Plan Review Details - Permit 08030326
Plan Review Stops For Permit 08030326
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-15 Cont ID  
Sent By rmcdouga Date 2008-04-15 Time 07:17 Rev Time 0.00
Received By rmcdouga Date 2008-04-15 Time 07:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By rmcdouga Date 2008-03-17 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2008-03-17 Time 12:51 Sent To  
Notes
2008-03-17 14:13:532004 FBC W/2007 REVISIONS
 REPLACE WINDOWS AND DOORS
  
 DENIED BY BUILDING
  
 1) THE VALUE OF THE WORK APPEARS TO BE TOO LOW. THE
 VALUE OF THE WORK IS TO INCLUDE THE COST OF THE
 MATERIALS PLUS THE COST OF THE LABOR BASED ON WHAT
 CONTRACTORS CHARGE FOR THE WORK. REVISE THE VALUE.
  
 2) PROVIDE 2 COPIES OF FLOOR PLANS INDICTING THE ROOMS
 THAT THE WINDOWS ARE LOCATED IN. WINDOWS IN SLEEPING
 ROOMS ARE REQUIRED TO COMPLY WITH EGRESS REQUIREMENTS
 AND CAN NOT BE MADE ANY LESS SAFE. 2004 FBC EXISTING
 BUILDING SECTION 505.1.
  
 3) THE PLANS APPEAR TO SHOW TWO DIFFERENT BUILDINGS.
 PLEASE IDENTIFY THE BUILDINGS ON THE PLANS. FBC
 106.1.1* CITY AMENDMENTS.
  
 4) THE DRAWINGS STATE BLOCK WINDOWS AT 2 LOCATIONS. ARE
 THESE 2 WINDOWS THAT ARE BEING ENCLOSED? PLEASE
 CLARIFY. SUBMIT DRAWINGS INDICATING HOW THE OPENINGS
 WILL BE ENCLOSED. PROVIDE DETAILS INDICATING EXISTING
 WALL CONSTRUCTION AND INFILL MATERIALS AND ATTACHMENTS.
 FBC 106.1.1* CITY AMENDMENTS.
  
 5) THE 53 X 50-5/8" WINDOW APPEARS TO BE 2 WINDOWS WITH
 A STRUCTURAL MULLION BETWEEN THEM. SUBMIT 2 COPIES OF
 PRODUCT APPROVALS FOR THE MULLION AS REQUIRED BY DCA
 RULE 9B-72.
  
 6) THE DRAWINGS SPECIFY A 6' ALUMINUM DOOR. SPECIFY THE
 DOOR TYPE ON THE PLANS. IS THIS A SLIDING GLASS DOOR,
 DOUBLE FRENCH DOOR OR SOMETHING ELSE?SUBMIT PRODUCT
 APPROVALS FOR THIS DOOR AS REQUIRED BY FAC RULE 9B-72.
  
 7) SPECIFY THE SWING OF THE DOORS ( INSWING OR OUTSWING
 )ON THE PLANS. AND SUBMIT PRODUCT APPROVALS FOR THE
 APPROPRIATE SWING. FAC RULE 9B-72.
  
 8) SUBMIT 2 COPIES OF ALL PRODUCT APPROVALS. FBC 106.1*
 CITY AMENDMENTS
  
 9) SUBMIT TWO (2) LEGIBLE COPIES OF THE UPDATED NOA FOR
 THE STORM PANELS WITH NOA # 05-0926.02. SUBMIT TWO
 COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, FASTENER TYPE AND
 SPACING, EDGE DISTANCE, SPANS, ETC. SEE ATTACHED SAMPLE
 SCHEDULE. FBC 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-17 Cont ID  
Sent By rmcdouga Date 2008-03-17 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2008-03-14 Time 15:21 Sent To  
Notes
***NONE***