Plan Review Details - Permit 08030425
Plan Review Stops For Permit 08030425
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-09-25 Cont ID  
Sent By mperson Date 2008-09-25 Time 08:21 Rev Time 0.30
Received By mperson Date 2008-09-25 Time 08:21 Sent To PC
Notes
2008-09-25 08:23:03REVISION: "OK" REMOVING DRYER & FUTURE WATER HEATER
 FROM PLANS. *MRPERSON.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-09-19 Cont ID  
Sent By mperson Date 2008-09-19 Time 16:21 Rev Time 0.00
Received By mperson Date 2008-09-19 Time 16:21 Sent To PC
Notes
2008-09-19 16:34:01GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: SUBMITTED REVISION DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS AND COMPLY.
  
 2. THE ABOVE GROUND SCHEDULE 40 METALLIC PIPE (GALV.)
 NEEDS TO BE 1". THE PIPE CAN REDUCE TO 3/4" AFTER THE
 SHUT OFF VALVE TO THE POOL HEATER. PLEASE REFERENCE
 TABLE 402.4(2) ATTACHED TO THESE COMMENTS INDICATING
 THIS. PER FBC-2004 FUEL GAS SIZING TABLE 402.4(2).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-08-07 Cont ID  
Sent By mperson Date 2008-08-07 Time 08:31 Rev Time 0.00
Received By mperson Date 2008-08-07 Time 08:31 Sent To I
Notes
2008-08-07 08:33:51REVISION: "OK", ADDED 25' OF GAS PIPING TO DRYER AND
 FUTURE WATER/HTR. PIPE SIZE CHANGES DUE TO NEW LONGEST
 LENGTH.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-03-19 Cont ID  
Sent By mperson Date 2008-03-19 Time 15:01 Rev Time 0.00
Received By mperson Date 2008-03-19 Time 15:01 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 14:57 Sent To G
Notes
2008-09-18 14:58:07TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-07 Cont ID  
Sent By mperson Date 2008-08-07 Time 08:34 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 08:31 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-19 Cont ID  
Sent By mperson Date 2008-03-19 Time 15:12 Rev Time 0.00
Received By mperson Date 2008-03-19 Time 15:01 Sent To  
Notes
***NONE***