Plan Review Details - Permit 08030433
Plan Review Stops For Permit 08030433
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By shill Date 2008-09-23 Time 10:50 Rev Time 0.00
Received By shill Date 2008-09-23 Time 10:50 Sent To  
Notes
2008-09-23 13:11:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ALL CHANGES TO THE ISSUED PERMIT ARE CONSIDERED
 REVISIONS AND APPROPRIATE FEES SHOULD BE PAID AT THE
 TIME OF SUBMITTAL. A BILL IS ATTACHED.
  
 2. FBC CHAPTER 35, INCORRECT VERSION OF ASCE7 DECLARED
 (SHOULD BE ASCE7-02 RATHER THAN -05), FBC1609.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL IS REQUIRED
 FOR THE MULLIONS, FAC9B72. IF A FLORIDA STATE PRODUCT
 APPROVAL IS NOT AVAILABLE FOR THIS PRODUCT,
 WWW.FLORIDABUIDLING.ORG, A LOCAL PRODUCT APPROVAL WILL
 BE REQUIRED, HTTP://WWW.DCA.STATE.FL.US/F
 BC/COMMITTEES/PRODUCT_APPROVAL/LOCAL%20PRODUCT%20APPROV
 AL%20APPL%20080103.PDF.
  
 PROOF OF QUALITY ASSUANCE, COMPLETED APPLICATION, MUST
 BE SUBMITTED AS WELL AS ENGINEERING. THE ENGINEERING
 SUBMITTED STATES "ALLOY 6061-T6 IS ASSUMED ALLOY AS
 THIS IS MOST COMMON ALLOY USED FOR ALUMINUM DRAWN
 TUBE." COMPONENTS AND CLADDING ARE REQUIRED TO HAVE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL; ENGINEERING
 WITH ASSUMPTIONS REGARDING MATERIALS USED CANNOT BE
 SUBMITTED. ENGINEERING MUST PROVIDE INFORMATION
 REGARDING THE MATERIALS ACTUALLY USED.
  
 4. ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED ON EACH SHEET (CERTIFICATE OF AUTHORIZATION,
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING
 THE DOCUMENT).
  
 5. PLEASE CONFIRM EXPOSURE B CONDITIONS. NOTE THAT PALM
 BEACH COUNTY PROPERTY APPRAISER AERIALS SHOW SOME OF
 THE BUILDINGS ADJACENT TO A GOLF COURSE WHICH APPEARS
 TO CREATE EXPOSURE C CONDITIONS FOR SOME OF THE
 BUILDING ELEVATIONS. IF NECESSARY, PROVIDE A SITE PLAN
 SHOWING THIS BUILDING LOCATION; USE OF AERIALS IS
 ACCEPTABLE. FBC1603.1.4, FBC1609.4(3).
  
 6. THE REVISION SUBMITTED, SHEET S1 4/25/07, STATES
 THAT "EXISTING STRUCTURAL MULLION TO REMAIN". THE FLOOR
 PLAN SHOWS THE MULLION AS AN EXISTING STRUCTURAL
 MULLION. PLEASE REVISE OTHER DOCUMENTS TO REFLECT THIS
 CHANGE TO THE SCOPE OF WORK; FBC*106, FBC16. DURING THE
 PLAN REVIEW PROCESS, I WAS TOLD BY THE CONTRACTOR THAT
 THIS WAS A STEEL STRUCTURAL MULLION/COLUMN. IF THIS IS
 A STRUCTURAL COLUMN, ALL LOADS MUST BE CONSIDERED
  
 7. NOTE THAT THE DESIGN PRESSURE FOR THE MULLIONS,
 +33.7/-44 IS LESS THAN THE DESIGN PRESSURES INITIALLY
 DECLARED FOR THE JOB, +39.5/-52.9 (REPORT, PAGE 2,
 CONCLUSIONS).
  
 8. PLEASE CLARIFY; THE MULLION CALCULATIONS STATE THAT
 ATTACHMENT IS INTO CONCRETE. IS THIS AT BOTH THE TOP
 AND BOTTOM?

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 11:54 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 11:54 Sent To B
Notes
2008-09-15 11:55:48TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-19 Cont ID  
Sent By spalmer Date 2008-03-19 Time 11:05 Rev Time 0.00
Received By spalmer Date 2008-03-19 Time 11:05 Sent To  
Notes
2008-03-19 11:05:18NO PLAN REVIEW FOR EXPIRED PERMIT