Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-03-13 Cont ID  
Sent By btrobaug Date 2008-03-11 Time 11:54 Rev Time 0.00
Received By btrobaug Date 2008-03-11 Time 11:20 Sent To I
Notes
2008-03-13 09:25:53 
 PROVISO
  
 1} THE REVERENCE TO ARTICLE310.17 FOR SIZING CABLE IS
 INCORRECT, 310.16 MUST BE USED FOR CABLE.
  
 TABLE 310.16 ALLOWABLE AMPACITIES OF INSULATED
 CONDUCTORS RATED 0 THROUGH 2000 VOLTS, 60?C THROUGH
 90?C (140?F THROUGH 194?F), NOT MORE THAN THREE
 CURRENT-CARRYING CONDUCTORS IN RACEWAY, CABLE, OR EARTH
 (DIRECTLY BURIED), BASED ON AMBIENT TEMPERATURE OF 30?C
 (86?F)
  
 #4/0 CONDUCTORS FOR 225 AMPS
  
 #1 CONDUCTORS FOR 125 AMPS
  
 THE FIELD INSPECTOR HAS BEEN MADE AWARE OF THE ERROR ON
 THE PLANS
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718