| 2008-04-10 13:38:53 | BUILDING PLAN REVIEW |
| | PERMIT: 08030236 |
| | ADD: 928 28TH ST |
| | CONT: TIM GIVINS BUILDING |
| | TEL: (561) 533-5828 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| | PLEASE PROVIDE ON YOUR PLANS |
| | THE 2007 SUPPLEMENTS. |
| | |
| | 2) PLEASE CORRECT, THE PERMIT APPLICATION INDICATES BY |
| | ADDRESS AND PCN THIS WORK WILL BE COMPLETED ON LOT 14 |
| | WHERE AS THE PLANS INDICATE LOT 10. SEE ALSO AREAL |
| | VIEWS INDICATE A STRUCTURE ON LOT 14 AND NO DEMO |
| | PERMITS. PLEASE MAKE CORRECTION ON THE PERMIT |
| | APPLICATION FOR THE ADDRESS AND LCORRECT PROPERTY |
| | CONTROLNUMBER. CONTACT LILY AT ADDRESSING FOR THE NEW |
| | ADDRESS FOR LOT# 10 |
| | AT 822-1239. |
| | |
| | 3)LANDSCAPE ARCHITECT MORIKOMI IS MISSING THEIR |
| | CERTIFICATE OF AUTHORIZATION.481.219 F.S. CERTIFICATE |
| | OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET |
| | BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER A |
| | FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| | OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO |
| | EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 4)1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 6) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 7) SHEET A-1 PLEASEPROVIDE THE CODE INFORMATION |
| | DESIGNED TOO! SEE 1E. |
| | |
| | 8) SHEET A-1 CORRECT THE BUILDING TYPE, PLANS INDICATE |
| | A TYPE IV WHICH IS HEAVY TIMBER PLEASE SEE TABLE 503 |
| | AND 602.4. |
| | |
| | NOTE FOR THIS BUILDING REVIEW THIS BUILDING WILL BE |
| | REVIEWED TO THE MINIMUM BUILDING TYPE: |
| | 2004 FBC W/ 2007 SUPPLEMENTS |
| | BUILDING TYPE: V-BF-1MAX OF 8,500 SQ FT. |
| | |
| | 9) THE PLANS INDICATE THE BACK WALL WILL BE LOCATED 7.5 |
| | FT. FROM THE PROPERTY LINE REQUIRING A 1 HR FIRE |
| | RATING, PLEASE PROVIDE HOW THIS SHALL BE ACCOMPLISHED. |
| | SEE TABLE 602. |
| | |
| | 10) SHEET A-1 IN F OCCUPANCIES COMMON PATH OF TRAVEL IS |
| | LIMITED TO 50'. THE END UNITS 1 & 4 APPEAR TO BE OVER |
| | BY A PROXXIMATELY 2'-0". PLEASE SEE 1013.3 EXCEPTION# |
| | 4. |
| | |
| | 11)SHEET A-1 THE END UNITS 1 & 4 BOTH REQUIRING 2 |
| | EXITS WILL ALSO NEED TO MAKE THE REAR EXIT COMPLY WITH |
| | 11-4.1.3(8)(A)(II)ACCESSIBLE ENTRANCES MUST BE |
| | PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO THE NUMBER |
| | OF EXITS REQUIRED BY THE APPLICABLE BUILDING/ FIRE |
| | CODES.THE REAR EXITS WILL NEED TO BE ACCESSIBLE NO |
| | DROPPED WALKWAY AND ACCESSIBLE TO THE PUBLIC WAY. (9) |
| | IN BUILDINGS OR FACILITIES, OR PORTIONS OF BUILDINGS OR |
| | FACILITIES, REQUIRED TO BE ACCESSIBLE, ACCESSIBLE MEANS |
| | OF EGRESS SHALL BE PROVIDED IN THE SAME NUMBER AS |
| | REQUIRED FOR EXITS BY LOCAL BUILDING/ FIRE SAFETY |
| | REGULATIONS. |
| | |
| | 12) THE TWO INTERIOR UNITS THAT DO NOT HAVE ACCESSIBLE |
| | EXITS WILL INDICATE AS SUCH: 11-4.30.7. |
| | |
| | 13) SHEET A-3 WALL SECTION- C, INDICATE ONE-HOUR RATED |
| | GYPSUM STEEL STUD WALL 3 1/2 INCH STUD @ 12" ON CENTER. |
| | PLEASE SEE TABLE 2508.1 EITHER GA-216 OR ASTM C 754 FOR |
| | NON-LOAD BEARING WALLS ,FOR STUD LIMITATIONS AND FOR |
| | MINIMUM LATERAL LOADING OF 5 LPSF.THE LIMITATION OF |
| | 22'-6". THE WALL AT THE CENTER OF THE BUILDING IS |
| | APPROXIMATELY 26'-0" TALL THE EAVES 22'-0" TALL. |
| | |
| | 14) PLEASE ALSO PROVIDE INFORMATION FOR A 1 HOUR FIRE |
| | RESISTANT FLEXIBLE SEALENT TO THE ROOF DECK. 708.4./ |
| | 713.1. |
| | |
| | 15) SHEET A-1 DOES NOT INDICATE ANY EXIT SIGNS SHOW |
| | COMPLIANCE WITH 1006.3.1. |
| | |
| | 16) SHEET A-3 INDICATES THE STEEL FRAME IS A PRE-FAB BY |
| | OTHERS, THERE IS NO ENGINEERED INFORMATION NOR PLANS |
| | SUBMITED WITH THIS PACKAGE. 1609..1.1 AND 1609.1.3. |
| | |
| | 17)SHEET A-3 INDICATES EAVE TRIM BUT NO GUTTERS. |
| | 1503.3.6 PROTECTION AGAINST DECAY & TERMITES. |
| | CONDENSATE LINES & ROOF DOWN SPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| | UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS. |
| | |
| | 18)MISSING WIND INFORMATION FOR DESIGN: |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WTIH SECTION1609.5. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 19) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 20)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | A) EXTERIOR DOORS WITH GLAZED OPENINGS |
| | B) EXTERIOR HOLLOW MEETAL DOORS |
| | C) OVERHEAD OR COIL DOORS |
| | D) SIDING |
| | E) ROOFING ASSEMBLIES. |
| | |
| | 21) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 22) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 23) NOTE CANVAS AWNINGS SHALL EQUIRE A SEPERATE |
| | PERMIT. |
| | |
| | 24) PLEASE SEE CALCULATED VALUE OF PROJECT 4600 SQ FT X |
| | 55.46= $ 255,116.00 ADDITIONAL FEES DUE. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3*BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 25)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |