| Plan Review Stops For Permit 08030172 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-11 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-11 |
Time |
11:20 |
Sent To |
I |
|
| Notes |
| 2008-03-13 09:25:53 | | | | PROVISO | | | | | | 1} THE REVERENCE TO ARTICLE310.17 FOR SIZING CABLE IS | | | INCORRECT, 310.16 MUST BE USED FOR CABLE. | | | | | | TABLE 310.16 ALLOWABLE AMPACITIES OF INSULATED | | | CONDUCTORS RATED 0 THROUGH 2000 VOLTS, 60?C THROUGH | | | 90?C (140?F THROUGH 194?F), NOT MORE THAN THREE | | | CURRENT-CARRYING CONDUCTORS IN RACEWAY, CABLE, OR EARTH | | | (DIRECTLY BURIED), BASED ON AMBIENT TEMPERATURE OF 30?C | | | (86?F) | | | | | | #4/0 CONDUCTORS FOR 225 AMPS | | | | | | #1 CONDUCTORS FOR 125 AMPS | | | | | | THE FIELD INSPECTOR HAS BEEN MADE AWARE OF THE ERROR ON | | | THE PLANS | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|