Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By rmcdouga Date 2008-04-04 Time 12:19 Rev Time 0.00
Received By rmcdouga Date 2008-04-04 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By rmcdouga Date 2008-03-19 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2008-03-18 Time 16:53 Sent To  
Notes
2008-03-19 07:40:052004 FBC W/2007 REVISIONS
 REPLACE 5 WINDOWS
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE LOCATION
 AND SIZE OF THE WINDOWS. IDENTIFY THE SLEEPING ROOMS ON
 THE PLANS. FBC 106.1.1* CITY AMENDMENTS
  
 2) IF THE SLEEPING ROOM WINDOWS ARE REPLACED THEY CAN
 NOT REDUCE THE CLEAR OPENING BY MORE THAN 5 PERCENT AND
 CAN NOT MAKE THE EGRESS OPENING LESS SAFE THAN THE
 EXISTING CONDITIONS. FBC EXISTING BUILDINGS SECTIONS
 501.2 AND 505.1.
  
 3) THE FBC EXISTING BUILDING SECTION 507.3 REQUIRES
 OPENING PROTECTION FOR REPLACED WINDOWS, WHEN MORE THAN
 25 PERCENT OF THE GLAZED AREA IN THE DWELLING IS
 REPLACED. SUBMIT PROOF THAT THE GLAZED AREA BEING
 REPLACED IS LESS THAN 25 PERCENT OR SUBMIT 2 COPIES OF
 PRODUCT APPROVALS FOR THE STORM PANELS.
  
 4) IN ADDITION TO THE PRODUCT APPROVALS FOR THE STORM
 PANELS, SUBMIT 2 COPIES OF A KEY PLAN AND AN
 INSTALLATION SCHEDULE FOR THE STORM PANELS. SPECIFY THE
 MOUNT TYPE, FASTENER TYPE AND SPACING, EDGE DISTANCES,
 SPANS, ETC. SEE THE ATTACHED SAMPLE FORM. FBC 106.1.2*
 CITY AMENDMENTS
  
 5) PART OF THE PRODUCT APPROVAL DRAWINGS THAT WERE
 SUBMITTED FOR THE WINDOWS HAS BEEN CUT OFF. SUBMIT THE
 COMPLETE DRAWINGS. DCA RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]