Plan Review Details - Permit 08030391
Plan Review Stops For Permit 08030391
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-07-23 Cont ID  
Sent By shill Date 2008-07-23 Time 15:04 Rev Time 0.00
Received By shill Date 2008-07-23 Time 15:04 Sent To PC
Notes
2008-07-23 15:07:41REVISED A0.0, A1.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 14:54 Rev Time 0.00
Received By shill Date 2008-05-29 Time 14:54 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-16 Cont ID  
Sent By shill Date 2008-05-16 Time 17:11 Rev Time 0.00
Received By shill Date 2008-05-16 Time 17:11 Sent To  
Notes
2008-05-16 17:15:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.CITY PLACE MANAGEMENT APPROVAL REQUIRED; PLEASE
 PROVIDE THE STAMP ON EACH NEW SHEET.
  
 2.TWO COLLATED SETS OF PERMIT DOCUMENTS REQUIRED FOR
 PERMIT ISSUANCE.PLEASE REMOVE THE OLD SHEETS AND
 INSERT THE NEW SHEETS INTO THE BOUND SET OF PLANS, AND
 SUBMIT OLD SHEETS SEPARATELY FOR REFERENCE.
  
 3.(INFORMATIONAL)ALL PLAN SHEETS AFFECTED BY
 BUILDING PLAN REVIEW (A0.0, A1.0, E1 DATED 5/8/8) HAVE
 BEEN STAMPED AND INITIALED.THEREFORE, IN MY ABSENCE,
 THE FAILED STATUS CAN BE CHANGED TO PASS ONCE ITEMS 1
 AND 2 HAVE BEEN ADDRESSED.NO NEW PLAN REVIEW
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 11:16 Rev Time 0.00
Received By shill Date 2008-04-29 Time 11:16 Sent To  
Notes
2008-04-29 11:23:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM,
 FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE
 SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL
 SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO
 REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE
 CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN
 AS NEW.
  
 THIS WAS ADDED TO A1.0; PLEASE ALSO ADD TO ELECTRIC
 SHEET(S) AS NECESSARY.
  
 2-7.ADDRESSED.
  
 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC.
  
 AS DISCUSSED, THE FOOD PREPARATION AREA IS TO BE
 SEPARATED FROM THE GENERAL AREA (CUSTOMER AND HALLWAY
 LEADING TO BATHROOM) WITH WALLS/DOORS.
  
 9-10. ADDRESSED.
  
 11.AS DISCUSSED, THE CORRIDOR IS MOST LIKELY A 1 HOUR
 DOOR (AS IT MAY SERVE A LARGE RESTAURANT, ASSEMBLY
 OCCUPANCY).PLEASE NOTE THIS 1 HOUR REQUIREMENT AND
 ALSO THE STRUCTURAL COLUMN REQUIREMENT ON THE PLAN SO
 THAT FIRE RESISTIVE REQUIREMENTS FOR WALLS, COLUMNS,
 AND PENETRATIONS WILL BE MAINTAINED.
  
 12.ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By shill Date 2008-03-24 Time 10:16 Rev Time 0.00
Received By shill Date 2008-03-24 Time 10:16 Sent To  
Notes
2008-03-24 10:49:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM,
 FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE
 SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL
 SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO
 REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE
 CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN
 AS NEW.
  
 2.APPLICABLE CODES STATE FBC2004 WITH WPB AMENDMENTS.
 PLEASE DECLARE GOVERNING CODE BASED ON APPLICATION
 DATE; IN THIS CASE, FBC 2004 WITH 2007
 SUPPLEMENTS/REVISIONS.NOTE THAT AMENDMENTS APPLY ONLY
 TO CHAPTER 1, ADMINISTRATION.OTHER (CODE)
 REVISIONS/SUPPLEMENTS GOVERN THROUGHOUT THE STATE.
  
 3.M1, A0.0, HAVE REVISIONS IN INK.AS THIS IS A
 PRIVATE PROVIDER PLAN, I HAVE NO WAY TO DETERMINE
 WHETHER OR NOT THE REVIEWER HAS SEEN THESE CHANGES.
 PLEASE INCORPORATE ALL CHANGES TO THE PLAN INTO THE
 PRINTED SET.
  
