| 2008-03-19 12:12:58 | BUILDING PLAN REVIEW |
| | PERMIT: 08030311 |
| | ADD: 226 CLEMATIS ST. |
| | CONT: R.A. HEATH CONST.INC. |
| | TEL: (770)271-8229 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)ALL THE SHEETS INDICATE EXISTING STORE DESIGN. IF |
| | THERE ARE CHANGES TO THE EXISTING STORE PLEASE INDICATE |
| | CLEARLY ON PROPOSED PLANS WHERE THE CHANGES ARE MADE. |
| | CONSTRUCTION DOCUMENTS SHALL BE ?DIMENSIONED? AND OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. FBC. 106.1.1 |
| | |
| | 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 5)SHEET G1.0 MAKES REFERENCE TO THE 2006 |
| | ACCESSIBILITY CODE, THIS IS INCORRECT, AND WE ARE |
| | PRESENTLY UNDER THE 2004 ACCESSIBILITY CODE VERSION. |
| | |
| | 6)PLEASE INDICATE IF THERE IS A FIRE SPRINKLER SYSTEM |
| | INSTALLED AT THIS BUILDING. IF A SPRINKLER SYSTEM IS |
| | INSTALLED, PROVIDE A SPRINKLER PLAN SHOW THE PLACEMENT |
| | OF THE SPRINKLER HEADS IN RELATION TO THE RENOVATION |
| | WALLS. FBC* 106.3.5.1.1(5) |
| | |
| | 7)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 8)A PORTION OF THE MAIN COUNTER SHALL BE 36 INCHES |
| | MINIMUM IN LENGTH AND SHALL BE A MAXIMUM OF 36 INCHES |
| | IN HEIGHT. FBC 11-7 THE ELEVATION DRAWINGS DO NOT SHOW |
| | THE DIMENSIONS OF THE NEW COUNTERS. |
| | |
| | 9)FBC 11-4.32.1 FIXED OR BUILT-IN SEATING OR TABLES |
| | REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 SHALL |
| | COMPLY WITH SECTION 11-4.32. SHOW COMPLIANCE. (SEE |
| | FIGURE 45)THE EXTERIOR SEATING SHALL HAVE A CLEAR |
| | PATH OF 44? FOR PEDESTRIANS. |
| | |
| | 10)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES VALUE SHALL INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, INTERIOR FINISH, |
| | ORCHESTRAL AND DESIGN FEES MARKETING COST AND OVER HEAD |
| | AND PROFIT EXCLUDING LAND. WPB AMENDMENTS 108.3* |
| | |
| | NOTE: PLEASE SHOW ON SEPARATE DRAWINGS AN EXISTING PLAN |
| | AND A PROPOSED PLAN. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |