Plan Review Details - Permit 08030275
Plan Review Stops For Permit 08030275
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-28 Cont ID  
Sent By mwennerg Date 2008-08-20 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2008-08-20 Time 10:27 Sent To  
Notes
2008-08-20 10:33:58INCOMPLETE REVIEW PENDING
  
 RECEIVED SUBMITTAL RESUMING REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 10:43 Rev Time 0.00
Received By mwennerg Date 2008-04-18 Time 10:43 Sent To  
Notes
2008-04-18 10:48:38***DENIED***
  
 PLANS APPEAR TO BE CODE COMPLIANT. PLEASE RESPOND TO
 THE FOLLOWING:
  
 1) THE FLOW TEST DATA IS DATED 7/13/06. IF A MORE
 RECENT TEST WAS PERFORMED, PLEASE PROVIDE THAT
 INFORMATION AS REFERENCED TEST IS GREATER THAN 1 YEAR
 FROM FIRE SPRINKLER SUBMITTAL.
  
 2) FIRE HYDRANT TO BE LOCATED AT A DISTANCE NOT GREATER
 THAN 150' FROM THE FIRE DEPARTMENT CONNECTION. PLEASE
 ILLUSTRATE ON SITE PLAN AND SHOW THE DISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 09:10 Sent To FIRE
Notes
2008-07-31 09:11:18TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 10:53 Rev Time 0.00
Received By mwennerg Date 2008-03-13 Time 11:58 Sent To  
Notes
2008-03-13 11:58:28FIRE BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved