CODE.
 WHERE IS THE REQUIRED DISCONNECT FOR A/C EQUIPMENT?
 PLEASE BE SURE TO LOOK AT THE SECTION OF THE CODE NOTED
 AND PROVIDE A DIAGRAM OR COMPLETE PLANS SHOWING
 COMPLIANCE.
  
 9) NOTE: PLEASE COORDINATE ELECTRICAL PLANS WITH
 MECHANICAL PLANS FOR CONTROLS OF BATHROOM EXHAUST
 FANS.
 MECHANICAL CODE REQUIRES CONTROLS OTHER THAN THE SINGLE
 POLE SWITCH AS SHOWN ON ELECTRICAL PLANS. THIS IS A
 MECHANICAL CODE REQUIREMENT.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION AND CLARITY REQUIRES PLANS TO MATCH.
 FBC/MECHANICAL CODE 402.3.1
  
 10) NOTE:PLEASE VERIFY NEW OR EXISTING ROOF-TOP GFI
 FOR NEW IT ROOM UNIT .210.63, 210.8B
  
 11) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE ACCESS
 CONTROL SYSTEM OR WILL THIS BE UNDER SEPARATE PLANS AND
 PERMIT.
 PLEASE SEE NFPA-101 7.2.1.5, 7.2.1.6.2
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW SOME ELECTRICAL PLANS AS WELL AS
 CALCULATIONS WERE RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-31 Cont ID  
Sent By dpalmer Date 2008-03-31 Time 16:14 Rev Time 0.00
Received By dpalmer Date 2008-03-27 Time 18:33 Sent To  
Notes
2008-03-31 16:14:22** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND
 SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE VERIFY IF THIS BUILDING CONTAINS AN
 EXISTING FIRE ALARM SYSTEM. IF SO, PLEASE SEE FBC
 11-4.28.1,.2 AND .3(4) WITH RESPECT TO MINIMUM DEVICE
 LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE. NEED TO
 SHOW ON THIS PLAN AT THIS TIME.
  
 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS. SOME DEVICES ARE
 SHOWN AND NOTED HOWEVER NO INFORMATION OR DETAIL WAS
 SUBMITTED ON THE NOTED LIGHTING CONTROL SYSTEM. THE
 PLANS MAKE NOTE OF OVER RIDES HOWEVER NO INFORMATION ON
 SYSTEM WAS SUBMITTED.
 PLEASE ALSO SEE THERE ARE NUMEROUS SWITCHES WHICH ARE
 SHOWN AS STANDARD SWITCHES IN WHICH SOME SORT OF
 AUTOMATED CONTROLS ARE REQUIRED.
 PLEASE SEE REDLINED PLANS AS MANY OF THESE ARE NOTED.
 ** AS THERE IS MUCH INFORMATION NOT SUBMITTED NOT ALL
 POSSIBLE COMMENTS CAN BE MADE AT THIS TIME.
  
 5) NOTE: PLEASE SEE 13-415.2., 13-415.2.ABC.1.1, .1.2
 AND .1.3. PLEASE SHOW MORE ON HOW LIGHTING PERFORMANCE
 LEVELS WERE DERIVED.
 TABLE STATES 100 FIXTURES, HOWEVER BASED ON PLANS
 SUBMITTED AND MINIMUMS REQUIRED PER CODE SECTIONS GIVEN
 ABOVE THE LIGHTING ON PLANS IS NOT CODE COMPLIANT.
 BASED ON THE STATEMENT OF 100 FIXTURES ALONE,
 COMPLIANCE IS NOT MET. THERE MORE THAN 100 FIXTURES ON
 PLANS.
 PLEASE BE SURE TO GO OVER LIGHTING LEVELS AND SHOW
 COMPLIANCE WITH EITHER TABLE B OR C.
 PLEASE COORDINATE ALL LIGHTING WHICH WAS SUBMITTED ON
 THE ENERGY CALCULATIONS.
 FOR EXAMPLE: PLEASE SEE THE INPUT DATA REPORT WHICH
 DOES NOT SHOW ANY FIXTURES. HOW IS THIS POSSIBLE WHEN
 THE PLANS CONTAIN FIXTURES?
 THIS IS NOTED AS ONE EXAMPLE ONLY.
  
 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR
 LIGHTING. PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2. THE
 LIGHTING LEVELS UNDER NORMAL CONDITIONS ARE REQUIRED TO
 BE AT 10FT CANDLE MINIMUM AT ALL STAIRS LEVELS/WALKING
 SURFACES.
 PLEASE SEE LIGHTING IN STAIRS IS SHOWN BEING CONTROLLED
 BY A WALL MOUNTED OCCUPANCY SENSOR, HOWEVER THE
 COVERAGE FOR THIS DEVICE DOES NOT SEEM TO BE MET FOR
 LIFE SAFETY OR FOR COVERAGE REQUIRED FOR LIGHTING
 CONTROLS.
 PLEASE ALSO SEE FBC 1016 AND LS 101 7.8.1.2.2 WHICH
 REQUIRES ANY OCCUPANCY DEVICE FOR EGRESS TO BE A
 MINIMUM OF 15MINS AND ALSO FAIL-SAFE *ON*.
 PLEASE ADJUST PLANS, DEVICES, SUPPLY PHOTO-METRICS
 ETC.
 FAC 61G15-33.004
  
 7) NOTE: PLEASE COMPLETE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. PLEASE ALSO COMPLETE PANEL WITH CIRCUITING
 WHICH IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE WATER HEATER IS MISSING THE
 REQUIRED DISCONNECT PER 422.31
  
 9) NOTE: PLANS INDICATE A NEW SERVICE BEING INSTALLED
 ONLY FOR THIS TENANT.
 PLEASE SEE 230.2 AS A NEW SERVICE IS NOT GRANTED AT
 THIS TIME. PLEASE PROVIDE MORE INFORMATION ON VOLTAGE,
 SIZES OF EXISTING, NEW, LOCATIONS ETC.
 230.2, 230.70, 230.72, 110.9 ETC..
  
 ** AS NOTED ABOVE IN SOME OF THE COMMENTS, NOT ALL
 POSSIBLE REVIEW NOTES CAN BE MADE AT THIS TIME AS THERE
 IS SOME INFORMATION NOT YET SUBMITTED FOR REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-27 18:33:232008-03-27 18:33:23
  
 PLANS IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-29 Cont ID  
Sent By mawillia Date 2008-09-29 Time 13:03 Rev Time 0.00
Received By mawillia Date 2008-09-29 Time 12:28 Sent To  
Notes
2008-09-29 12:50:46*****APPROVED W/REMINDER*****
  
  
 PLAN SHEETS A2.1, A2.3, A4.1, A6.1, LS2.1, AND LS2.2
 WERE STAMPED, INITIALED, AND DATED.
  
 **REMINDER**
 THE NUMERICAL ADDRESS SHALL BE POSTED ON THAT PORTION
 OF THE BUILDING STRUCTURE FRONTING OR FACING UPON NORTH
 DIXIE HIGHWAY, SO AS TO BE READILY VISIBLE. PLEASE BE
 ADVISED THAT WINDOWS, DOORS, CANOPIES, ETC ARE NOT
 CONSIDERED BUILDING STRUCTURES FOR THE POSTING OF
 ADDRESS NUMBER.
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-15 Cont ID  
Sent By mwennerg Date 2008-07-15 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2008-07-15 Time 14:29 Sent To  
Notes
2008-07-15 14:36:21***PROVISO***
  
 COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING NEW COMMENT:
  
 1) SHEET LS2.1 ILLUSTRATES AN EMERGENCY LIGHT LOCATED
 IN CORRIDOR 112 AND SHEET E3.1 DOES NOT. PLEASE
 CORRELATE INFOMATION.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By mawillia Date 2008-04-21 Time 16:41 Rev Time 0.00
Received By mawillia Date 2008-04-21 Time 15:26 Sent To  
Notes
2008-04-21 16:02:09*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 4.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIRS
 GUARDRAILS/HANDRAILS.
  
 5.IT IS INDICATED ON SHEET LS2.1 THAT THE BUSINESS
 OCCUPANCY IS SPRINKLERED AND THE PARKING GARAGE IS NOT.
 PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.HOW
 WILL THE SPRINKLER SYSTEM BE MONITORED?
  
