Plan Review Details - Permit 08030477
Plan Review Stops For Permit 08030477
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By lursu Date 2008-04-09 Time 08:26 Rev Time 0.00
Received By lursu Date 2008-04-09 Time 08:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-20 Cont ID  
Sent By lmartine Date 2008-06-20 Time 16:00 Rev Time 0.00
Received By lmartine Date 2008-06-20 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-28 Cont ID  
Sent By jwitmer Date 2008-05-28 Time 10:11 Rev Time 1.22
Received By jwitmer Date 2008-05-28 Time 10:11 Sent To PC
Notes
2008-05-28 10:16:12BUILDING PLAN REVIEW
 PERMIT: 08030477
 ADD: 1441 BRANDYWINE RD UNIT "H"
 CONT: PENCO CONSTRUCTION
 TEL: (407)898-9896
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B)COMPLIED.
  
 1C)SHEET A1-0 PROJECT DESCRIPTION USE OF WHITE OUT
 NOT ALLOWED. PLEASE REMOVE AND REPLACE THIS SHEET WITH
 THE CORRECTION MADE, NO WHITE OUT.106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By jwitmer Date 2008-04-11 Time 12:07 Rev Time 2.22
Received By jwitmer Date 2008-04-11 Time 12:07 Sent To  
Notes
2008-04-11 14:55:01BUILDING PLAN REVIEW
 PERMIT: 08030477
 ADD: 1441 BRANDYWINE RD UNIT "H"
 CONT: PENCO CONSTRUCTION
 TEL: (407)898-9896
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE. NOTE ONLY ONE
 ENGINEERING REPORT WAS SUBMITTED, ONE ENERGY FORM AND
 ONE PRODUCT APPROVAL PACKET.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)THE ENGINEERING REPORT THAT WAS SUBMITTED BY MILTON
 ENGINEERING IS NOT SIGNED NOR SEALED BY EITHER ENGINEER
 LISTED WITHIN THE REPORT.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXEDTO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 3)MILTON ENGINEERING,ENGINEERS REPORTS PLEASE NOTE
 HOW TO IDENTIFY WHAT IS COVERED WITHIN THE REPORT AND
 NOT HAVING TO SIGN AND SEAL EACH PAGE. 61G15-23.002(2)
 FL. ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX.
  
 4) MILTON ENGINEERING, MISSING THEIR COA, CERTIFICATE
 OF AUTHORIZATION.61G15-23.002(2)FL. ADMIN. CODE.
 PLANS AND OR REPORTS PREPARED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE
 NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 5) 106.1.2 ADDITIONAL INFORMATION REQUIRRED. THERE
 APPEARS TO BE A BIT OF DISCREPANCY, THE PLANS INDICATE
 WORK TO BE COMPLETED IN BUILDING 900 UNIT "H". WHERE AS
 THE PERMIT APPLICATION IN THE LOCATION PORTION OF THE
 APPLICATION INDICATES G & H BUT THE G WAS STRUCK. IN
 THE BODY OF TEXT DESCRIPTION OF PROJECT THE TEXT READS
 BLDG 900 UNITS G & H THEN ON THE NEXT LINE,
 "UNIT H FLOOR PLAN",UNIT G REPAIR & REPLACE DRYWALL
 ELECTRICAL SWITHES AND RECEPTACLES, CPLEASE CLARIFY AS
 TO WHAT WORK WILL BE ACCOMPLISHED UNDER THIS PERMIT.
 NOTE IS UNIT "H" TO BE A LEVEL 2 ALTERATION AND UNIT G
 WE CAN'T DETERMINE AT THIS POINT IN TIME IF THIS IS TO
 BE CONSIDERED A REPAIR ASPER CHAPTER 4 OFTHE FBC
 EXISTING BUILDING CODE OR ALEVEL 1 ALTERATION?
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
 6)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 11:46 Sent To B
Notes
2008-06-20 11:46:57PLANS REMOVED FROM BOARD AND GIVEN TO LUIS MARTINEZ

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 15:55 Sent To  
Notes
2008-05-04 15:55:25** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5 AS THE
 COMMENT WAS RELATED TO DINING ROOM CIRCUIT. THE CIRCUIT
 WAS UPDATED HOWEVER THE LOAD CALCULATIONS WERE NOT
 UPDATED. PLEASE SEE 210.52B1, 210.11C1, 220.52.
  
