Plan Review Details - Permit 08030346
Plan Review Stops For Permit 08030346
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2008-11-14 Cont ID  
Sent By mjacobs Date 2008-11-14 Time 14:50 Rev Time 0.00
Received By mjacobs Date 2008-11-14 Time 14:50 Sent To  
Notes
2008-11-14 14:51:19PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-12 Cont ID  
Sent By mjacobs Date 2008-11-12 Time 11:50 Rev Time 0.00
Received By mjacobs Date 2008-11-12 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-10-22 Cont ID  
Sent By mjacobs Date 2008-10-22 Time 11:50 Rev Time 0.00
Received By mjacobs Date 2008-10-22 Time 11:10 Sent To  
Notes
2008-10-22 11:50:432ND REVIEW
 BUILDING PLAN REVIEW
 PERMIT: 08030346
 ADD: 848 SOUTHERN BLVD.
 CONT: PLAN REVIEW
 TEL: (561)201-4278
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 NOTE: THE STATUS OF THIS APPLICATION WILL REMAIN IN THE
 FAIL CATEGORY UNTIL A CERTIFIED GENERAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
 1) OK
  
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
  
 4) OK
 5) OK.
 6) OK.
 NEW: OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-21 Cont ID  
Sent By mjacobs Date 2008-08-21 Time 12:07 Rev Time 0.00
Received By mjacobs Date 2008-08-21 Time 10:03 Sent To  
Notes
2008-08-21 12:07:24 
 2ND REVIEW
 BUILDING PLAN REVIEW
 PERMIT: 08030346
 ADD: 848 SOUTHERN BLVD.
 CONT: PLAN REVIEW
 TEL: (561)201-4278
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 NOTE: THE STATUS OF THIS APPLICATION WILL REMAIN IN THE
 FAIL CATEGORY UNTIL A CERTIFIED GENERAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
 1) OK
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **NOT ADDRESSED**
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 **NOT ADDRESSED**
 4) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 5) NOTED: WALLS ARE EXISTING.
  
 6) NO SPRINKLER SYSTEM.
  
 NEW: PLEASE PROVIDE THE LIFE SAFETY PLAN SHOWING THE
 MEANS OF EGRESS, EXIT ACCESS, EXIT AND EXIT DISCHARGE.
 106.3.5.1.1(7)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By mjacobs Date 2008-03-24 Time 14:26 Rev Time 0.00
Received By mjacobs Date 2008-03-24 Time 10:31 Sent To  
Notes
2008-03-24 13:58:00BUILDING PLAN REVIEW
 PERMIT: 08030346
 ADD: 848 SOUTHERN BLVD.
 CONT: PLAN REVIEW
 TEL: (561)201-4278
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 NOTE: THE STATUS OF THIS APPLICATION WILL REMAIN IN THE
 FAIL CATEGORY UNTIL A CERTIFIED GENERAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 5)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ALL CHANGES TO THE EXISTING SPACE. SUBMIT A
 WALL LEGEND ON THE DRAWINGS SHOWING THE EXISTING WALLS
 AND THE NEW WALLS. STATE THE MATERIALS WHICH WILL BE
 USED TO CONSTRUCT THE NEW WALLS.
 6)IF THERE IS A FIRE SPRINKLER SYSTEM IN THE SPACE,
 PROVIDE A SPRINKLER PLAN SHOWING HOW THE NEW RENOVATION
 WILL AFFECT THE LAYOUT OF THE SPRINKLER HEADS. FBC
 106.3.5.1.1(5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-11-14 Cont ID  
Sent By btrobaug Date 2008-11-14 Time 09:23 Rev Time 0.00
Received By btrobaug Date 2008-11-14 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 16:19 Sent To  
Notes
2008-10-23 16:21:32 
  
 THE STATUS OF THE PERMIT WILL CHANGE TO PASS WHEN A
 CONTRACTOR IS SIGNED ON.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-22 Cont ID  
Sent By btrobaug Date 2008-08-22 Time 09:43 Rev Time 0.00
Received By btrobaug Date 2008-08-22 Time 09:26 Sent To PC
Notes
2008-08-22 09:37:00 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE SAME COMMENTS FROM THE PREVIOUS REVIEW. SHEET #2 OF
 THE INPUT DATA REPORT ONLY GIVES WATTAGE OF THE
 FIXTURES, NO ALLOWABLE WATTAGES OR COMPARISON
 INDICATING COMPLIANCE.THIS CAN BE ILLUSTRATED ON THE
 PLAN, SHEET E2.
  
 1} 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 PROVIDE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By btrobaug Date 2008-03-19 Time 16:48 Rev Time 0.00
Received By btrobaug Date 2008-03-19 Time 16:12 Sent To  
Notes
2008-03-19 16:48:20 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 PROVIDE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-11-14 Cont ID  
Sent By mawillia Date 2008-11-14 Time 13:11 Rev Time 0.00
Received By mawillia Date 2008-11-14 Time 13:01 Sent To  
Notes
2008-11-14 13:08:29*****APPROVED*****
  
 PLAN SHEETS A4 AND E2 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-10-27 Cont ID  
Sent By mawillia Date 2008-10-27 Time 12:42 Rev Time 0.00
Received By mawillia Date 2008-10-27 Time 12:35 Sent To  
Notes
2008-10-27 12:41:01*****PROVISO******
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEWS HAVE BEEN
 ADDRESSED; NOTE: THE FIRE PLAN REVIEW SHALL REMAIN IN A
 "F" STATUS UNTIL A CERTIFIED GENERAL CONTRACTOR IS
 SIGNED ON THE APPLICATION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-08-18 Cont ID  
Sent By mawillia Date 2008-08-18 Time 11:43 Rev Time 0.00
Received By mawillia Date 2008-08-18 Time 10:29 Sent To  
Notes
2008-08-18 11:41:47*****PROVISO******
  
 *AMEND/CORRECT THE FOLLOWING ITEMS: ON SHEET AA1 UNDER
 CODE REVIEW NOTE 1 (#6 - OTHER CODES), (A.) CHANGE FROM
 2005 TO 2004 FLORIDA FIRE PREVENTION CODE AND (B.)
 AMEND WORDING TO REFLECT 2003 NFPA 101 - LIFE SAFETY
 CODE.
 ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED;
  
 NOTE: THE FIRE PLAN REVIEW SHALL REMAIN IN A "F" STATUS
 UNTIL A CERTIFIED GENERAL CONTRACTOR IS SIGNED ON THE
 APPLICATION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 21:59 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 20:15 Sent To  
Notes
2008-03-25 21:58:30*****DENIED******
  
  
 1.THE ADDRESS, INCLUDING THE SUITE NUMBER, OF THE
 SCOPE OF WORK SITE SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.VERIFYFLAME SPREADS ON THE PRODUCT RATINGS ON
 INTERIOR FINISHES CHART (SHEET AA1) FOR THE LAY-IN
 CEILING, POLOMYX PAINT, AND THE HALLWAY WAINSCOT
 PANELS.INTERIOR WALL AND CEILING FINISH (CLASS A,
 CLASS B, CLASS C.)INTERIOR FLOOR FINISH (CLASS I OR
 CLASS II).
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE.
  
 7.ON SHEET A5, ONCE A PERSON PASSES THROUGH THE REAR
 EXIT, WHERE DOES ONE GO TO EXIT THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 14:37 Sent To  
Notes
2008-11-07 14:40:03TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 10:56 Sent To  
Notes
2008-10-17 10:59:26TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 09:34 Rev Time 0.00
Received By adarroug Date 2008-08-05 Time 09:34 Sent To  
Notes
2008-08-12 13:33:49TO "BOB"#1
2008-08-05 09:34:20WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 22:02 Rev Time 0.00
Received By mawillia Date 2008-03-17 Time 11:29 Sent To  
Notes
2008-03-17 11:36:55TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-17 Cont ID  
Sent By tgordon Date 2008-03-17 Time 15:39 Rev Time 0.25
Received By tgordon Date 2008-03-17 Time 15:39 Sent To  
Notes
2008-03-17 15:40:04NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-08-13 Cont ID  
Sent By mperson Date 2008-08-13 Time 13:18 Rev Time 0.00
Received By mperson Date 2008-08-13 Time 13:18 Sent To  
Notes
2008-08-13 13:22:42NOTE: THERE IS NO PLUMBING WORK BEING INDICATED ON
 PLANS OR PLUMBING PERMIT BEING APPLIED FOR. PLUMBING
 SYSTEMS ARE BEING INDICATED AS EXISTING. ALL PLUMBING
 WORK IS BEING DONE UNDER PERMIT #08070695.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By jleech Date 2008-03-19 Time 10:43 Rev Time 0.00
Received By jleech Date 2008-03-19 Time 10:34 Sent To  
Notes
2008-03-19 10:55:08DENIED;
 EXTENT OF PLUMBING WORK TO BE DONE IS NOT CLEAR;
 SHOW EXISTING SPACE (BEFORE
 ALTERATIONS) ARE PLUMBING FIXTURES EXISTING, OR
 LOCATIONS CHANGED? IF NOT ADD NOTE, ( FIXTURE CHANGE
 OUT ONLY). IF LOCATION OF FIXTURES ARE CHANGED OR A
 FIXTURE IS ADDED PLEASE PROVIDE WATER AND SANITARY
 RISER DIAGRAMS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-03-19 Cont ID  
Sent By choops Date 2008-03-19 Time 14:02 Rev Time 0.00
Received By choops Date 2008-03-19 Time 14:02 Sent To  
Notes
2008-03-19 14:04:54ZONING REVIEW MAY OR MAY NOT BE REQUIRED.AS THERE IS
 NO DECLARED VALUE ON THE MAJOR WORKING DRAWING, ZONING
 REQUIREMENT CANNOT BE DETERMINED AT THIS TIME.IF THE
 DECLARED VALUE OF THE WORK EXCEEDS 50% OF THE
 STRUCTURE'S VALUE, LANDSCAPING WILL NEED TO BE BROUGHT
 TO COMPLIANCE WITH THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS.