Plan Review Details - Permit 08030216
Plan Review Stops For Permit 08030216
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-12-22 Cont ID  
Sent By jgomez Date 2008-12-22 Time 10:40 Rev Time 0.00
Received By jgomez Date 2008-12-22 Time 10:30 Sent To PC
Notes
2008-12-22 10:41:24BATHROOM WINDOW REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status   Date 2008-10-31 Cont ID  
Sent By jgomez Date 2008-10-31 Time 14:10 Rev Time 0.00
Received By jgomez Date 2008-10-31 Time 14:10 Sent To PC
Notes
2008-10-31 14:14:481- REMAINDER: PROVIDE INFORMATION REQUESTED ON PROVISO
 DATED 5-06-08 AS SOON AS POSSIBLE TO AVOID ANY
 CONFLICTS OR DELAYS IN THE CONSTRUCTION. SEE ATTACHED
 COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-07-29 Cont ID  
Sent By jgomez Date 2008-07-29 Time 14:50 Rev Time 0.00
Received By jgomez Date 2008-07-29 Time 14:50 Sent To PC
Notes
2008-07-29 14:59:47TRUSS PACKAGE CHECKLIST:
  
 1- TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OFRECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 2- SOME TRUSSES ARE DESIGNED FOR EXPOSURE "B".
 PROPERTY IS LOCATED ON EXPOSURE "C".REVISE AS
 REQUIRED SHOWING ALL TRUSSES TO BE DESIGNED FOR
 EXPOSURE "C".
  
 3- COVER/INDEX PAGE DOESN'T COMPLY WITH FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-31.003.MISSINGTHE
 NAME OF THE DESIGNER OF RECORD AND THE SHEETS ARE NOT
 PROPERLY NUMBERED TO MATCHINDEX SHEET.
  
 4- ALL GENERAL DETAILS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER AS REQUIRED BY CHAPTER471FLORIDA
 STATUTE.
  
  
 *** REMAINDER:PLEASE PROVIDE INFORMATION REQUESTED ON
 PROVISO DATED 05/06/08 TO AVOID CONFLICTS OR DELAYS.
 SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-06 Cont ID  
Sent By jgomez Date 2008-06-06 Time 10:46 Rev Time 0.00
Received By jgomez Date 2008-06-06 Time 10:46 Sent To  
Notes
2008-06-06 10:47:15NO IMPACT FEES ASSESSED BY PALM BEACH COUNTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-06 Cont ID  
Sent By jgomez Date 2008-05-06 Time 16:31 Rev Time 0.00
Received By jgomez Date 2008-05-06 Time 16:29 Sent To PC
Notes
2008-05-06 16:49:11BUILDING REVIEW APPROVED WITH PROVISO.
  
 1- RESUBMIT PRODUCT APPROVALFOR:
 A) PRECAST LINTELS.NOA 03-0605.04SUBMITTED IS
 FOR 4",6" & 12" LINTELS. NEED PRODUCT APPROVAL FOR 8"
 LINTELS.
 B) GARAGE SWING DOOR. NOA 02-1211.11 SUBMITTED
 EXPIRED ON FEBRUARY 11, 2008. NEED CURRENT ONE.
 2- ARCHITECT TO REVIEW AND APPROVED ALL RE-SUBMITTED
 PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC
 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-30 Cont ID  
Sent By jgomez Date 2008-04-30 Time 16:22 Rev Time 0.00
Received By jgomez Date 2008-04-30 Time 16:22 Sent To PC
Notes
2008-04-30 16:58:45BUILDING REVIEW .
  
 1- ENERGY CALCULATIONS:
 A) REVISE WALL INSULATION TO MATCH PLANS. SEE SHEET
 A-3.
 B) REVISE RAISED WOOD FLOOR INSULATION TO MATCH
 PLANS. SEE SHEET A-3.
 C) REVISE RAISED WOOD FLOOR AREA. SEE PLANS FOR
 CORRECT AREA.
 D) REVISE ITEM 10. THIS IS A SINGLE ASSEMBLYNOT
 UNDER ATTIC AREA. SEE PLANS.
 E) REVISE OPENING AREA SHOWN ON SHEET #2 TO MATCH
 PLANS.
  
 2- RESUBMIT PRODUCT APPROVALFOR:
 A) PRECAST LINTELS.NOA 03-0605.04SUBMITTED IS
 FOR 4",6" & 12" LINTELS. NEED PRODUCT APPROVAL FOR 8"
 LINTELS.
 B) FLAT ROOF.NOA 07-0111.03 IS OK, BUT RAS 117
 CALCULATIONS NEED TO BE REVISED. SEE ATTACHED
 CALCULATIONS. REVISE CALCULATIONS AND RE-SUBMIT PRODUCT
 APPROVAL.
 C) GARAGE SWING DOOR. NOA 02-1211.11 SUBMITTED
 EXPIRED ON FEBRUARY 11, 2008. NEED CURRENT ONE.
  