 2) NOTE: PLEASE KNOW AS PREVIOUS REVIEW NOTE #1 ABOVE
 THE LOAD ON THE SERVICE WHICH HAS NOW BEEN DECREASED TO
 100AMPS IS OF CONCERN. THIS OFFICE CAN NOT CONFIRM CODE
 COMPLIANCE AS THE LOAD ON THE REVISED 100AMP PANEL IS
 ALREADY AT 96.04 AMPS.
 PLEASE SEE 220.83, 220.87
  
 3) NOTE: PLEASE SEE THE PLANS APPEAR TO SHOW A MISPRINT
 FOR THE SMALL APPLIANCE CIRCUIT A-2, AS THE A-2 ON
 PANEL SCHEDULE IS ONE LEG OF THE WATER HEATER. THE
 PANEL SCHEDULE SHOWS CIRCUITS ONE AND THREE AS THE
 SMALL APPLIANCE CIRCUITS.
 210.52B1, 408.4
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 16:38 Sent To  
Notes
2008-03-21 16:39:07** DENIEDREVIEW **
  
  
  
 1) NOTE:PLEASE SEE THE FOLLOWING CODE IS IN AFFECT
 FOR THE ELECTRICAL CODE.
 2005 NFPA-70
 THIS IS REFLECTED ON COVER SHEET HOWEVER SEVERAL OF THE
 CODE SECTIONS NOTED ON ELECTRICAL PLANS ARE ACTUALLY
 NOT FROM THE CURRENT NEC.
 FOR EXAMPLE: PLEASE SEE PLANS REFLECT 220.19A, 220.30
 ETC WHICH ARE NOT IN THE CURRENT CODE.
 PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN THE
 FOLLOWING CODES REFERENCE FOR DESIGN.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE THE CONDUCTORS SHOWN FOR FEEDERS
 ARE NOT RATED FOR THE 125AMP MCB ON PANEL.
 PLEASE SHOW THE OVER CURRENT PROTECTION WHICH FEEDS
 THESE CONDUCTORS AT METER/SERVICE MAIN LOCATION.
 310.16, 310.15B6, 240.6, 240.4 ETC
  
 3) NOTE: PLEASE VERIFY IF PANEL IS GOING TO BE NEW OR
 ALREADY EXISTS. PLEASE SEE RISER WHICH NOTES THIS PANEL
 AS NEW YET THE PANEL SCHEDULE SHOW THIS AS EXISTING?
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS
 CLEARLY STATE AND SHOW *SMOKE DETECTORS*. SMOKE
 DETECTORS ARE ONLY DEVICE WHICH DETECT AND DO NOT SOUND
 AN ALARM. THIS WOULD REQUIRE DEVICES TO BE PART OF HORN
 DEVICES AND A FIRE ALARM SYSTEM WHICH IS NOT SHOWN ON
 PLANS.
 SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND AN
 ALARM.
 PLEASE ADJUST ACCORDINGLY.
 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, AND 220.52 AS
 THE DINING ROOM RECEPTACLES ARE NOT PERMITTED TO BE
 PART OF THE LIGHTING CIRCUIT WHICH IS WHAT IS NOTED ON
 PANEL SCHEDULE AND SHOWN ON PLANS.
 PLEASE ADJUST CIRCUITING, PLEASE ADJUST LOADS AND LOAD
 CALCULATIONS.
 PLEASE SEE SECTIONS AS NOTED.
  
 6) NOTE: PLEASE SEE 210.11C3 AS THE BATH CIRCUITS SHALL
 BE DEDICATED TO EACH BATH ROOM OR ONLY THE RECEPTACLES
 MAY BE FED TO OTHER BATH ROOMS.
 IN EITHER CASE THESE MAY NOT FEED OTHER RECEPTACLES OR
 LOCATIONS.
 FOR EXAMPLE: BOTH BATH ROOMS ARE FED FROM THE SAME
 CIRCUIT AND ALSO PLANS SHOW THIS SAME CIRCUIT FEEDING
 OUTSIDE GFI.
 ALL OF THESE AS SHOWN ARE NOT PERMITTED.
  
 7) NOTE: PLEASE LIST THE REQUIRED ARC FAULT CIRCUITS
 PER 210.12. THE PLANS DO NOTE PROTECTION IS REQUIRED
 HOWEVER THE CIRCUITS ON PANEL NEED TO SHOW THIS.
  
 8) NOTE: PLEASE SEE 408.4 AS THIS REQUIRES THE PANEL
 SCHEDULE TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED.
  
 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FS
 471.025, FAC 61G15-23.002 AND FBC 13-103.1.1.1. THE
 SHEETS IN FACT CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED.
  
 10) NOTE: PLEASE VERIFY SCOPE OF WORK AS PERMIT
 APPLICATION STATES UNIT G AND H YET PLANS ARE ONLY FOR
 UNIT H.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-19 Cont ID  
Sent By mawillia Date 2008-06-19 Time 15:49 Rev Time 0.00
Received By mawillia Date 2008-06-19 Time 15:20 Sent To  
Notes
2008-06-19 15:49:53*****APPROVED*****
  
 PLAN SHEETS A1.0 AND E1-1 WERE STAMPED, INITIALED, AND
 DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By mawillia Date 2008-05-14 Time 16:54 Rev Time 0.00
Received By mawillia Date 2008-05-14 Time 16:35 Sent To  
Notes
2008-05-14 16:51:49*****PROVISO*****
  