 6.ON SHEET E2.1, WHAT IS THE REASONING FOR THE CARD
 READER AS SHOWN IN THE REC ROOM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 13:01 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 13:01 Sent To  
Notes
2008-09-11 13:04:25TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 15:59 Sent To  
Notes
2008-06-18 10:04:32TO "COMM" BD#14
2008-06-17 16:00:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 15:26 Rev Time 0.00
Received By mawillia Date 2008-03-21 Time 14:10 Sent To  
Notes
2008-03-21 14:10:27TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-03 Cont ID  
Sent By rregueir Date 2008-10-03 Time 11:59 Rev Time 0.00
Received By rregueir Date 2008-10-03 Time 11:38 Sent To  
Notes
2008-10-03 12:00:26NEW ENERGY AND COOLING LOAD CALCS OK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-07 Cont ID  
Sent By rregueir Date 2008-07-07 Time 11:57 Rev Time 0.00
Received By rregueir Date 2008-07-07 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By rregueir Date 2008-04-11 Time 14:07 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 17:22 Sent To  
Notes
2008-04-11 14:07:06REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG AC-1: GENERAL NOTE #2 CALLS FOR RETURN DUCT TO BE
 TIGHT TO UNDERSIDE OF SUPPLY DUCT. SUFFICIENT SPACE
 SHALL BE PROVIDED ADJACENT TO ALL MECHANICAL COMPONENTS
 LOCATED IN OR FORMING A PART OF THE AIR DISTRIBUTION
 SYSTEM TO ASSURE ADEQUATE ACCESS FOR (1) CONSTRUCTION
 AND SEALING IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 603.1 OF THIS CODE; (2) INSPECTION; AND (3)
 CLEANING AND MAINTENANCE IN ACCORDANCE WITH FBCM
 603.1.3. SHOW HOW THIS IS TO BE ACCOMPLISHED WITH THESE
 TWO DUCT SYSTEMS TIGHT TO EACH OTHER.
  
 2. PG AC-2: GENERAL NOTES #1 INDICATES THAT EF-1 AND
 EF-2 ARE TO BE LOCATED ON ROOF ABOVE THE GARAGE, BUT
 THE GARAGE VENTILATION PLAN AND THE FAN SCHEDULE CALL
 FOR EF-7 AND EF-8 TO BE FOR THE GARAGE. PLEASE
 COORDINATE PLANS, SCHEDULES AND NOTES TO CLARIFY THE
 SCOPE OF WORK. FBCM 401.1 AND FBCB 106.1.1.
  
 3. PG AC-2: PLEASE INDICATE ON PLANS THE SOURCE OF
 MAKEUP AIR FOR EF-7 IN GARAGE. PLAN INDICATES SF-1 WILL
 ONLY OPERATE DURING CO ALARM MODE IN CONJUNCTION WITH
 EF-8.
  
 4. PG AC-2: PLEASE INDICATE ON PLANS WHICH METHOD WAS
 USED FOR DESIGN OF THE VENTILATION (OUTDOOR AIR). ONE
 OF TWO METHODS SHALL BE SELECTED IN ACCORDANCE WITH
 FBCM 403.1 AND 403.4. IT APPEARS THAT TABLE 403.3 WAS
 USED. HOWEVER, THERE ARE SOME CALCULATIONS WHICH DO NOT
 CORRESPOND WITH THE TABLE. EXAMPLE: THE RECEPTION AREA
 IS SHOWN AS BEING 465 SQUARE FEET. THE TABLE PUTS THE
 OCCUPANT LOAD AT 60 PEOPLE PER 1000SF FOR A TOTAL
 OCCUPANT LOAD OF 28 PEOPLE. THE TABLE ALSO CALLS FOR A
 VENTILATION RATE OF 15CFM PER PERSON. THIS GIVES A
 REQUIREMENT OF 420CFM OF OUTDOOR AIR FOR THIS AREA.
 THERE ARE OTHER AREAS WHICH APPEAR TO BE MISCALCULATED.
 PLEASE VERIFY ALL VALUES ON THE OUTDOOR AIR SUMMARY
 PRIOR TO RESUBMITTAL.
  
  
 5. PG AC-2: AIR CONDITIONING CONTROL SEQUENCE NOTE #4
 CALLS FOR EXHAUST FANS TO BE INTERLOCKED WITH ROOM
 LIGHT SWITCHES. WHERE MECHANICAL EXHAUST IS REQUIRED BY
 TABLE 403.3, RECIRCULATION OF AIR FROM SUCH SPACES
 SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3 IN ACCORDANCE WITH FBCM
 403.2.1(3). SINCE NOTE #1 REQUIRES SUPPLY FANS TO RUN
 CONTINUOUS DURING OCCUPIED MODE, HOW WILL THE AIR BEING
 SUPPLIED TO THE TOILET ROOMS BE EXHAUSTED WHEN LIGHT
 SWITCHES ARE TURNED OFF? SHOW COMPLIANCE WITH THIS
 SECTION BY EITHER INTERLOCKING EXHAUST FANS WITH AHU?S
 OR USING TRANSFER DUCTS FOR MAKEUP AIR TO THESE ROOMS.
  
 6. PG AC-2: PLAN SHOWS FOUR CONDENSING UNITS ON ROOF.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
 ALSO, CLEARANCES FOR ROOFTOP EQUIPMENT AND APPLIANCES
 SHALL BE IN ACCORDANCE WITH FBCB 1509.7. PROVIDE DETAIL
 FOR ROOF CURBS OR PRODUCT APPROVAL FOR PRE-ENGINEERED
 A/C STANDS AS APPROPRIATE FOR THE INSTALLATION METHOD
 CHOSEN. IF OTHER THAN A PRE-ENGINEERED SYSTEM IS USED,
 PROVIDE WIND LOAD CALCULATIONS WITH CORRESPONDING
 ATTACHMENT DETAILS.
  
 7. ENERGY CALCULATIONS: THERE ARE SOME BUILDING
 ENVELOPE COMPONENTS IN THE INPUT DATA REPORT (IDR)
 WHICH DO NOT CORRESPOND WITH THE INFORMATION ON THE
 PLANS. EXAMPLE: THERE ARE NO DOORS SHOWN IN THE IDR
 WHILE THE ARCHITECTURAL FLOOR PLAN SHOWS NEW DOORS
 BEING INSTALLED. EXAMPLE: THE IDR CALLS FOR R-22.2 ON
 THE ROOF, INCLUDING R-19 MINERAL WOOL BATTS.
 ARCHITECTURAL PLANS DO NOT CALL FOR R-19 BATTS. PLEASE
 SHOW ON PLANS HOW THE R-22.2 IS TO BE ACHIEVED OR
 ADJUST CALCULATIONS TO THE R-VALUE OF THE EXISTING ROOF
 SYSTEM PLUS THE INSULATION BEING ADDED AS SHOWN ON
 REFLECTIVE CEILING PLAN. THE OWNER SHALL DEMONSTRATE TO
 THE BUILDING DEPARTMENT?S SATISFACTION THAT ALL
 R-VALUES AND EQUIPMENT EFFICIENCIES CLAIMED ARE
 PRESENT. IF THE BUILDING WAS BUILT AFTER 1980, THE
 ORIGINAL ENERGY CODE SUBMITTAL MAY BE USED TO
 DEMONSTRATE EFFICIENCIES IN ACCORDANCE WITH FBCB
 13-101.4.2.1.
  