 4.MAXIMUM TRAVEL DISTANCE A0.0 IS SHOWN AS 300FT, SEE
 FBC TABLE 1015.1 AND REVISE TO BE CODE COMPLIANT.
  
 5.DOORS E3, E1 ARE SHOWN ON THE PLAN AND LABELED BUT
 I WAS UNABLE TO LOCATE A NOTE INDICATING WHETHER THE
 EXISTING WILL REMAIN OR IF THEY WILL BE REPLACED.IF
 REPLACING, PROVIDE PRODUCT APPROVAL FAC9B72, HAVE
 REVIEWED BY DESIGNER OF RECORD, AND DECLARE COMPONENTS
 AND CLADDING PRESSURES FBC1603.IF EXISTING WILL
 REMAIN, PLEASE NOTE ON THE PLAN.
  
 6.BUILDING TYPE III IS DECLARED.OTHER PLANS HAVE
 DECLARED THIS BUILDING AS NONCOMBUSTIBLE; PLEASE
 PROVIDE INFORMATION REGARDING HOW YOU DETERMINED THIS
 BUILDING TYPE.
  
 7.A0.0 DECLARES THIS BUILDING AS "PROTECTED".THIS
 IS LANGUAGE FROM FBC2001 AND IS NO LONGER USED IN
 FBC2004.PLEASE DECLARE TYPE A OR B, FBC TABLE 601.
  
 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC.
  
 9.PLEASE PROVIDE SPECIFICATIONS FOR THE FRP PANEL AS
 I WAS UNABLE TO LOCATE THE THE TYPE SPECIFIED ON THE
 INTERNET.
  
 10.CERTIFICATE OF AUTHORIZATION REQUIRED FOR ZIEL
 DESIGN GROUP.THIS NUMBER IS REQUIRED TO BE PRINTED ON
 EACH SHEET, FAC61G1-15.002,003.
  
 11.TWO TENANT SEPARATION WALLS ARE SHOWN.NO
 INFORMATION WAS PROVIDED REGARDING THE THIRD INTERIOR
 WALL, BUT A MECHANICAL PENETRATION IS SHOWN THROUGH
 THIS WALL.PLEASE CLARIFY FIRE RESISTANCE RATING
 REQUIREMENT.IF THE THIS IS NOT A TENANT SEPARATION
 WITH A FIRE RATED DOOR, INCLUDE THIS ADDITONAL SQUARE
 FOOT AREA AND INCLUDE IN OCCUPANT LOAD.
  
 12.SIGNAGE REQUIED, FBC712.5 ABOVE THE NEW CEILING
 ALONG THE TENANT SEPARATION WALLS.PLEASE NOTE THAT ON
 THE PLAN THAT SIGNAGE WILL BE ADDED IF REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-08-05 Cont ID  
Sent By btrobaug Date 2008-08-05 Time 16:23 Rev Time 0.00
Received By btrobaug Date 2008-08-05 Time 15:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-22 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 16:49 Rev Time 0.00
Received By btrobaug Date 2008-07-22 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-02 Cont ID  
Sent By btrobaug Date 2008-06-02 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-06-02 Time 09:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 10:22 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 09:50 Sent To  
Notes
2008-05-22 10:22:18 
 NONCOMPLIANT
  
 SEE BUIDING COMMENTS REGARDING CITY PLACE MANAGEMENT
 APPROVAL AND COLATED PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 13:43 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 13:43 Sent To  
Notes
2008-05-04 13:43:35** DENIED 2ND AUDIT **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS AUDIT STILL
 REMAIN AND CODE COMPLIANCE ON PLANS HAS NOT YET BEEN
 ACHIEVED. AS STATED PREVIOUSLY AS THERE WERE SOME ITEMS
 NOT YET SUBMITTED CODE COMPLIANCE FOR THOSE ITEMS COULD
 BE DETERMINED. PLEASE SEE SOME OF THE SPECIFIC CODES
 AND NOTES BELOW ARE BASED ON REVISED PLANS AND
 INFORMATION ONLY NOW BEING SUBMITTED.
  
 1) NOTE: PLEASE COMPLETE LIGHTING FIXTURE LEGEND ON
 PLANS AND LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THE FOLLOWING ARE SOME EXAMPLES GIVEN FOR
 BENEFIT ONLY. THIS MAY NOT BE AN EXHAUSTED LIST.
 FOR EXAMPLE:
 THE LIGHT FIXTURE IN BATHROOM IS NOT ON LEGEND. PLEASE
 KNOW THE WATTAGE AS FIGURED INTO THE LIGHTING
 CALCULATIONS SHALL BE BASE DON THE FIXTURE AVAILABLE
 WATTAGE AND NOT THE BULB.
 FOR EXAMPLE:
 PLEASE SEE PLANS CLEARLY SHOW TRACK/ACCENT LIGHTING
 HOWEVER THE LIGHTING CALCULATIONS DO NOT INCLUDED ANY
 OF THESE FIXTURES. PLEASE ALSO SEE THE FIXTURE LEGEND
 DOES NOT INCLUDE ANY OF THESE.
 PLEASE SPECIFICALLY SEE THE CODE SECTIONS ABOVE AS THE
 TRACK LIGHTING IS FIGURED ON TRACK VA PER FT, VA PER
 FIXTURE OR VA FOR TRANSFORMER.
 THIS WILL DEPEND ON ONE OF THREE SCENARIOS. AS THESE
 FIXTURES ARE NOT ON LEGEND THE SECTION OF THE CODE IN
 GENERAL FOR ALL TRACK LIGHTING IS BEING GIVEN.
  
 2) NOTE: PLEASE BE SURE THE NOTICE TO BUILDING OFFICIAL
 IS COMPLETE AND INFORMATION ON THE NOTICE COORDINATES
 WITH THE SIGNED AFFIDAVITS FOR PRIVATE PROVIDER.
 PLEASE BE SURE ONCE PLANS ARE REVISED TO OBTAIN NEW
 AFFIDAVITS TO COORDINATE WITH REVISED DATED PLANS.
 FS 553.791
  
 3) NOTE: PLEASE SEE BUILDING REVIEWER COMMENT WITH
 RESPECT TO HORN/STROBE DEVICE IN BATHROOM. AS THIS WILL
 AFFECT THE ELECTRICAL PLANS PLEASE BE SURE TO INCLUDE.
 PLEASE BE SURE TO SEE 11-4.28.1,.2 AND .3(4) FOR
 MINIMUM LEVELS OF UNITS FOR ADA FOR ANY DEVICES
 INSTALLED.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT IS COMPLETE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By dpalmer Date 2008-03-19 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2008-03-19 Time 12:24 Sent To  
Notes
2008-03-19 12:24:58** DENIED**
  
  
 ICE BERRY
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES ARE
 REFLECTED ON PLANS. THERE ARE CURRENTLY CODES NOTES
 WHICH ARE NOT ADOPTED IN THE STATE OF FLORIDA. FOR
 EXAMPLE: THE PLANS NOTE *BOCA* CODE WHICH IS THE
 BUILDING OFFICIALS CODE ADMINISTRATION. THIS OFFICE HAS
 NO RECORDS OF THE BOCA CODE EVER ADOPTED IN THIS
 JURISDICTION AND EVEN AT A STATE LEVEL BEFORE 2001 UBC<
 SBCCI AND BOCA WAS ADOPTED IN SECTIONS OR SOME PLACES
 ON THE STATE LEVEL.
 PLEASE SEE THAT THE BOCA CODES WERE MERGED INTO ICC
 SEVERAL YEARS AGO. (SEE NOTE #40 ON E-0)
 PLEASE BE SURE TO REFERENCE THE FOLLOWING ON ELECTRICAL
 AND ARCHITECTURAL SHEETS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THE ABOVE ARE CORRECT ON SHEET A0.0 BUT NOT
 ALL. NONE ARE ON ELECTRICAL.
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL TITLE BLOCKS ARE
 MISSING THE REQUIRED FIRM LICENSE NUMBER WHICH IS ALSO
 KNOWN AS A CERTIFICATE OF AUTHORIZATION NUMBER.
 FAC 61G1-16.004 AND FS 481.219
  
