Plan Review Details - Permit 08030072
Plan Review Stops For Permit 08030072
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By lursu Date 2008-06-11 Time 08:39 Rev Time 0.00
Received By lursu Date 2008-06-11 Time 08:39 Sent To  
Notes
2008-06-11 08:40:39THE WORK IS DONE AT THE UNIT WITH THE SITE ADDRESS OF
 2401 N DIXIE HWY ,THEREFORE THE PERMIT IS ATTACHED TO
 THIS ADDRESS.
  
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-03-24 Cont ID  
Sent By lursu Date 2008-03-24 Time 13:53 Rev Time 0.00
Received By lursu Date 2008-03-24 Time 13:53 Sent To  
Notes
2008-03-24 13:54:40THE SITE ADDRESS OF 2401 N DIXIE HWY MUST BE DEPICTED
 ON THE TITLE BLOCK OF EACH SHEET REPRESENTING THE NEW
 UNIT .
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By lursu Date 2008-03-19 Time 15:57 Rev Time 0.00
Received By lursu Date 2008-03-18 Time 08:12 Sent To  
Notes
2008-03-19 16:00:20THE SITE ADDRESS ON THE APPLICATION READS 2401-2405 N
 DIXIE HWY , HOWEVER THE PCN = 74434309050520010 IS
 LISTED IN CITY RECORDS AS 2409 N DIXIE HWY . IF A
 COMBINATION OF TWO UNITS WILL BECOME ONE UNIT THEN THE
 REVISEDPLANS MUST DEPICT THE ADDRESS RANGE OF
 2405-2409 N DIXIE HWY .PLEASE CALL FOR QUESTIONS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-04-27 Cont ID  
Sent By jwitmer Date 2009-04-27 Time 09:48 Rev Time 1.55
Received By jwitmer Date 2009-04-27 Time 09:48 Sent To  
Notes
2009-04-27 09:49:56STAMP PLANS ARCHITECTURAL AND STRUCTURAL REVISIONS
 STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-04-27 Cont ID  
Sent By jwitmer Date 2009-04-27 Time 09:48 Rev Time 0.55
Received By jwitmer Date 2009-04-09 Time 14:23 Sent To  
Notes
2009-04-09 14:32:53PLAN REVISIONS APPEAR TO BE CODE COMPLIANT, IN RECEIPT
 OF ENGINEERING LETTER FROM TABIO ENGINEERING CORP
 DELEGATING AND REVIEWING AN INDEPENDENT ENGINEER TOMMY
 TAVERAS-OK
 ISSUE AT HAND IS ENGINEERING LETTER FROM SW ENGINEERING
 HAS NOT BEEN REVIEWED BY TABIO ENGINEERING. FAXED A
 COPY OF THIS DOCUMENT TO TABIO ENGINEERING, CALLED THE
 FIRM BUT WAS ONLY ABLE TO LEAVE A MESSAGE. THEN TRIED
 CALLINF THE ARCHITECT OF RECORD DAVID SER AND WAS ABLE
 TO LEAVE A MESSAGE WITH EITHER RECEPTIONIST OR
 ANSWERING SERVICE. THURS PM DAVID SER DID RETURN MY
 TELEPHONE CALL, I EXPLAINED THE NEED OF ANOTHER LETTER
 FROM TABIO ENGINEERING COVERING THE WORK BROUGHT IN BY
 SW ENGINEERING. MR SER INDICATED THAT HE WOULD WORK ON
 THIS ISSUE RIGHT AWAY. I AM AWAITNG THE RAISED SIGNED &
 SEALED LETTER FROM TABIO ENGINEERING TO BE ABLE TO PASS
 ALL DOCUMENTS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-02-06 Cont ID  
Sent By jwitmer Date 2009-02-06 Time 16:03 Rev Time 1.22
Received By jwitmer Date 2009-02-06 Time 16:03 Sent To  
Notes
2009-02-06 16:37:18BUILDING PLAN REVIEW
 PERMIT: 08030072
 ADD: 2401-2405 N DIXIE HWY
 CONT: PLAN REVIEW
 TEL: (954)253-1716
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) THE COVERSHEET OF THE ISSUED PLANS INDICATES THE
 STRUCTURAL ENGINEER OF RECORD AS TABIO ENGINEERING
 CORP. THE NEW S-1 SHEET IS DESIGNED BY TOMMY TAVERAS
 P.E. A DIFFERENT ENGINEER FROM THE ENGINEER OF RECORD,
 IS MR. TAVERAS TAKING OVER THE PROJECT AS THE
 STRUCTURAL ENGINEER. PLEASE REVIEW FLORIDA
 ADMINISTRATIVE CODE 61G15-27.001.
 61G15-27.001 PROCEDURES FOR A SUCCESSOR PROFESSIONAL
 ENGINEER ADOPTING AS HIS OWN THE WORK OF ANOTHER
 ENGINEER.
 (1) A SUCCESSOR PROFESSIONAL ENGINEER SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 PROFESSIONAL ENGINEER'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. IN OTHER WORDS, CALCULATIONS,
 SITE VISITS, RESEARCH AND THE LIKE MUST BE DOCUMENTED
 AND PRODUCEABLE UPON DEMAND. FURTHER, THE SUCCESSOR
 PROFESSIONAL ENGINEER MUST TAKE ALL PROFESSIONAL AND
 LEGAL RESPONSIBILITY FOR THE DOCUMENTS WHICH HE SEALED
 AND SIGNED AND CAN IN NO WAY EXEMPT HIMSELF FROM SUCH
 FULL RESPONSIBILITY. PLANS NEED NOT BE REDRAWN BY THE
 SUCCESSOR PROFESSIONAL ENGINEER; HOWEVER, JUSTIFICATION
 FOR SUCH ACTION MUST BE AVAILABLE THROUGH WELL KEPT AND
 COMPLETE DOCUMENTATION ON THE PART OF THE SUCCESSOR
 PROFESSIONAL ENGINEER AS TO HIS HAVING RETHOUGHT AND
 REWORKED THE ENTIRE DESIGN PROCESS. A SUCCESSOR
 PROFESSIONAL ENGINEER MUST USE HIS OWN TITLE BLOCK,
 SEAL AND SIGNATURE AND MUST REMOVE THE TITLE BLOCK,
 SEAL AND SIGNATURE OF THE ORIGINAL PROFESSIONAL
 ENGINEER BEFORE REUSING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING AND SIGNING WORK A SUCCESSOR
 PROFESSIONAL ENGINEER SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL PROFESSIONAL ENGINEER, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL PROFESSIONAL ENGINEER OF THE
 SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 PROFESSIONAL ENGINEER'S WORK. THE SUCCESSOR
 PROFESSIONAL ENGINEER WILL TAKE FULL RESPONSIBILITY FOR
 THE DRAWING AS THOUGH THEY WERE THE SUCCESSOR
 PROFESSIONAL ENGINEER'S ORIGINAL PRODUCT.
 SPECIFIC AUTHORITY 471.033(2) FS. LAW IMPLEMENTED
 471.033(1)(J), 471.005(6) FS. HISTORY???NEW 8-25-87,
 AMENDED 4-21-88, 8-3-88, FORMERLY 21H-27.001.
  
 2) THIS COMMENT IS A CROSS-OVER BETWEEN THE STRUCTURAL
 REQUIREMENTS IN 1609.6.2.2 COMPONENTS AND CLADDING AND
 SECTION 301. 13WIND RESISTANCE OF THE 2004 FBC
 MECHANICAL CODE, REQUIRING SUFFICENT INFORMATION TO
 DETERMINE IF THE ROOF TOP AIR HANDLER WILL HOLD
 TOGETHER AND STAY IN PLACE IN A HIGH WIND EVENT. THE
 MECHANICAL PLANS THAT WERE ISSUED INDICATES THE USE OF
 RHEEM ROOF TOP EQUIPMENT BUT THE
 UNIT REVIEWED BY YURASEK CONSULTANTS INDICATES A
 DIFFERENT UNIT A TEMPSTAR PAE 090. WE DO NOT HAVE ANY
 CUT SHEETS OR INFORMATION ON THIS UNIT NOR WERE THER
 CALCULATIONS SUBMITTED BY YURASEK FOR REVIEW BY THIS
 OFFICE. INREGARDS TO IF THIS REQUIREMENT WAS ADOPTED BY
 THE COUNTY I BELIEVE YOU MEAN TO SAY THE CITYS
 CONSTRUCTION BOARD OF ADJUSTMENT AND APPEAL AND RULING,
 IT WAS OVERTURNED AT THE STATE LEVEL, THE MECHANICAL
 REVIEWER WILL ELABORATE MORE ON THIS MATTER.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-08 Cont ID  
Sent By jwitmer Date 2008-09-08 Time 15:26 Rev Time 0.77
Received By jwitmer Date 2008-09-08 Time 15:26 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-18 Cont ID  
Sent By lmartine Date 2008-07-18 Time 15:50 Rev Time 0.00
Received By lmartine Date 2008-07-18 Time 15:38 Sent To  
Notes
2008-07-18 15:49:15BUILDING REVIEW COMMENTS
  
  
  
  
 #6 FROM PREVIOUS REVIEW IS COMPLIED WITH.
  
 #8 FROM PREVIOUS REVIEW IS STILL REQUIRED, PLEASE CARRY
 PLANS TO PALM BEACH COUNTY IMPACT FEE OFFICE FOR THEIR
 REVIEW AND PROVIDE A LICENSED CONTRACTOR FOR BUILDING
 PERMIT APPLICATION.
  
  
  
 THANK YOU,
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 14:40 Rev Time 1.22
Received By jwitmer Date 2008-06-06 Time 14:40 Sent To  
Notes
2008-06-06 14:44:01BUILDING PLAN REVIEW
 PERMIT: 08030072
 ADD: 2401-2405 N DIXIE HWY
 CONT: PLAN REVIEW
 TEL: (954)253-1716
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST, SHEET A6 & A7 DO NOT PROVIDE WHERE THE
 CEILING OR ROOF INSULATION WILL BE IN THE SECTION OF
 BUILDING WITH THE HIGHER FLAT ROOF? 13-404.1.ABC.1
 RESPONCE INDICATED THIS IS A HISTORIC BUILDING.
 CURRENTLY THIS BUILDING IS NOT DESIGNATED AS A
 HISTORICAL LANDMARK AND WILL NEED TO COMPLY WITH THE
 ENERGY CODE.
  
 7) COMPLIED.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By jwitmer Date 2008-04-10 Time 14:21 Rev Time 4.44
Received By jwitmer Date 2008-04-10 Time 14:21 Sent To  
Notes
2008-04-10 15:34:51BUILDING PLAN REVIEW
 PERMIT: 08030072
 ADD: 2401-2405 N DIXIE HWY
 CONT:PLAN REVIEW
 TEL: (954)253-1716
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 NOTE THE 2004 FBC W/ 2007 SUPPLEMENTS AND 2004
 EXISTING BUILDING CODE ARE BOTH TO BE USED IN DESIGN
 FOR REMODELING.
 PROVIDE WHAT LEVEL OF ALTERATION TO BE COMPLETED
 UNDER THIS PERMIT. EXXISTING BUILDING CODE 301.5. B)
 THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601.
  
 3)PLEASE SEE THE EXIT CORRIDOR THAT IS SHARED BY BOTH
 TENANTS AND SECTION 605.1 IN THE 2004 EXISTING BUILDING
 CODE. THE DOORWAY FROM THE UNIT BEING REMODELED SWINGS
 INTO THE EXIT ACCESS CORRIDOR AND LEAVES LESS THAN THE
 REQUIRED 18".
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A LANDING. THE LANDING
 SHALL HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH OF THE
 DOOR.
  
 4) A-4 ALSO INDICATES TWO DOORS B & C.
  
 4A) DOOR TYPE B IS A PAIR OF DOORS REQUIRING A CLEAR
 WIDTH OF 32". 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). WHERE
 THIS SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32
 INCHES (813 MM) AND A DOOR OPENING INCLUDES TWO DOOR
 LEAVES WITHOUT A MULLION, ONE LEAF SHALL PROVIDE A
 CLEAR OPENING WIDTH OF 32 INCHES (813 MM). THE MAXIMUM
 WIDTH OF A SWINGING DOOR LEAF SHALL BE 48 INCHES (1219
 MM) NOMINAL. MEANS OF EGRESS DOORS IN AN OCCUPANCY IN
 GROUP I-2 USED FOR THE MOVEMENT OF BEDS SHALL PROVIDE A
 CLEAR WIDTH NOT LESS THAN 41? INCHES (1054 MM). THE
 HEIGHT OF DOORS SHALL NOT BE LESS THAN 80 INCHES (2032
 MM). 11-4.13.4. DOUBLE LEAF DOORS.
  
 4B) DOOR C IN THE DEMO PLAN WAS AN OPENING OF 4'-0" YOU
 CAN'T REDUCE OPENINGS TO WHERE THEY ARE NOT CODE
 COMPLIANT. THE MINIMUMDOOR OPENING SIZE WOULD BE A
 2'-10" LEAVING A 32"
 OPENING. FLORIDA EXISTING BUILDING CODE 606.1 A
 BUILDING ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE. 11-4.13.5.
  
 5) SHEET A-6 INDICATES A NEW A/C ROOF TOP UNIT, PLEASE
 PROVIDE A CURB DETAIL AND ANCHORAGE AGAINST OVER
 TURNING AND SLIDDING. 1609.1.3.
  
 6) SHEET A6 & A7 DO NOT PROVIDE WHERE THE CEILING OR
 ROOF INSULATION WILL BE IN THE SECTION OF BUILDING WITH
 THE HIGHER FLAT ROOF? 13-404.1.ABC.1
  
 7) SHEET A-25 IS LABELED AS A PROPOSED "SECOND FLOOR"
 ACCESSIBILITY PLAN, IS THERE A SECOND FLOOR? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-04-24 Cont ID  
Sent By dpalmer Date 2009-04-24 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2009-04-24 Time 16:34 Sent To  
Notes
2009-04-24 16:35:07E-3 OK

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-04-14 Cont ID  
Sent By dpalmer Date 2009-04-14 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2009-04-14 Time 16:16 Sent To  
Notes
2009-04-14 16:16:30** DENIED/PASSED**
  
  
  
 1) NOTE: SHEET E-5 OK AND STAMPED. ALL ELECTRICAL
 SHEETS WERE PLACED IN ONE ROLL WHEN SUBMITTED. TWO
 COPIES NEED TO GO BACK TO CONTRACTOR.
 WHEN RESUBMITTING PLANS PLEASE BE SURE TO PLACE SHEETS
 IN SEPARATE ROLLS/SETS.
  
 2) NOTE: CALLED AND SPOKE TO ENGINEER. FIXTURE *I*
 MISSING FROM FIXTURE LEGEND AND ENERGY CALCULATIONS.
 FIXTURES *J* WERE PLACED IN CALCULATIONS BASED ON THE
 CFL BULB WATTAGE WHEN 13-415.2.ABC.1.1, .1.2 REQUIRES
 THE RATING OF THE FIXTURE. PLEASE ADJUST CALCULATIONS
 AND PLANS.
 THIS WAS GONE OVER ON THE PHONE WITH ENGINEER. THIS
 WILL BE REVISED ACCORDINGLY AND FIXTURE *I* WILL BE
 STATED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-02-20 Cont ID  
Sent By dpalmer Date 2009-02-20 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2009-02-20 Time 14:38 Sent To  
Notes
2009-02-20 14:38:20** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SEE SHEET E-3. ALL OF THE MANUFACTURE
 INFORMATION FOR THE LIGHTING FIXTURES HAS BEEN REMOVED.
 THE REVISION IN THE TITLE BLOCK STATES *AS-BUILT*.
 HOWEVER REVISIONS FOR THE FINAL INSPECTIONS OF A
 PROJECT WOULD NOT REMOVE INFORMATION. IT MAY CHANGE OR
 BE REVISED BASED ON A DIFFERENT MANUFACTURE HOWEVER THE
 INFORMATION ON THE FINAL RECORD SETS OF PLANS WOULD NOT
 BE REMOVED.
 PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3.
 SINCE THE CODE REQUIRES THE VA/ WATTAGES TO BE USED ARE
 BASED ON THE FIXTURE BALLAST RATINGS ETC AND NOT THE
 BULB WATTAGE THE SPECIFIC FIXTURES NEED TO BE LISTED TO
 VERIFY CODE COMPLIANCE.
 PLEASE SEE THAT THE FACT THE MINIMUM LIGHTING
 PERFORMANCE CALCULATIONS WHICH WERE PREVIOUSLY SHOWN ON
 E-3 WERE ALSO COMPLETELY REMOVED.
  
 2) NOTE: RISER DIAGRAM IS NOW COMPLETELY REVISED
 SHOWING A NEW SERVICE TO BE GRANTED BY *SPECIAL
 PERMISSION*.
 THIS SERVICE IS NOT GRANTED BY 230.2. NO CONTACT TO
 THIS OFFICE/REVIEWER HAS BEEN MADE TO GO OVER ANY OF
 THESE CHANGES OR PROPOSALS TO DATE. THE SPECIAL
 PERMISSION DEFINITIONS IS NOT GRANTED AND NO ADDITIONAL
 INFORMATION WAS PROVIDE OR SHOWN FOR CONSIDERATIONS.
 SERVICES ARE NOT GRANTED WITHOUT JUSTIFICATION.
 THIS WAS IN THE ORIGINAL COMMENTS FROM MARCH 2008 AND
 INFORMATION WAS NOT PROVIDED AT THAT TIME EITHER. THE
 SERVICE WAS REVISED FOR PERMITTING FROM THE SERVICE
 PROVIDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-08-06 Cont ID  
Sent By dpalmer Date 2008-08-06 Time 11:35 Rev Time 0.00
Received By dpalmer Date 2008-08-06 Time 11:35 Sent To B
Notes
2008-08-06 11:41:54PLANS ROUTED TO LUIS MARTINEZ'S OFFICE FOR REVIEW AND
 PROCESSING.
  
 NEW ENERGY CALCULATIONS SUBMITTED ON AUG 5TH ARE OK FOR
 ELECTRICAL AND MECHANICAL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-08-01 Cont ID  
Sent By dpalmer Date 2008-08-01 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2008-08-01 Time 11:44 Sent To P
Notes
2008-08-01 13:04:53** NOTE ADDED
  
 SPOKE TO JOHN FROM T&F 12:57PM ON 8/1/08HE WILL BRING
 IN CALCULATIONS ON MONDAY THE 7TH SO THEY MAY BE
 REVIEWED.
2008-08-01 11:49:48** TEMP DENIED ***
  
 1) NOTE: NO NEW ENERGY CALCULATIONS SUBMITTED ONLY THE
 OLD ARE IN PACKAGE. CALLED JOHN FROM T&F CONTRACTORS TO
 HAVE THE CALCULATIONS BROUGHT IN TOBE REVIEWED.
 ELECTRICAL PLANS ARE OK HOWEVER STILL NEED TO REVIEW
 CALCULATIONS FOR *MINIMUM* CODE COMPLIANCE WITH
 13-415.2.ABC.1.1,.1.2.
 CONTRACTOR SAID ON PHONE HE WILL CALL BACK AS HE WAS IN
 A MEETING AND COULD NOT TALK. ROUTED TO OTHER TRADES
 FOR THEIR FINAL REVIEW/STAMPING AND PROCESSING OF
 PLANS.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-17 Cont ID  
Sent By dpalmer Date 2008-07-17 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2008-07-17 Time 14:03 Sent To  
Notes
2008-07-17 14:03:18** DENIEDRE-SUB FOR PLAN REVIEW ONLY**
  
  
  
 1) NOTE: PLANS HAVE STILL ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT YET BEEN SUBMITTED FOR PERMIT.
  
 2) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY
 CALCULATIONS ARE BEING SUBMITTED FOR REVIEW.THIS
 REVIEWER HAS CALLED ENGINEER OF RECORD AND GONE OVER
 ITEMS. NOTES WERE BEING TYPED AT THE TIME OF
 CONVERSATION WITH THE DESIGN PROFESSIONAL.
 PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS ARE IN
 NEED OF REVISING TO MEET COMPLIANCE WITH FBC
 13-400.3.B, 13-415.2, 13-415.2.ABC.1.1 AND .1.2. PLEASE
 SEE THE ELECTRICAL PLANS CONTAIN LIGHTING FIXTURES
 WHICH ARE NOT IN THE INPUT DATA REPORT. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
 PLEASE SEE THE PLANS AS THE LIGHTING PERFORMANCE
 CALCULATIONS SHOWN DO NOT COORDINATE WITH THE SUBMITTED
 CALCULATIONS. THE LIGHTING PERFORMANCE CALCULATIONS ON
 PLANS DO NOT NEED TO BE THERE IF COMPLIANCE IS GOING TO
 BE SHOWN IN THE METHOD *B* CALCULATIONS.
 ** SOME EXAMPLES OF THESE ARE GIVEN BELOW.
  
 FOR EXAMPLE:
 PLANS SHOW A TOTAL OF 20 108W FIXTURES YET THE IDR ONLY
 CONTAINS 17 OF THESE.
  
 FOR EXAMPLE:
 PLEASE SEE THE FIXTURE *J* AS SHOWN ON PLANS AND ON
 FIXTURE LEGEND IS A 26WATT FIXTURE. PLANS SHOW 4 OF
 THESE AND YET THE IDR DO NOT SHOW ANY 26WATT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS INDICATE *L* FIXTURES WHICH ARE SHOWN
 AS 50W FIXTURES YET THE IDR DOES NOT CONTAIN ANY 50WATT
 FIXTURES.
  
 ** PLEASE COORDINATE ALL OF THE ABOVE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By dpalmer Date 2008-06-11 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2008-06-11 Time 09:05 Sent To PC
Notes
2008-06-11 09:06:02** DENIED 2ND REVIEW **
  
 ** THIS PROJECT IS STILL ONLY SUBMITTED FOR *PLAN
 REVIEW* ONLY AND IS NOT SUBMITTED UNDER PERMIT
 APPLICATION.
  
 ** PLEASE SEE THERE ARE STILL SOME ITEMS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING. THERE ARE ALSO
 NEW COMMENTS BASED ON REVISED PLANS/RISER NOW SHOWN AND
 INFORMATION WHICH WAS NOT ON PREVIOUS PLANS.
  
 ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE ITEMS NOT
 IN DESIGN YET AT THIS TIME OR SHOWN ON PLANS, NEW
 COMMENTS MAY BE GENERATE WHICH CAN NOT POSSIBLY BE MADE
 AT THIS TIME. REVIEWS ARE DONE BASED ON PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING CONTROLS
 STILL NEED TO BE ADDRESSED. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 SECTION 13-415.1.ABC.1.4 WILL APPLY FOR ANY OUTSIDE
 LIGHTING.
 PLEASE SEE SECTIONS OF CODES NOTED ABOVE WITH RESPECT
 TO INTERIOR LIGHTING. THE PLANS CAME BACK WITH A
 LIGHTING CONTROL PANEL/TIME CLOCK AND THE RESPONSE
 MENTIONS MANUAL CONTROLS ARE SHOWN BY SWITCHES IN
 SEPARATE SPACES. THE SEPARATE SPACE CONTROLS ARE
 REQUIRED TO OVER RIDE ANY TIME OF DAY SCHEDULING AND
 ARE ALSO LIMITED IN THE TIME OF THE OVER RIDES.
 STANDARD SWITCHES SHOWN ON PLANS DO NOT COMPLY WITH THE
 FLORIDA BUILDING CODE FOR ENERGY CODE COMPLIANCE. AS
 SHOWN ON PLANS, IF AN OCCUPANT TURNS A LIGHT SWITCH ON
 IN ANY ROOM IN *OUT OF BUSINESS HOURS* THE LIGHTING
 WOULD REMAIN ON INDEFINITELY. AUTOMATED CONTROLS FOR
 *ALL* LIGHTING WITHIN THIS BUILDING IS REQUIRED
 INCLUDING THAT OF SEPARATE SPACES TO OVER-RIDE TIME OF
 DAY SCHEDULING AS NOTED.
 AS NOT SYSTEM, DEVICES ETC WERE SHOWN IN DESIGN A FULL
 REVIEW OF SEVERAL ITEMS COULD NOT BE DONE AT THIS
 TIME.
 ** AS NOTED ABOVE, OUTSIDE LIGHTING IN PARKING LOTS,
 DECORATIVE ETC OF ANY KIND WHICH WILL BE FED ON THIS
 PROPERTY SHALL HAVE LIGHTING CONTROLS.
 PLEASE KNOW THERE ARE MINIMUM LIGHTING REQUIRED IN
 PARKING LOTS UNDER ZONING REQUIREMENTS IN DEFINED AREAS
 OF THE CITY OF WEST PALM BEACH.
 IF THERE IS EXISTING LIGHTING IN PARKING LOT AT THIS
 TIME WHICH ARE FED FROM PANELS, PLEASE BE SURE TO SEE
 SECTION AS NOTED ABOVE FOR OUTDOOR LIGHTING.
 ** AS NOTED ON PREVIOUS REVIEW **
  
 2) NOTE: PLEASE SEE REQUIREMENTS FOR LIGHTING
 PERFORMANCE DOES NOT MEET FLORIDA BUILDING CODE FOR
 ENERGY EFFICIENCIES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.1, .1.2, .1.3.
 THE RESPONSE MENTIONS TO SEE LIGHTING CALCULATIONS
 SHOWN ON PLANS. THE REVIEW OF THESE CALCULATIONS SHOWS
 THE MINIMUM DESIGN EXCEEDING THE ALLOWANCES BY THE
 CODE. THERE ARE SEVERAL ITEMS WHICH WILL BE NOTED
 BELOW.
 **AS NOTED ON PREVIOUS REVIEW**
  
 A) MAY NOT USE RETAIL AS THE OCCUPANCY AS STATED IN
 FLORIDA BUILDING CODE AND NFPA-101 STATES THIS IS
 BUSINESS OCCUPANCY. THEREFORE THE ALLOWANCES SHOWN IN
 TABLES MUST ONLY USE OFFICE.
 THIS APPLIES TO MOST AREAS ON PLANS WHICH SHOWS *SALES
 AREAS* AS THE ALLOWED USE. ONE EXAMPLE OF AN AREA WHICH
 CAN NOT BE *SALES AREA* IS THE *CHANGING ROOM*. THIS IS
 ONLY ONE EXAMPLES AS MOST OF THE AREAS NOTED AS SALES
 AREAS ARE JUST NOT SALES AREAS. THE CLOSET AS SHOWN IS
 NOT CONSIDERED *ACTIVE STORAGE* BASED ON USE SHOWN ON
 PLANS.
 THE CODE IS CLEAR FOR USE AND OCCUPANCIES. PLEASE KNOW
 AS INFORMATIONAL USE, MAY NOT USE 3.9 WATTS PER SQ FT
 AS FIGURED IN TABLE. THIS OCCUPANCY AND USE IS NOT
 INCLUDED.
 THESE ARE ONLY A COUPLE OF EXAMPLES.
  
 B) THE ALLOWANCES SHOWN ON PLANS FOR DECORATIVE
 LIGHTING ALSO EXCEED TABLES AND EXCEPTIONS TO TABLES.
 THE ALLOWANCE FOR DECORATIVE LIGHTING ABOVE THE GENERAL
 LIGHTING IS ONLY 1W PER SQ/FT. THE WATTAGE SHOWN
 EXCEEDS THIS LEVEL SUBSTANTIALLY.
  
 C) PLEASE SEE THE ALLOWANCES FOR DECORATIVE LIGHTS ETC
 MAY ONLY BE USE WHEN ACTUALLY INSTALLING THESE TYPES OF
 LIGHTS. CALCULATIONS SUBMITTED SHOW AN ALLOWANCE BEING
 ASSUMED WHEN NO DECORATIVE LIGHTING IS BEING
 INSTALLED.
  
 D) PLEASE SUBMIT ENERGY CALCULATIONS. AS NOTED IN
 MECHANICAL REVIEW NONE WERE LOCATED IN PLANS ETC
 SUBMITTED. PLEASE KNOW THIS OFFICE GIVES NOTICE TO
 PLEASE BE SURE ALL INFORMATION SHOWN ON PLANS IS
 SUBMITTED AND SHOWN ON THE SUBMITTED ENERGY
 CALCULATIONS. PLEASE BE SURE ALL INFORMATION ON THE
 INPUT DATA REPORT WHEN SUBMITTED COORDINATES WITH THE
 SUBMITTED PLANS.
 13-400.3.B, 13-400.3.C, 13-101.1.3
  
 ** PLEASE GO OVER ACTUAL CODE PERMITTED ALLOWANCES.
 PLEASE SEE SOME OF THE EXAMPLES ABOVE FOR NON-CODE
 COMPLIANCE IS GIVEN AS A BENEFIT AND IS NOT ALL ITEMS
 IN LIGHTING PERFORMANCE CALCULATIONS SUBMITTED WHICH DO
 NOT COMPLY.
  
 3) NOTE: PLEASE SEE RISER DOES NOT SHOW ANY METERING
 DEVICE ON THE MAIN 1 OF 2 WHICH APPEARS TO BE FOR THE
 SECOND TENANT. PLEASE SEE FPL MINIMUM SERVICE
 REQUIREMENTS WHICH AT THIS TIME HAVE NOT BEEN MET BY
 THE INFORMATION SHOWN ON RISER.
  
 4) NOTE: PLEASE SEE 250.6, 250.24. THE RISER SHOWS
 *EQUIPMENT GROUNDING CONDUCTORS* BEING INSTALLED BEFORE
 THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT
 PERMITTED. AS SHOWN THESE WOULD PARALLEL THE NEUTRAL
 CONDUCTORS THUS CREATING OBJECTIONABLE CURRENTS. PLEASE
 REMOVE ALL EQUIPMENT GROUNDING CONDUCTORS BEFORE THE
 FIRST MEANS OF DISCONNECTS.
  
 5) NOTE: PLEASE SEE RISER NOTE #9 WHICH CALLS FOR
 INTERRUPTION OF *FEEDERS* TO GO TO MAIN ONE OF TWO.
 THESE ARE NOT FEEDERS.
 PLEASE SEE NEC FOR DEFINITIONS IN ART 100, 230, 215,
 ETC
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINGLY. THERE WAS NO RESPONSE IN
 THE RESPONSE LETTER SUBMITTED. THIS WAS NOTED ON
 PREVIOUS REVIEW.
  