 8. PG A2.3 SHOWS SKYLIGHTS WHICH MAY OR MAY NOT REMAIN.
 IS THE HEAT GAIN FROM THE SKYLIGHTS INCLUDED IN THE
 COOLING LOAD CALCULATIONS FOR A/C SIZING? DO THESE
 SKYLIGHTS HAVE AN IMPACT ON THE R-VALUE OF THE ROOF
 SYSTEM? PLEASE CLARIFY AND INDICATE WHETHER OR NOT
 THESE SKYLIGHTS WILL REMAIN. THE PLANS AND
 SPECIFICATIONS, INCLUDING THE ENERGY CODE CALCULATIONS,
 SHALL SHOW, IN SUFFICIENT DETAIL, ALL PERTINENT DATA
 AND FEATURES OF THE BUILDING IN ACCORDANCE WITH FBCB
 13-103.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-15 Cont ID  
Sent By kstevens Date 2008-07-15 Time 12:14 Rev Time 0.00
Received By kstevens Date 2008-07-15 Time 12:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By kstevens Date 2008-04-16 Time 14:53 Rev Time 0.00
Received By kstevens Date 2008-04-15 Time 12:58 Sent To  
Notes
2008-04-16 17:52:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHTS A0, A2.1, A2.3 & A2.4 COMPASS "N" IS
 INCONSISTANT. SHT A0 SHOWS COMPASS "N" AT THE TOP OF
 THE SHEET AS DOES SHT A2.3. BUT SHTS A2.1, A2.2 & A2.4
 SHOW COMPASS "N" AT THE BOTTOM OF THE SHEET.PLEASE
 CORRELATE. SECTION 106.1.1.
  
 2. SHT A2.1 TOILET ROOMS 109 & 110 SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. SHOW
 THE CLEAR FLOOR SPACE FOR ALL FIXTURES. DOORS MAY NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. SHOW THE TURNING AREA IN EACH TOILET ROOM.
 (DETAILS 8 & 9 SHT A8.2 ARE NOT CODE COMPLIANT). SEE
 SECTION 11-4.1.3(11).
  
 3. SHT A2.1 SHOW THE CLEAR FLOOR SPACE FOR THE ELECTRIC
 WATER COOLER, (DRINKING FOUNTAIN), AND SHOWERS AS WELL
 AS THE W/C'S & LAVS IN ALL TOILET ROOM/BATHROOMS.
 SECTIONS 11-4.15.5, 11-4.16.2, 11-4.19.3 & 11-4.21.2
 (FIG 35A OR 35B). ALSO SHOW THE CLEAR FLOOR SPACE FOR
 THE KITCHEN SINK PER 11-4.24.5.
  
 4. SHT A2.1 SHOWERS SHALL BE ACESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.21 WITH ALL
 SUBSECTIONS. SHOWER SIZES SHALL COMPLY WITH SECTION
 11-4.21.2 AND ARE REQUIRED TO BE 36" X 36" FINISHED
 DIMENSIONS, FIGURE 11-35A OR 30" X 60" FIGURE 11-35B.
 PLEASE INDICATED SIZE OF SHOWER ON PLANS.
  
 5. SHT A8.1 DETAILS 1,3 & 5 SHOW COMPLIANCE WITH
 SECTION 11-4.16.5 FLUSH CONTROLS, 11-4.19.2 CLEARANCES
 & 11-4.19.5 FAUCETS.
  
 6. SHT A8.1 DETAIL 21 SHOW COMPLIANCE WITH SECTIONS
 11-4.24.4 SINK DEPTH & 11-4.24.7 FAUCETS.
  
 7. SHT P-2 TRAP PRIMERS SHALL BE INSTALLED FOR THE
 FLOOR DRAINS AT EACH WATER HEATER. SECTION 1002.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-20 Cont ID  
Sent By mflis Date 2008-06-20 Time 11:05 Rev Time 0.00
Received By mflis Date 2008-06-20 Time 11:05 Sent To  
Notes
2008-06-20 11:05:50ZONING REVIEW: PASSED
  
 ** NOTE - APPROVED ELEVATIONS INCLUDE PLANTER BOXES ON
 DIXIE HWY
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By mflis Date 2008-04-03 Time 08:29 Rev Time 0.00
Received By mflis Date 2008-04-03 Time 08:29 Sent To  
Notes
2008-04-03 08:31:21ZONING REVIEW: FAILED
  
 1) PLEASE INDICATE PARKING SPACES AS DOUBLE STRIPED PER
 CITY REQUIREMENTS; SEE CODE FOR STANDARD DETAIL
 2) PLEASE INDICATE ACCESSBILE ROUTE FROM ADA SPACE TO
 OFFICE AREA
 3) THE PLANS DO NOT INCLUDE ANY EXTERIOR ELEVATIONS.
 CONFIRM THAT NO EXTERIOR WORK IS TO BE COMPLETED UNDER
 THIS PERMIT.
  
 MATT FLIS - 822-1445