  
 1.ON SHEET A1-0 - GENERAL NOTE 18 - REFERENCES THE
 2006 EDITION OF NFPA 101;AMEND TO SHOW 2003 EDITION
 AS CORRECTLY LISTED UNDER CODES.INCORRECTLY SHOWING
 REFERENCE TO 2006 CODE IN GENERAL NOTE 18 AND UNDER THE
 CODE DATA
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENT AND ANY OTHER REVIEWER'S COMMENTS HAVE
 BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By mawillia Date 2008-04-16 Time 15:33 Rev Time 0.00
Received By mawillia Date 2008-04-16 Time 14:38 Sent To  
Notes
2008-04-16 14:50:25*****DENIED*****
  
  
 1.ON SHEET A1-0 - GENERAL NOTE 18 - REFERENCES THE
 2006 EDITION OF NFPA 101;AMEND TO SHOW 2003 EDITION
 AS CORRECTLY LISTED UNDER CODES.
  
 2.VERIFY WITH THE PERMIT SPECIALIST THAT THE
 APPROPIATE UNIT OR UNITS IS/ARE REFLECTED IN THE
 PROJECT SITE ADDRESS.PRESENTLY, NO UNIT/UNITS IS/ARE
 SHOWN WHEN THE APPLIED PERMIT NUMBER IS ENTERED INTO
 COMMUNITY PLUS.
  
 3.ON THE PERMIT APPLICATION, IT IS INDICATED THAT THE
 SCOPE OF WORK IS FOR UNITS G & H OF THE 900 BUILDING;
 HOWEVER ONLY UNIT "H" IS LISTED IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.IN THE GENERAL NOTES UNDER
 THE WALL TYPE LEGEND, UNIT "G" IS LISTED.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING ROADS, ALLEYS, FIRE
 LANES).
  
 6.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 7.SMOKE DETECTORS OR SMOKE ALARMS?ON SHEET E1-0,
 SMOKE DETECTORS (SD) ARE SHOWN IN THE ELECTRICAL LEGEND
 AS WELL AS THE ELECTRICAL PLAN LAYOUT.PLEASE BE
 ADVISED THAT SMOKE DETECTORS (SD) ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS (SA)
 SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT AND SHALL
 NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
  
 8.SHOW THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFIES THE 75' TRAVEL DISTANCE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 15:31 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 15:31 Sent To  
Notes
2008-06-05 15:38:21TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 16:47 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 16:47 Sent To  
Notes
2008-04-28 16:47:32TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-16 Cont ID  
Sent By mawillia Date 2008-04-16 Time 14:38 Rev Time 0.00
Received By mawillia Date 2008-03-20 Time 16:18 Sent To  
Notes
2008-03-20 16:32:11TO "COMM" BD#36

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 16:58 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 16:30 Sent To  
Notes
2008-04-09 16:58:19ENERGY CALCULATIONS WHICH WERE PROVIDED WITH THE PERMIT
 APPLICATION WERE NOT REVIEWED FOR COMPLIANCE WITH THE
 MECHANICAL PROVISIONS OF FBCB CHAPTER 13. METHOD A
 CLACULATIONS ARE NOT APPLICABLE FOR THE WORK PROPOSED
 IN ACCORDANCE WITH FBCB 13-101.6. MECHANICAL ELEMENTS
 SHOWN ON PLANS MEET THE MINIMUM EFFICIENCIES ALLOWED ON
 FORM 600C AND ARE THEREFORE DEEMED CODE COMPLIANT UNDER
 THIS SECTION. PLEASE SEE OTHER TRADE REVIEWS FOR FBCB
 CHAPTER 13 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-05-10 Cont ID  
Sent By kstevens Date 2008-05-10 Time 07:16 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 07:16 Sent To  
Notes
2008-05-10 07:17:19PLUMBING PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By kstevens Date 2008-04-11 Time 17:52 Rev Time 0.00
Received By kstevens Date 2008-04-11 Time 17:52 Sent To  
Notes
2008-04-11 17:55:48DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. NO PLUMBING PLANS SUBMITTED OR REQUIRED FOR SCOPE OF
 WORK, BUT CLARIFICATION REQUIRED ON IF THIS IS ONE UNIT
 OR TWO UNITS. APPLICATION INDICATES UNITS G & H IN
 DESCRIPTION OF WORK, BUT PLANS ONLY INDICATE ONE UNIT.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-29 Cont ID  
Sent By choops Date 2008-04-29 Time 08:44 Rev Time 0.00
Received By choops Date 2008-04-29 Time 08:44 Sent To  
Notes
2008-04-29 08:45:02***APPROVED - RESUB #1 (RESTAMPED PLANS)***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 13:11 Rev Time 0.00
Received By choops Date 2008-03-26 Time 13:11 Sent To  
Notes
2008-03-26 13:13:23***APPROVED***
  
 PROVISO:
 A/C CONDENSOR UNIT SHALL NOT PROJECT MORE THAN 4' INTO
 A REQUIRED SETBACK.