Plan Review Details - Permit 08030270
Plan Review Stops For Permit 08030270
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-25 Cont ID  
Sent By rmcdouga Date 2008-09-25 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2008-09-25 Time 15:28 Sent To  
Notes
2008-09-25 15:30:21REVISION TO INCREASE THE SCOPE OF WORK IS OK. ADDED A
 NEW SHEET S-3 TO DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2008-08-20 Cont ID  
Sent By rmcdouga Date 2008-08-20 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2008-08-20 Time 16:41 Sent To  
Notes
2008-08-20 15:43:112004 FBC W/2007 REVISIONS
  
 REVISION IS DENIED
  
 1) THIS IS A REVISION TO THE PLANS AND CHANGES TO SCOPE
 OF WORK. A REVISION FEE IS DUE. FBC 108.1* CITY
 AMENDMENTS
  
 2) THE ADDITION TO THE SCOPE OF WORK REQUIRES THAT THE
 VALUE OF THE WORK IS INCREASED TO INCLUDE THE
 ADDITIONAL WORK. PLEASE INDICATE THE VALUE OF THE
 ADDITIONAL WORK. THE VALUATION IS TO INCLUDE THE LABOR,
 MATERIAL, DESIGN FEES, DEBRIS REMOVAL, OVERHEAD AND
 PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. FBC 108.3*
 CITY AMENDMENTS.
  
 2) HANDWRITTEN NOTES ARE NOT ALLOWED ON SIGNED AND
 SEALED DRAWINGS. CHANGES TO SIGNED AND SEALED PLANS CAN
 ONLY BE MADE BY THE DESIGNER OF RECORD. FS 481
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By rmcdouga Date 2008-04-08 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2008-04-07 Time 16:04 Sent To  
Notes
2008-04-07 16:09:36BUILDING PROVISO
  
 THE NEW 2 X 8 EXTERIOR WOOD FRAME AND STUCCO WALL AT
 GARAGE IS REQUIRED TO COMPLY WITH R319.1 AND R704, FOR
 PROTECTION AGAINST DECAY AND INSPECTION FOR TERMITES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-03-14 Cont ID  
Sent By rmcdouga Date 2008-03-14 Time 13:16 Rev Time 0.00
Received By rmcdouga Date 2008-03-14 Time 13:16 Sent To E
Notes
2008-03-14 13:34:31BUILDING PROVISO
  
 THE NEW 2 X 8 EXTERIOR WOOD FRAME AND STUCCO WALL AT
 GARAGE IS REQUIRED TO COMPLY WITH R319.1 AND R704, FOR
 PROTECTION AGAINST DECAY AND INSPECTION FOR TERMITES.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2008-03-28 Cont ID  
Sent By btrobaug Date 2008-03-28 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2008-03-28 Time 16:24 Sent To P
Notes
2008-03-28 16:28:27 
 ELECTRICAL PERMIT NUMBER #08020238 ISSUED FOR THIS
 PROJECT./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By btrobaug Date 2008-03-17 Time 15:48 Rev Time 0.00
Received By btrobaug Date 2008-03-17 Time 15:16 Sent To P
Notes
2008-03-17 15:27:44 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. SUBMIT
 PLANS FOR ALL ELECTRICAL WORK, MOVING THE PANEL,
 PROVIDE A RISER DIGRAM INDICATING THE RATING OF THE
 PANEL AND FEEDER SIZES.
  
 2} SHOW THE LOCATION OF THE RELOCATED A/C EQUIPMENT ON
 THE PLAN. ALSO SHOW COMPLIANCE WITH THE REQUIRED
 DISCONNECT PER 440.14,RECEPTACLE PER 210.63.
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.LOCATE ON
 PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-03-12 Cont ID  
Sent By swurafti Date 2008-03-12 Time 16:18 Rev Time 0.00
Received By swurafti Date 2008-03-12 Time 16:18 Sent To  
Notes
2008-03-12 16:18:52HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 09:17 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 09:17 Sent To B
Notes
2008-09-23 09:18:08TO "RMDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 13:44 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 13:44 Sent To B
Notes
2008-08-20 13:45:13TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 13:44 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 13:44 Sent To E
Notes
2008-03-28 13:45:15TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-18 Cont ID  
Sent By mperson Date 2008-03-18 Time 10:10 Rev Time 0.00
Received By mperson Date 2008-03-13 Time 08:55 Sent To  
Notes
2008-03-13 08:58:42TO ""MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-17 Cont ID  
Sent By tgordon Date 2008-03-17 Time 10:52 Rev Time 0.25
Received By tgordon Date 2008-03-17 Time 10:52 Sent To E
Notes
2008-03-17 10:54:23NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
 ** A MECHANICAL PERMIT WILL BE REQUIRED WHEN RELOCATING
 A/C CONDENSER UNIT. **

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-02 Cont ID  
Sent By mperson Date 2008-04-02 Time 11:40 Rev Time 0.00
Received By mperson Date 2008-04-02 Time 11:40 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By mperson Date 2008-03-18 Time 09:37 Rev Time 0.00
Received By mperson Date 2008-03-18 Time 09:37 Sent To PC
Notes
2008-03-18 10:10:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 IS INDICATING A NEW PREP SINK IN KITCHEN,
 NEW WATER HEATER AND NEW WASHER. PLEASE KNOW THAT A
 PLUMBING PERMIT IS REQUIRED FOR THE PROPOSED WORK.
 PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 105.1
 PERMIT REQUIRED. ANY OWNER, AUTHORIZED AGENT, OR
 CONTRACTOR WHO INTENDS TO ERECT, INSTALL, ENLARGE,
 ALTER, REPAIR, REMOVE, CONVERT OR REPLACE ANY GAS OR
 PLUMBING SYSTEM, THE INSTALLATION OF WHICH IS REGULATED
 BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE DONE,
 SHALL FIRST MAKE APPLICATION TO THE BUILDING OFFICIAL
 AND OPTAIN A PERMIT.
  
 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS FOR THE PROPOSED PREP SINK AND WASHER.
  
 **THE FOLLOWING ARE REQUIREMENTS FOR THE WASHING
 MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **THE CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 3. SHEET A-1 IS INDICATING A NEW WASHER, DRYER, AND
 WATER HEATER TO BE INSTALLED IN AN EXISTING GARAGE.
 PLEASE INDICATE HOW THESE APPLIANCES WILL BE PROTECTED
 FROM DAMAGE BY APPROVED BARRIERS. PER FBC MECHANICAL
 SECTION 303.4 PROTECTION FROM DAMAGE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]