 3- ARCHITECT TO REVIEW AND APPROVED ALL RE-SUBMITTED
 PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC
 2004.
  
 4- CONTRACTOR TO FOLLOW GEO-TECHNICAL ENGINEER
 RECOMMENDATIONS TO SUPPORT NEW COLUMNS. SEE SOIL TEST
 REPORT SUBMITTED.
  
 5- MINIMUM CEILING FAN SIZE REQUIRED IS 56" AS REQUIRED
 BY TABLE 13-607.1.A.1 FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By jleech Date 2008-04-28 Time 08:49 Rev Time 0.00
Received By jgomez Date 2008-03-17 Time 13:45 Sent To PC
Notes
2008-03-17 14:13:05RESIDENTIAL ADDITION, BUILDING REVIEW CHECKLIST. REVIEW
 UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH A FLOOD
 ELEVATION OF 7.0'. ELEVATION CERTIFICATE (7.5' MIN.
 ELEVATION) WILL BE REQUIRED PRIOR TO C.O. TO SHOW
 ELEVATION OF ALL EQUIPMENT.
  
 4- SPECIFY LOCATION AND SIZE OF ROOF CROSS VENTILATION
 AS REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- BRING ALL REVISED DRAWINGS FOR HITORIC APPROVAL
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- CLARIFY WHY LOADING A 2X6 WOOD FRAMED WALL ON AN
 EXISTING 2X4 WOOD FRAMED WALL. PROVIDE ENGINEERING
 CALCULATIONS SHOWING THAT EXISTING 2X4 WALL WILL
 ADEQUATELY SUPPORT 2X6 PROPOSED ADDITION.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 ALSO, CLARIFY HOW IS THE NEW FOUNDATION GOING TO BE
 INSTALLED IF EXISTING WALLS ARE GOING TO REMAIN?
  
 7-PROVIDE STRUCTURAL DETAILSHOWING ATTACHMENT OF
 STRUCTURAL BUCK TO STEEL COLUMN AND STEEL HEADER FOR
 NEW GARAGE DOOR. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 TO VERIFY COMPLIANCE WITH SEC. R301.
  
 8-SHEET A-2:
 A) REVISE LOCATION OF EMERGENCYSCUPPER TO COMPLY
 WITH SEC. R903.4.1.
  
 B) PROVIDE COMPLETE INFORMATION FOR FABRIC AWNINGS
 TO SHOW COMPLIANCE WITH SEC. 3105 FBC 2004 OR APPLY FOR
 SEPARATE PERMIT.
  
 9- SHEET A-4:
 A) REVISE SPECIFICATIONS FOR CEILING TYPE IN GARAGE
 AREA TO COMPLY WITH SEC. R309.2.
  
 B) REVISE SPECIFICATIONS FOR DOUBLE TOP PLATE ON
 EXISTING 2X4 WALL. IT SAYS 2X6 TOP PLATES. REVISE AS
 REQUIRED.
  
 10- SHEET S-1 (SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH SEC. R301):
 A) PROVIDE DETAILS SHOWINGHOWIS THE W8X21 BEAM
 ATTACHED TO THE OTHER W8X21 BEAM AND W8X21 BEAM TO THE
 W12X26 BEAM.
  
 B) TYPICAL EXTERIOR WALL SECTION 5/S-1 DOESN'T
 REFLECT ACTUAL CONDITIONS SHOWN ON THE FRAMING PLAN.
 W8X21 BEAM IS NOT RESTING ON THE STEEL COLUMN AS SHOWN
 ON THE DETAIL.ALSO, STEEL BEAMS ARE NOT SHOWN TO
 SCALE. SIZE OF BEAM SPECIFIED IS NOT THE SAME OF FLOOR
 TRUSSES. REVISE AS REQUIRED.
  
 C) PROVIDE DETAIL/SPECIFICATIONS SHOWING HOWIS THE
 2X6 BOTTOM PLATE ATTACHED TO STEEL BEAM.
  
 D) SPECIFY HOW ARE FLOOR TRUSSES ATTACHED TO STEEL
 BEAMS.WHERE IS JUS-21 TRUSS HANGER BY SIMPSON TAKEN
 FROM?.NEED TO SPECIFY CONNECTOR PROPER FOR STEEL BEAM
 INSTALLATION. SEE SIMPSON CATALOG FOR PROPER CONNECTORS
 TO BE USED.
  
 E) TRELLIS COLUMNS ARE NOT SPECIFIED. WHAT'S WCI?.
 THERE IS NOT INFORMATION ON THE COLUMN SCHEDULE.
  
 F) INFORMATION FOR STEEL COLUMNS IS CONFUSING.
 INFORMATION SHOWN ON DETAIL 4/S-1 AND COLUMN SCHEDULE
 DOESN'T MATCH. REVISE AS REQUIRED AND PROVIDE CLEAR
 SPECS FOR TOPAND BOTTOM PLATES AND ANCHORS. REVISE
 WIDTH AND LENGTH INFORMATION SHOWN ON STEEL COLUMN
 SCHEDULE. IT CAN'T BE 4".
  
 G) NOA 01-0209.03 IS NOT LISTEDIN THE MIAMI
 WEBSITE. REVISE INFORMATION AS REQUIRED.
  
 11- S-2(SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH SEC. R301):
 A) TRUSS ANCHOR SCHEDULE IS NOT CLEAR. BOTH ANCHORS
 ARE MARKED AS "ANCHOR MARK I"AND THERE IS NOT
 REFERENCED ON THE FRAMING PLANS. REVISE AS REQUIRED TO
 CORRELATE TRUSS ANCHOR SCHEDULE WITH FRAMING PLANS.
  
 B) REVISE DISTANCE"A" SPECIFIED ON COMPONENTS &
 CLADDINGDETAIL D.SEE NOTE AT BOTTOM OFFIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 C) REVISE DETAIL 2/S-2:STEEL BEAM NEEDS TO BE
 DRAWN TO SCALE.(1) THIS BEAM IS NOT 16" DEEP.(2)
 NEED TO DRAW TO SCALE TO SHOW PROPER ATTACHMENT OF
 FLOOR TRUSSES AND TERRACE TRUSSES TO THE BEAM.
 (3) SPECIFY CORRECT TRUSS HANGER FOR PROPOSED
 INSTALLATION TO STEEL BEAM.(4) SPECIFY ATTACHMENT OF
 2X6 BOTTOM PLATE TO STEEL BEAM.
  
 D) BOTTOM PLATEANCHOR TYPE AND SPACING SPECIFIED
 ON DETAIL 6/S-2 DOESN'T MATCH INFORMATION SHOWN ON
 DETAILS 5/S-3, 6/S-3 AND 8/S-3. REVISE AS REQUIRED TO
 MATCH.
  
 E) PROVIDE COMPLETE DETAIL/ SPECIFICATIONS FOR
 ATTACHMENT OF 2X WOOD TO STEEL BEAM SHOWN ON DETAIL
 4/S-2.
  
 F) ALL DETAILS NEED TO INDICATE HOW IS THE2X6
 BOTTOM PLATEFASTENED TOFLOOR TRUSSES AND ROOF
 TRUSSES. SEC.R601.2.
  
 12- SHEET S-3 (SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH SEC. R301)
 A) REVISE DISTANCE "A"SHOWING ON DETAIL A. SEE
 NOTE ON FIGURE R301.2(8) OF 2004 FLORIDA RESIDENTIAL
 CODE AND REVISE AS REQUIRED.
  
 B) WINDOW AND DOOR WIND PRESSURES CHART. REVISE ITEM
 D).THIS IS EXPOSURE "C", NOT"B".
 ALSO, REVISE NOTE #1.SEE ITEM 12 A) ABOVE.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GARAGE DOORS. NEED PRODUCT APPROVAL FOR DOOR THAT
 MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
  
 B) PRECAST LINTELS.
  
 C) GARAGE SWING DOOR.
  
 D) FLAT ROOF:1) CLEARLY IDENTIFY SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED. 2) CLEARLY INDICATE SPECIFIC
 BASE SHEET FASTENING OPTION IF MORE THAN ONE FASTENING
 OPTION IS SHOWN ON SELECTED ASSEMBLY. 3) PROVIDE RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7.
 NOTE: APPROVED ASSEMBLIES WITH GENERAL LIMITATION #9
 ARE NOT GOOD IN THIS AREA BECAUSE NAIL ENHANCING IS NOT
 ALLOWED.
  
 14- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 15- SOIL TEST REPORT :
 A) NEED REPORTWITH ORIGINAL SIGNATURE AND SEAL AS
 REQUIRED BY SEC. 61G15-23.002.
  
 B) NEED TO PROVIDE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002(2).
  
 16- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600A-2004 R.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
  
 C) INSULATION VALUES SHOWN FOR FLOOR, WALLS AND
 CEILING DON'T MATCH. PLANS. REVISE AS REQUIRED TO
 MATCH.
  
 D) CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO. THEREFORE, BUILDING CORRECT ORIENTATION MUST
 MATCH ACTUAL BUILDING ORIENTATION. REVISE ORIENTATION
 INFORMATION ON SECOND PAGE AS REQUIRED. SEE SURVEYOR
 SITE PLAN FOR CORRECT BUILDING ORIENTATION.
  