 3) NOTE: PLEASE SEE FBC 13-101.3.2 AS THIS PROJECT
 STATES A CHANGE IN OCCUPANCY EVEN STATED ON PERMIT
 APPLICATION.
 PLEASE SEE THE SECTION GIVEN AS ALL LIGHTING EVEN IF
 EXISTING ALONG WITH LIGHTING CONTROLS SHALL MEET 13-4,
 MORE SPECIFICALLY 13-415.1.ABC.1.1, .1.1, .1.3 AND
 .1.4.
 PLEASE ALSO SEE 13-415.2 FOR LIGHTING PERFORMANCE
 LEVELS.
  
 4) NOTE: PLEASE SEE CODE SECTION NOTED FOR CIRCUITING
 OF EMERGENCY/EXIT LIGHTS IS NOT UNDER THE CURRENT CODE.
 PLEASE SEE 2005 NEC WHICH IS 700.12F.
 THIS COULD HAVE RED-LINED HOWEVER AS PLANS ARE COMING
 BACK AND THIS IS A PRIVATE PROVIDER PROJECT, PLANS MAY
 NOT BE RED-LINED OR PROVISO.
  
 5) NOTE: PLEASE KNOW AS THERE ARE SOME ITEMS NOT
 SUBMITTED OR IN DESIGN FOR REVIEW, THERE MAY VERY WELL
 BE NEW COMMENTS OF THE FOLLOWING AUDIT OF PLANS WHICH
 CAN NOT POSSIBLY BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-07-23 Cont ID  
Sent By mwennerg Date 2008-07-23 Time 14:13 Rev Time 0.00
Received By mwennerg Date 2008-07-23 Time 14:13 Sent To  
Notes
2008-07-23 14:13:42REVISION DATED 6/29/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By mawillia Date 2008-05-29 Time 15:10 Rev Time 0.00
Received By mawillia Date 2008-05-29 Time 15:02 Sent To  
Notes
2008-05-29 15:08:21*****APPROVED*****
  
  
 PLAN SHEETS A1.0 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-23 Cont ID  
Sent By mwennerg Date 2008-05-23 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2008-05-23 Time 10:54 Sent To  
Notes
2008-05-23 10:56:59***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING CITY
 PLACE MANAGEMENT APPROVAL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-30 Cont ID  
Sent By mwennerg Date 2008-04-30 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2008-04-30 Time 10:47 Sent To  
Notes
2008-04-30 10:48:24PLANS WILL BE STAMPED WHEN RETURNED FOR OTHER REVIEW
 CORRECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mawillia Date 2008-03-24 Time 11:54 Sent To  
Notes
2008-03-24 12:33:11*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.ON SHEET A0.0, MAXIMUM TRAVEL DISTANCE TO AN EXIT
 (SPRINKLERED) OF 300' IS INCORRECT.AS PER 2003 NFPA
 101 (37.2.6.1 AND/OR 36.2.6.2), TRAVEL DISTANCE (IN A
 SPRINKLERED BUILDING) SHALL NOT EXCEED 250 FEET.
  
 4.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.NO EXIT LIGHT(S) SHOWN ON PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 16:37 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 16:37 Sent To  
Notes
2008-08-04 16:45:34TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 09:10 Sent To  
Notes
2008-07-03 09:11:04TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 14:49 Rev Time 0.00
Received By shill Date 2008-05-29 Time 14:49 Sent To B
Notes
2008-05-29 15:25:135/29/8; PASSED/STAMPED BY BUILDING & FIRE
 ROUTED TO BT DESK FOR ELECTRIC REVIEW/STAMP
2008-05-29 14:49:43TO "SHILL' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 11:40 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 11:40 Sent To  
Notes
2008-04-28 11:43:08TO "COMM" BD#10--PRIVATE PROVIDER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-24 Cont ID  
Sent By mawillia Date 2008-03-24 Time 11:55 Rev Time 0.00
Received By mawillia Date 2008-03-18 Time 10:51 Sent To  
Notes
2008-03-18 10:53:30TO "COMM" BD#25

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-23 Cont ID  
Sent By tgordon Date 2008-07-23 Time 09:53 Rev Time 0.30
Received By tgordon Date 2008-07-23 Time 09:53 Sent To  
Notes
2008-07-23 10:11:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M-1
 *** DENIED ***
  
 1) REVISED MECHANICAL PLAN HAS NO CHANGES TO IT AND
 STILL ONLY SHOWS ALL EXISTING MECHANICAL CONDITIONS AND
 NO NEW OR RELOCATED MECHANICAL. THEREFORE NO NEW
 MECHANICAL WORK IS BEING DONE AND REQUIRES NO
 MECHANICAL PLAN REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-05-05 Cont ID  
Sent By tgordon Date 2008-05-05 Time 10:49 Rev Time 0.30
Received By tgordon Date 2008-05-05 Time 10:49 Sent To  
Notes
2008-05-05 10:51:54MECHANICAL PLAN M-1 SHOWS ALL MECHANICAL IS EXISTING
 AND NO NEW MECHANICAL WORK TO BE DONE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 15:33 Rev Time 0.20
Received By tgordon Date 2008-03-21 Time 15:33 Sent To  
Notes
2008-03-21 15:36:21PLANS SHOW NO MECHANICAL WORK TO BE DONE THAT WOULD
 REQUIRE A MECHANICAL PERMIT. NO MECHANICAL PERMIT
 APPLIED FOR.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-22 Cont ID  
Sent By kstevens Date 2008-07-22 Time 12:24 Rev Time 0.00
Received By kstevens Date 2008-07-22 Time 12:24 Sent To  
Notes
2008-07-22 12:25:37REVISION OK--SHT P-1

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-16 Cont ID  
Sent By kstevens Date 2008-05-16 Time 16:42 Rev Time 0.00
Received By kstevens Date 2008-05-16 Time 16:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-30 Cont ID  
Sent By kstevens Date 2008-04-30 Time 08:48 Rev Time 0.00
Received By kstevens Date 2008-04-30 Time 08:43 Sent To  
Notes
2008-04-30 08:47:53AUDIT DENIED
 REFERENCE: FLORIDA STATUTES
  
 1. THE NOTICE TO BUILDING OFFICIAL USE OF PRIVATE
 PROVIDER FORM PRIVATE PROVIDER DOES NOT REFLECT THE
 PRIVATE PROVIDER INDICATED ON THE PRIVATE PROVIDER
 BUILDING PLANS COMPLIANCE AFFIDAVIT. PLEASE CORRELATE.
 FS 533.791.
  
 2. PLANS ARE TECHNICALLY CORRECT AND HAVE BEEN STAMPED
 FOR AUDIT. AUDIT STATUS WILL CHANGE TO PASSED WHEN THE
 ABOVE ISSUE IS RESOLVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE AUDITED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By kstevens Date 2008-03-20 Time 07:26 Rev Time 0.00
Received By kstevens Date 2008-03-19 Time 18:56 Sent To  
Notes
2008-03-20 07:43:32AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1.ALL ARCHITECTURAL SHEETS ARE MISSING THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION),
 REQUIRED IN THE TITLE BLOCKS. FAC 61G1-16.004(2) & FS
 489.219, 481.2055.
  
 2. PLEASE CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE AT THE UTILITY DEPT. INDUSTRIAL
 PRE-TREATMENT TO DETERMINE IF A GREASE INTERCEPTOR IS
 REQUIRED FOR THE OCCUPANCY. MR. COMPO CAN BE REACHED BY
 PHONE (561) 644-1821, BY FAX (561) 822-2287, OR BY
 E-MAIL [email protected]. A WRITTEN DETERMINATION WILL BE
 SUBMITTED INDICATING THE REQUIREMENTS OF AN INTERCEPTOR
 OR WAIVER AS ISSUED BY MR. COMPO.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-05-18 Cont ID  
Sent By eschneid Date 2008-03-19 Time 15:32 Rev Time 0.00
Received By eschneid Date 2008-05-18 Time 12:26 Sent To  
Notes
2008-05-18 12:26:31NO EXTERIOR WORK.