Plan Review Details - Permit 08030414
Plan Review Stops For Permit 08030414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By rmcdouga Date 2008-04-30 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2008-04-30 Time 17:21 Sent To  
Notes
2008-04-30 17:23:44REVISED SECONDARY WATER BARRIER PRODUCT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By rmcdouga Date 2008-03-27 Time 08:52 Rev Time 0.00
Received By rmcdouga Date 2008-03-27 Time 07:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By shill Date 2008-03-20 Time 12:59 Rev Time 0.00
Received By shill Date 2008-03-20 Time 12:59 Sent To  
Notes
2008-03-20 13:01:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
 INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE
 MITIGATION.
 THIS IS REQUIRED FOR BOTH THE FLAT DECK AND THE STEEP
 SLOPE ROOF.PLEASE BE SPECIFIC AS TO HOW YOU WILL
 COMPLY WITH THIS REQUIREMENT.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
 PLEASE SPECIFY SQUARE FOOT AREA OF EARCH ROOF TYPE.
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
 THE NOA FOR THE FLAT DECK IS INCOMPLETE, MISSING THE
 LAST PAGE.PLEASE SEE GENERAL LIMITATION #7 ON THE
 LAST PAGE TO SEE IF ENGINEERING IS REQUIRED.
  
 THREE DIFFERENT ASSEMBLIES WERE PROVIDED.ONE IS A
 TILE UNDERLAYMENT; IS THIS WHAT YOU ARE USING FOR THE
 SECONDARY WATER BARRIER FOR THE SHINGLE ROOF?ONE
 ASSEMBLY REFERRED TO GENERAL LIMITATION #9; NO ENHANCED
 FASTENING PERMITTED.PLEASE CLARIFY WHICH SYSTEM YOU
 WILL BE USING.
  
 _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 12:04 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 12:04 Sent To B
Notes
2008-04-30 12:05:02TO "RMCDOUGAL" DESK/REV