 E) OVERHANG LENGTH AND OVERHANG HEIGHT ARE
 INCORRECT. REVISE INFORMATION ON SECOND PAGE AS
 REQUIRED TO MATCH PLANS AND ELEVATIONS.
  
 17- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. THEN NEED TO SPECIFY ON PLANS SIZE OF FAN AS
 REQUIRED BY TALE 13-607.1.A.1 OF FBC 2004.
  
 18- OWES $3.84 FOR RADON FEES.
  
 ***NOTE:
 PLEASE RETURN REVIEWED SET OF DRAWINGS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS TO EXPEDITE
 THE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-03-12 Cont ID  
Sent By btrobaug Date 2008-03-12 Time 14:43 Rev Time 0.00
Received By btrobaug Date 2008-03-12 Time 12:19 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-06-05 Cont ID  
Sent By jleech Date 2008-06-05 Time 09:51 Rev Time 0.00
Received By jleech Date 2008-06-05 Time 09:45 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By jleech Date 2008-03-13 Time 09:13 Rev Time 0.00
Received By jleech Date 2008-03-13 Time 08:59 Sent To P
Notes
2008-03-13 09:27:06DENIED;
 1. THE RISER DIAGRAM LOOKS LIKE THE PIPE IS RUNNING
 DOWN THE WALL, THE CHART (402.4(1) IS FOR CAST IRON
 PLASTIC PIPE IS SPECED OUT ON PLAN . PLEASE CORRECT.
 2. THE REGULATOR SHOULD BE ON THE SUPPLY SIDE OF THE
 METER.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-03-11 Cont ID  
Sent By ssherman Date 2008-03-11 Time 12:18 Rev Time 0.00
Received By ssherman Date 2008-03-11 Time 12:18 Sent To  
Notes
2008-03-11 12:19:25HISTORICAL APPROVAL PER FRIEDERIKE MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 15:26 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 15:26 Sent To  
Notes
2008-12-19 15:26:26TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 13:40 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 13:40 Sent To Z
Notes
2008-10-17 13:41:17TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 09:59 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 09:59 Sent To B
Notes
2008-07-29 10:00:40TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 16:07 Sent To G
Notes
2008-05-23 16:09:22TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 10:33 Rev Time 0.00
Received By adarroug Date 2008-04-25 Time 10:32 Sent To M
Notes
2008-04-25 10:33:22TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-17 Cont ID  
Sent By jgomez Date 2008-03-17 Time 14:13 Rev Time 0.00
Received By jgomez Date 2008-03-11 Time 15:00 Sent To  
Notes
2008-03-11 15:01:00TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-10-24 Cont ID  
Sent By rkussner Date 2008-10-24 Time 16:58 Rev Time 0.00
Received By rkussner Date 2008-10-24 Time 16:58 Sent To PC
Notes
2008-11-04 13:19:49REFER TO PERMIT # 08040678 FOR LANDSCAPE PLANS AND
 APPROVAL.---RAK 11/4/08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-25 Cont ID  
Sent By tgordon Date 2008-04-25 Time 11:27 Rev Time 0.30
Received By tgordon Date 2008-04-25 Time 11:27 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By tgordon Date 2008-03-13 Time 07:57 Rev Time 0.30
Received By tgordon Date 2008-03-13 Time 07:57 Sent To P
Notes
2008-03-13 08:01:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PER 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1 OR 13-407.1.ABC.1.
  
 3)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-28 Cont ID  
Sent By jleech Date 2008-04-28 Time 08:49 Rev Time 0.00
Received By jleech Date 2008-04-28 Time 08:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By jleech Date 2008-03-13 Time 10:22 Rev Time 0.00
Received By jleech Date 2008-03-13 Time 09:27 Sent To B
Notes
2008-03-13 10:14:40DENIED;
 1. PLUMBING GENERAL NOTES SHALL BE OF SUFFICIENT
 CLARITY ( CANNOT READ NOTES) SEE FBC-BUILDING CHAPTER 1
 SECTION 106.1.1.
 2. SECONDARY ROOF DRAINS OR SCUPPERS ARE REQUIRED PER
 FBC-PLUMBING TABLE 1106.7 AND SECTION 1107.3.
 3. SANITARY RISER DIAGRAM. THE W/M AND L/T ARE NOT
 PERMITTED ON A SANITARY CROSS AS DRAWN, L/T SHOULD BE
 ABOVE W/M. SEE SECTION 706.3. SHOW THE CLEANOUT ( AT
 THE BOTTOM OF THE STACK) AT 48" AFF.
 4. WATER RISER DIAGRAM; A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE REF. PLEASE SHOW ON DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-11 Cont ID  
Sent By choops Date 2008-03-11 Time 16:07 Rev Time 0.00
Received By choops Date 2008-03-11 Time 16:07 Sent To B
Notes
2008-03-11 16:13:46***APPROVED***
  
  
  
  
 SENT TO "E" - SF RACK
  