 7) NOTE: PLEASE PROVIDE INFORMATION AND SHOW EGRESS
 LIGHTING ON EXIT ACCESS CORRIDOR. IS THE LIGHTING GOING
 TO BE NEW OR EXISTING? PLEASE SHOW THE MINIMUM LIGHTING
 AND EXIT LIGHTING PER NFPA-101 7.8, 7.9.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE REVIEW.
  
 8) NOTE: PLEASE CLARIFY THE REAR HALLWAY. SOME SHEETS
 SHOW THE PREVIOUS EGRESS DOOR FROM OTHER TENANT SPACE
 BEING NOTED AS SEALED UP YET SOME SHEETS INDICATE THIS
 DOOR WILL BE *EXISTING TO REMAIN*.
 HOW WILL EGRESS FOR ADJACENT TENANT TAKE PLACE?
 IS THIS HALLWAY A COMMON AREA?
 THE NOTES ON PLANS DO NOT IDENTIFY THIS HALL WAY AS ANY
 ONE SPACE FOR EITHER TENANTS.
 SHEET A1 STATES THE ELECTRICAL PANELS SHOWN WILL
 REMAIN. IF THESE PANELS ARE FOR OTHER TENANT THEN THEY
 NEED TO BE RELOCATED INTO THE OTHER TENANT SPACE UNLESS
 THIS IS A COMMON AREA.
 IF THIS IS A COMMON AREA AND NOT PART OF EITHER TENANT
 THEN LIGHTING ETC WILL BE REQUIRED TO BE FED FROM A
 *HOUSE PANEL*.
  
 *** THESE ITEMS MAY BE BUILDING AND FIRE REVIEW RELATED
 HOWEVER MUST COMPLY WITH THE MINIMUM REQUIREMENTS OF
 THE FLORIDA BUILDING CODE AND ALL OTHER ADOPTED CODES,
 LAWS AND ORDINANCES.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 9) NOTE: PLEASE SEE 408.4, ALL CIRCUITING ON PLANS AND
 PANEL SCHEDULE SHALL BE SPECIFIC. LISTING *LIGHTING* AS
 A DESCRIPTION IS NOT SPECIFIC TO ROOMS OR AREAS.
  
 10) NOTE: PLEASE KNOW THE APPLIED VALUE FOR SCOPE OF
 WORK IS YET TO BE REVIEWED. THIS DOES AFFECT SECTIONS
 OF THE CODE(S) WHICH CAN NOT BE REVIEWED AT THIS TIME.
 FBC 108.3.
  
 11) NOTE: PLEASE SHOW AND IDENTIFY ALL PANELS ON RISER
 AND ON PLANS. AS NOTED IN NOTED #8 ABOVE, AREAS IN
 WHICH THESE PANELS ARE LOCATED HAVE NOT BEEN DETERMINED
 TO COMPLY WITH SECTIONS OF THE CODE(S).
 240.24, 110.26 ETC.
  
 12) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS THE
 ADDRESS ON TITLE BLOCKS CALL FOR 2401 ON SOME SHEETS
 AND 2409 ON OTHERS.FAC 61G1-16.004, 61G15-23.002, FBC
 106.5
  
 *** PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME DUE
 TO INFORMATION ETC NOT YET IN DESIGN OR ON PLANS.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By dpalmer Date 2008-03-17 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2008-03-17 Time 17:08 Sent To  
Notes
2008-03-17 17:09:05** DENIEDREVIEW**
  
 1) NOTE: PLEASE SEE THAT THE PLANS WERE ONLY SUBMITTED
 FOR PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 ONCE ALL COMMENTS ARE ADDRESSED AND PERMIT APPLICATION
 HAS NOT BEEN MADE REVIEW WILL STILL REMAIN IN FAILED
 STATUS UNTIL PERMIT HAS BEEN APPLIED FOR.
 REVIEW OF LICENSING ETC WILL BE DONE AT PERMIT
 APPLICATION BEFORE PERMIT ISSUANCE.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON ELECTRICAL PLANS AS WELL AS ARCHITECTURAL.
 2004 FBC W2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE)
  
 3) NOTE: PLEASE SEE THE PLANS AND RISER SEEMS TO SHOW A
 MAIN TWO OF TWO HOWEVER DOES NOT SHOW HOW THIS MAIN IS
 CONNECTED INTO THE NEW SERVICE.
 AT THIS TIME IT APPEARS THERE IS A NEW SERVICE BEING
 PROPOSED AND NOT ENOUGH INFORMATION TO GRANT A SEPARATE
 SERVICE PER 230.2
 240.4, 310.16, ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING PERFORMANCE
 CALCULATIONS AND ENERGY CALCULATIONS PER 13-415.2,
 13-400.3.B, 13-400.3.C ETC.
 PLEASE SEE BE SURE TO SEE 13-415.2.ABC.1.1, .1.2 AND
 .1.3 FOR LIGHTING INPUTS.
 PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH
 CALCULATIONS WHEN SUBMITTED.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED.
 PLEASE SEE THE PLANS DO SHOW SOME KIND OF LIGHTING
 PANEL, HOWEVER PLANS DO NOT SHOW ANY OVER RIDES, OVER
 RIDE LOCATIONS, SEPARATE SPACES CONTROLS, SCHEDULING,
 MAXIMUM TIMES ON DEVICES. ETC.
 PLEASE INDICATE IF TIME CLOCK FOR ANY OUTSIDE LIGHTING
 IS ASTRONOMICAL WITH MINIMUM 10HR BATTERY BACK UP.
 ** AS NO SYSTEM, DEVICES ETC WERE SUBMITTED FOR
 COMPLETE SYSTEM, A FULL REVIEW COULD NOT BE DONE AT
 THIS TIME.
  
 6) NOTE: PLEASE VERIFY NO OUTSIDE LIGHTS, PARKING ETC
 ARE SHOWN.
 FBC 106.1.2
  
 7) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 CIRCUITS IN PANEL SCHEDULE. PLEASE SEE 408.4 WHICH
 REQUIRES ALL CIRCUITS TO BE NOTED SPECIFIC TO EACH
 LOCATION IN WHICH THEY ARE FEEDING.
 FOR EXAMPLE: PLEASE SEE PANEL *B* WHICH INDICATES TWO
 DEDICATED SIGN CIRCUITS AS REQUIRED PER 600.5 HOWEVER
 PLEASE SEE PLANS AS BOTH SIGN CIRCUITS ARE NOTED ON THE
 SAME CIRCUIT WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SHOW HOW LOADS FOR SHOW WINDOWS WERE
 FIGURED INTO LOAD CALCULATIONS.
 220.43A
  
 9) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER IS
 CONSIDERED A CONTINUOUS LOAD AND LOAD SHOULD BE NOTED
 ACCORDINGLY.
  
 10) NOTE: PLEASE SEE THE MDP INDICATE A TWO POLE SINGLE
 PHASE FEED TO PANEL *B* YET BY THE CIRCUITING SHOWN ON
 MDP, THIS WOULD PLACE A HIGH-LEG ON PANEL *B* FEEDERS
 WHICH CONTAIN SINGLE POLE 120V CIRCUITS.
 PLEASE ADJUST.
 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR ANY NEW SERVICE
 EQUIPMENT. 110.9
 PLEASE BE AWARE OF NOTE ABOVE WITH RESPECT TO SERVICE
 PERMITTED AND ADJUSTMENTS NEEDED BASED ON SERVICE AS
 SHOWN.
  
 12) NOTE: PLEASE SEE 250.104 AS GAS METALLIC PIPES
 REQUIRE BONDING.
  
 13) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS ARE
 MISSING THE REQUIRED PRINTED NAME AND PRINTED LICENSE
 NUMBER OF SAID DESIGNER.
 FAC 61G1-16.004.
  
 14)NOTE: PLEASE SEE POSSIBLE BUILDING REVIEW COMMENTS
 WITH RESPECT TO EGRESS DOOR SWINGING INTO WHAT APPEARS
 TO EXIT ACCESS CORRIDOR.
 THIS IS ONLY NOTED BY THIS REVIEW AND IS NOT PLAN
 REVIEW NOTE.
  
 15) NOTE: PLEASE SEE 13-415.1.ABC.2.1 AND .2.2 FOR
 MISSING NOTES ON PLANS.
  
 16) NOTE: PLEASE BE SURE ADDRESSING AS APPLIED AND
 STATED ON PLANS COORDINATES. THIS HAS BEEN ROUTED TO
 ADDRESSING REVIEWER .
 AS APPLIEDTHE ADDRESS IS 2401-2405 N DIXIE, HOWEVER
 BASED ON COMPUTER AND PCN USED THIS ADDRESS IS 2409
 DIXIE HWY.
 PLEASE BE SURE ONCE ADDRESS IS CONFIRMED THE TITLE
 BLOCKS ARE CORRECTED TO SHOW APPLIED LOCATION WITH
 FINAL DETERMINED ADDRESS.
 FAC 61G1-16.004, 61G15-23.002
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-04-28 Cont ID  
Sent By mwennerg Date 2009-04-28 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2009-04-28 Time 14:24 Sent To E
Notes
2009-04-28 14:25:24SHEET E-3 STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2009-04-21 Cont ID  
Sent By mawillia Date 2009-04-21 Time 13:01 Rev Time 0.00
Received By mawillia Date 2009-04-21 Time 12:33 Sent To  
Notes
2009-04-21 12:37:49*****UNSAT*****
  
 REVISED PLAN SHEETS A-4, A-14, AND A-25 WERE STAMPED,
 INITIALED, AND DATED; ONLY SHEET E-3 ( WHICH WAS
 STAMPED IN THE ORIGINAL PLAN SET) WOULD NEED TO BE
 FIRE-STAMPED. THIS SHEET TO BE FIRE-STAMPED WHEN THE
 ELECTRICAL EXAMINER'S COMMENTS HAVE BEEN ADDRESSED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2009-02-26 Cont ID  
Sent By mawillia Date 2009-02-26 Time 11:30 Rev Time 0.00
Received By mawillia Date 2009-02-26 Time 11:09 Sent To  
Notes
2009-02-26 11:11:56*****UNSAT*****
  
 OF THE REVISED PLAN SHEETS E-2, E-3, E-5, P-1, P-3,
 P-4, AND M-1 THAT WERE SUBMITTED, ONLY SHEET E-3 (
 WHICH WAS STAMPED IN THE ORIGINAL PLAN SET( WOULD NEED
 TO BE FIRE-STAMPED. THIS SHEET TO BE FIRE-STAMPED WHEN
 THE OTHER EXAMINERS'S COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-08-11 Cont ID  
Sent By mawillia Date 2008-08-11 Time 14:34 Rev Time 0.00
Received By mawillia Date 2008-08-11 Time 14:04 Sent To B
Notes
2008-08-11 14:28:01*****APPROVED*****
  
 PLAN SHEETS A-2, A-4, A-14, A-25, AND E-3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-07-17 Cont ID  
Sent By mwennerg Date 2008-07-17 Time 09:41 Rev Time 0.00
Received By mwennerg Date 2008-07-17 Time 09:41 Sent To  
Notes
2008-07-17 09:42:49PLANS APPEAR TO BE CODE COMPLIANT BUT WILL REMAIN IN
 FAILED STATUS UNTIL SUBMITTAL FOR PERMIT APPLICATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-06-04 Cont ID  
Sent By mwennerg Date 2008-06-04 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2008-06-04 Time 13:44 Sent To  
Notes
2008-06-04 13:53:48***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED AND
 CORRECTED EXCEPT THE FOLLOWING:
  
 1) ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE AN
 ADDRESS OF 2401 NORTH DIXIE HIGHWAY AND THE MEP SHEETS
 SHOW 2409 NORTH DIXIE HIGHWAY.
  
 6) WORK SHALL COMPLY WITH NFPA 101, 2003 EDITION
 CHAPTER 38 FOR NEW BUSINESSES, NOT CHAPTER 36 WHICH IS
 MERCANTILE OCCUPANCIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 12:23 Sent To  
Notes
2008-04-07 14:04:30*****DENIED*****
  
 01.THE CORRECT ADDRESS, 2401 NORTH DIXIE HIGHWAY (NOT
 2401 - 2405), OF THE NEW PROJECTED SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.ON THE COVER PAGE, THE BUILDING SHOULD BE LOCATED
 BETWEEN 23RD STREET AND NORTHWOOD ROAD;NOT 24TH
 STREET AND 25TH STREET AS INDICATED ON THE SITE PLAN OR
 NW 24TH STREET AND 25TH STREET AS INDICATED ON THE
 LOCATION PLAN.
  
 03.PLEASE SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS NORTH DIXIE
 HIGHWAY.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN SIX INCHES IN HEIGHT AND NO LESS
 THAN ONE INCH IN WIDTH/STROKE.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.THE GUIDELINES OF CHAPTER 38 (NEW BUSINESS
 OCCUPANCIES) WILL BE USED.
  
 07.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 08.PROVIDE LIFE SAFETY / TRAVEL DISTANCE TO THE
 EXITS.
  
 09.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 10.IN REFERENCE TO THE REAR EXIT DOOR THAT LEADS TO
 AN EXIT ACCESS CORRIDOR, VERIFY THE FOLLOWING:A.) THE
 DOOR LEADING TO THE CORRIDOR SHALL BE AN APPROVED,
 LISTED, AND LABELED FIRE DOOR & ASSEMBLY IN ACCORDANCE
 WITH THEBREQUIREMENTS OF NFPA 80.(B) DURING ITS SWING
 , ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS
 THAN ONE-HALF THE REQUIRED WIDTH OF THE AISLE,
 CORRIDOR, A PASSAGEWAY, OR A LANDING.(C)THE ADDRESS
 NUMBER SHALL BE POSTED ON THE EXTERIOR DOOR OF THE
 SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 14:22 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 14:22 Sent To  
Notes
2009-03-04 14:24:01DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P-3 GAS PIPING DIAGRAM. PLEASE SHOW THE REQUIRED
 DRIP/SEDIMENT TRAP. SECTIONS 408.2 & 408.4.
  
 2. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54 &
 FBC-2004 FUEL GAS SECTION 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 13:10 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 13:10 Sent To E
Notes
2008-08-04 13:16:10****************PROVISO****************
 NOTE: PLAN REVIEW FOR THE GAS PIPING DIAGRAM ON SHEET
 P-3 UNDER FBC-2004 FUEL GAS TABLE 402.4(2) AND TWO
 COPIES OF MANUFACTURER SPECIFICATION SHEETS REQUIRED
 FOR THE 120,000 BTU DRYER CLEARLY INDICATING THE MAKE,
 MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABOATORY (EXAMPLES OF A
 LISTING= AGA, CSA, UL).
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-04-22 Cont ID  
Sent By dpalmer Date 2009-04-22 Time 11:52 Rev Time 0.00
Received By dpalmer Date 2009-04-22 Time 11:52 Sent To E
Notes
2009-04-22 11:52:55DVP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 14:53 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 14:53 Sent To  
Notes
2009-03-30 16:10:27TO "C37"

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 09:06 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 09:06 Sent To  
Notes
2009-02-02 09:06:36TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 11:50 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 11:50 Sent To B
Notes
2008-09-08 11:50:34TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 13:19 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 13:19 Sent To E
Notes
2008-07-30 13:20:23TO "DPALMER" DESK/RESUB--PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 14:11 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 14:11 Sent To  
Notes
2008-07-11 14:12:10TO "COMM" BD#6/PLANS ON RACK--2 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 11:49 Sent To  
Notes
2008-05-16 11:49:18TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-11 Cont ID  
Sent By jleech Date 2008-04-11 Time 08:52 Rev Time 0.00
Received By jleech Date 2008-03-05 Time 11:25 Sent To  
Notes
2008-03-05 11:27:34TO "COMM" BD#18--PROJECT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-04-27 Cont ID  
Sent By rregueir Date 2009-04-24 Time 09:37 Rev Time 0.00
Received By rregueir Date 2009-04-14 Time 11:50 Sent To B
Notes
2009-04-27 09:39:23WAS WAITING ON LETTER FROM ENGINEER REGARDING WIND
 RESISTANCE OF REVISED A/C EQUIPMENT. LETTER RECEIVED,
 REVIEWED BY BUILDING REVIEWER. PAGE M-2 PASSED.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2009-02-23 Cont ID  
Sent By rregueir Date 2009-02-23 Time 20:54 Rev Time 0.00
Received By rregueir Date 2009-02-23 Time 19:39 Sent To  
Notes
2009-02-23 20:54:45REVIEW #: 1ST REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISED PAGE M-1 OK AND STAMPED. HOWEVER, THIS REVIEW
 WILL REMAIN IN FAIL STAUS UNTIL THE FOLLOWING COMMENTS
 ARE ADDRESSED:
  
 1. CALCULATIONS PROVIDED BY A STRUCTURAL ENGINEER
 INDICATE THAT THE A/C ROOFTOP PACKAGE UNITS INSTALLED
 ON THIS PROJECT ARE "TEMPSTAR" WHILE THE EQUIPMENT
 SCHEDULE ON PAGE M-2 OF THE PERMIT SET OF PLANS CALLS
 FOR RHEEM EQUIPMENT TO BE INSTALLED. PLEASE REVISE THE
 EQUIPMENT SCHEDULE TO REFLECT THE EQUIPMENT WHICH WAS
 ACTUALLY INSTALLED IN ACCORDANCE WITH FBC-B 106.11 AND
 FBC-M 304.1.
  
 2. THE WIND RESISTANCE CAPABILITIES OF THE "TEMPSTAR"
 EQUIPMENT HAS NOT BEEN ADEQUATELY DEMONSTRATED.
 MECHANICAL EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE ANTICIPATED WIND PRESURES IN ACCORDANCE WITH
 FBC-M 301.13. THE STATEMENTS THAT WIND RESISTANCE
 CRITERIA HAVE NOT BEEN "ADOPTED" BY THE PALM BEACH
 COUNTY COMMISSION IS IRRELEVANT. WE ARE NOT IN THE
 JURISDICTION OF THE PALM BEACH COUNTY COMMISSION AND
 THE FLORIDA BUILDING CODE (FBC) IS A STATE WIDE
 MANDATED MINIMUM CODE. NO LOCAL JURISDICTION HAS THE
 AUTHORITY TO MAKE THE FBC MORE OR LESS STRINGENT. ALSO,
 THERE IS NO BASIS IN CODE FOR THE ENGINEER'S STATEMENT
 THAT ALL STRUCTURES UNDER 35 FEET IN HEIGHT ARE EXEMPT
 FROM WIND RESISTANCE REQUIREMENTS. ALL BUILDINGS,
 REGARDLESS OF HEIGHT, CONSTRUCTED IN THE STATE OF
 FLORIDA ARE SUBJECT TO THE WIND RESISTANCE PROVISIONS
 OF THE FBC. IN ORDER TO DEMONSTRATE CODE COMPLIANCE FOR
 THE EQUIPMENT BEING INSTALLED ON THIS PROJECT, PLEASE
 USE ONE OF THE FOLLOWING METHODS:
  
 A) PROVIDE SUPPORTING DOCUMENTATION FROM THE EQUIPMENT
 MANUFACTURER SHOWING THAT THESE UNITS ARE DESIGNED AND
 WILL WITHSTAND THE ANTICIPATED WIND PRESSURES AS
 CALCULATED IN ACCORDANCE WITH FBC-B SECTION 1609.
  
 B) PROVIDE A RATIONAL ANALYSIS OF THE CONSTRUCTION OF
 THE EQUIPMENT SHOWING THESE UNITS WILL WITHSTAND THE
 ANTICIPATED WIND PRESSURES AS CALCULATED IN ACCORDANCE
 WITH FBC-B SECTION 1609.
  
 FOR ADDITIONAL INFORMATION REGARDING WIND RESISTANCE
 REQUIREMENTS FOR MECHANICAL EQUIPMENT AND APPLIANCES,
 PLEASE SEE THE DECLARATORY STATEMENT FROM THE FLORIDA
 BUILDING COMMISSION DCA08-DEC205. A COPY IS ATTACHED TO
 THESE COMMENTS FOR YOUR CONVENIENCE.
  
 NOTE: DOCUMENTATION WAS PREVIOUSLY PROVIDED FOR THE
 RHEEM EQUIPMENT ORIGINALLY PROPOSED FOR THIS PROJECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-01 Cont ID  
Sent By rregueir Date 2008-08-01 Time 10:02 Rev Time 0.00
Received By rregueir Date 2008-08-01 Time 10:02 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-16 Cont ID  
Sent By rregueir Date 2008-07-16 Time 15:00 Rev Time 0.00
Received By rregueir Date 2008-07-16 Time 14:38 Sent To  
Notes
2008-07-16 15:00:02**PLAN REVIEW ONLY**
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE. ALL
 OUTSTANDING MECHANICAL REVIEW COMMENTS HAVE BEEN
 ADDRESSED. THE REVIEW WILL REMIAN IN FAIL STATUS
 PENDING SUBMISSION OF A PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By rregueir Date 2008-06-02 Time 15:39 Rev Time 0.00
Received By rregueir Date 2008-06-02 Time 14:19 Sent To  
Notes
2008-06-02 15:39:41REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 5: OK
  
 6. RTU ATTACHMENT DETAIL AND CALCULATIONS HAVE BEEN
 RECEIVED AND WILL BE REVIEWED BY THE BUILDING PLAN
 REVIEWER. HOWEVER, NO INFORMATION WAS PROVIDED
 REGARDING THE ROOFTOP APPLIANCES THEMSELVES. PROVIDE
 DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING
 RTUS THEMSELVES ARE DESIGNED TO RESIST ANTICIPATED WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 7 THROUGH 9: OK
  
 10. NOTE # 3 ON RTU SCHEDULE CALLS FOR MANUAL DAMPER ON
 OUTSIDE AIR INTAKE. FBC 13-409.1.ABC.3.3 CALLS FOR
 MOTORIZED DAMPERS FOR OUTSIDE AIR INTAKES IN EXCESS OF
 300 CFM. THESE DAMPERS SHALL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES SERVED ARE NOT IN USE IN
 ACCORDANCE WITH THIS SECTION. A MANUAL DAMPER MAY BE
 USED FOR BALANCING BUT THE MOTORIZED DAMPER IS REQUIRED
 FOR COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION
 CODE.
  
 11. OK
  
 12. A) THE WRITTEN RESPONSE FROM THE ENGINEER STATES,
 ?ENERGY CALCS AND LOAD CALCS HAVE BEEN PROVIDED.? NO
 ENERGY CALCULATIONS COULD BE FOUND WITH THIS SUBMITTAL.
 PROVIDE ENERGY CALCULATIONS AS PREVIOUSLY REQUESTED.
 NOTE: WHEN PROVIDING ENERGY CALCULATION, BE SURE TO
 PROVIDE METHOD B OR C COMPLIANCE FORMS AS THIS IS
 NEITHER NEW CONSTRUCTION NOR AN ADDITION. RENOVATED
 COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE (SEE
 SECTION 202 OF CHAPTER 13 FOR A DEFINITION OF A
 RENOVATION), COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS
 CONTAINED IN FORM 400C OR WITH METHOD B OF SUBCHAPTER
 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER
 HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 B) THE SYSTEM SIZING SUMMARY PROVIDED INDICATES A
 DESIGN OUTDOOR AIRFLOW OF 500 CFM PER UNIT. THIS DOES
 NOT CORRESPOND WITH THE OUTSIDE AIR CALCULATIONS SHOWN
 ON PG M-1. PROVIDE A SUMMARY USING VALUES WHICH
 CORRESPOND WITH THE CONDITIONS SHOWN ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By rregueir Date 2008-03-26 Time 14:17 Rev Time 0.00
Received By rregueir Date 2008-03-26 Time 09:17 Sent To  
Notes
2008-03-26 14:17:22REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENOED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-1: SIZE OF RETURN GRILLS IN WAXING ROOM AND AT
 REAR ENTRANCE ABOVE WATER FOUNTAINS ARE MISSING.
 CORRECT AND RESUBMIT. FBCM 603.1
  
 2. M-1: SIZE OF TRUNK LINE FEEDING STAFF LOUNGE AND
 OFFICE IS MISSING. PLEASE CORRECT AND RESUBMIT. FBCM
 603.1
  
 3. M-1: A SPACE-BY-SPACE ANALYSIS OF THE VENTILATION
 REQUIREMENTS OF THE PROPOSED SPACES INDICATES THAT THE
 OUTSIDE AIR PROVIDED IS INADEQUATE BASED ON FBCM TABLE
 403.3. WITH EACH SPACE ADDED UP THE APPROXIMATE TOTAL
 IS 1675 CFM. THE TOTAL MAY ACTUALLY BE HIGHER BASED ON
 THE FACT THAT A COMMON VENTILATION SYSTEM IS BEING
 USED. PLEASE PROVIDE OUTSIDE AIR CALCULATIONS BASED ON
 THE OCCUPANT LOAD AS LISTED IN THE SPECIALTY SHOPS-
 BEAUTY OCCUPANCY IN TABLE 403.3. THIS WOULD REQUIRE AN
 OCCUPANT LOAD OF 25 PEOPLE PER 1000SF OF FLOOR AREA
 (FOR THE ENTIRE FLOOR AREA) AND A VENTILATION TARE OF
 25 CFM PER PERSON.
  
 4. M-1: THE NAIL SALON PORTION OF THE SPACE IS SUBJECT
 TO FOOTNOTE B OF TABLE 403.3, WHICH PROHIBITS AIR
 SUPPLIED TO THIS SPACE FROM BEING RECIRCULATED IN
 ACCORDANCE WITH FBCM 403.2.1(3). HOW WILL AIR FROM THIS
 SPACE BE PREVENTED FROM RECIRCULATING WITH
 PARTIAL-HEIGHT PARTITIONS AND A COMMON RETURN? ALSO,
 ACCORDING TO THE FLOOR PLAN, 730 CFM OF SUPPLY IS
 PROVIDED IN THIS LOCATION WITH ONLY 400 CFM OF EXHAUST.
 ALL AIR SUPPLIED TO THIS SPACE SHALL BE EXHAUSTED TO
 PREVENT RECIRCULATION IN ACCORDANCE WITH FBCM
 403.2.1(3).
  
 5. M-1: FLOOR PLAN SHOWS DUCT SMOKE DETECTORS IN SUPPLY
 RISERS ABOVE THE STAFF LOUNGE AND PROCESSING ROOMS.
 THESE ROOMS SHAVE HARD GYPSUM PANEL CEILINGS AS SHOWN
 ON PG A-4. ACCESS SHALL BE PROVIDED TO SMOKE DETECTORS
 FOR INSPECTION AND MAINTENANCE IN ACCORDANCE WITH FBCM
 606.3.
  
 6. M-2: MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS
 THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCB
 CHAPTER 16 PER FBCM 301.13. PROVIDE WIND LOAD
 CALCULATIONS FOR APPLIANCE ATTACHMENT TO STRUCTURE TO
 SUPPORT THE ATTACHMENT DETAIL FOR BUILDING PLAN REVIEW.
 ALSO, PROVIDE DATA FROM THE MANUFACTURER OF THE OUTDOOR
 APPLIANCES (RTU?S) SHOWING THEY HAVE BEEN DESIGNED AND
 TESTED TO WITHSTAND ANTICIPATED WIND LOADS IN
 ACCORDANCE WITH FBCM 301.13 AND FBCB SECTION 1609.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1
  
 8. PROVIDE AUXILIARY DRAIN PROTECTION IN ACCORDANCE
 WITH FBCM 307.2.3. A WATER LEVEL DETECTION DEVICE (SUCH
 AS A FLOAT SWITCH) INSTALLED INTERNALLY ON THE PRIMARY
 DRAIN PAN WILL MEET THIS REQUIREMENT.
  
 9. PG M-2: GENERAL NOTE #17, PLEASE REFERENCE THE
 CORRECT CODE. THIS PROJECT IS BEING REVIEWED UNDER THE
 2004 FLORIDA BUILDING CODE W/ 2007 AMENDMENTS.
  
 10. PROVIDE SHUTOFF DAMPER CONTROLS ON OUTSIDE AIR AND
 EXHAUST IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3.
  
 11. PROVIDE AN AIR BALANCE SCHEDULE TO SHOW THE
 MECHANICAL SYSTEMS ARE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.2.
  
 12. ENERGY CALCULATIONS WERE NOT PROVIDED. RENOVATED
 COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE (SEE
 SECTION 202 OF FBCB CHAPTER 13), COMPLY WITH THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN FORM 400C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR INSULATION, HVAC
 SYSTEMS, LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED IN
 ACCORDANCE WITH FBCB 13-101.1.3. PROVIDE ENERGY
 CALCULATIONS TO DEMONSTRATE COMPLIANCE. SYSTEM SIZING
 MAY NEED TO BE REDONE BASED ON ENERGY CALCULATIONS AND
 RECALCULATED OUTSIDE AIR RATES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-04-27 Cont ID  
Sent By kstevens Date 2009-04-27 Time 14:42 Rev Time 0.00
Received By kstevens Date 2009-04-27 Time 14:42 Sent To  
Notes
2009-04-27 14:58:30REVISIONS OK -- SHTS P-1, P-2, P-3 & P-4

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 14:10 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 14:10 Sent To  
Notes
2009-03-04 14:21:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P-3 SANITARY RISER DIAGRAM. PLEASE INDICATE THE
 VENT TERMINATION POINT FOR THE P-3 SINKS BY THE P-4
 FIXTURES. SECTION 901.1.
  
 2. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN AT THE P-3 SINKS BY THE P-4 FIXTURES.
 SECTIONS 106.1.1 & 601.1.
  
 3. SHT P-3 WATER PIPING DIAGRAM. AIR CHAMBERS ARE NOT
 APPROVED. (SHOWN AT ALL FIXTURES). SECTION 604.9 &
 PDI-WH 201. PLEASE DELETE.
  
 4, SHT P-3 WATER PIPING DIAGRAM SHOWS TWO 1" LINES &
 TWO 3/4" INCH LINES WHERE THERE ARE ONLY 3 WATER LINES.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 5. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. SINK IN THE NAIL SPA IS MOVED TO THE FAR
 SIDE OF THE ROOM, BUT THE RISER WAS NOT REVISED TO
 REFLECT CHANGE. SECTIONS 106.1.1 & 601.1. PLEASE
 CORRELATE.
  
 5. SHT P-3 GAS PIPING DIAGRAM. PLEASE SHOW THE REQUIRED
 DRIP/SEDIMENT TRAP. SECTIONS 408.2 & 408.4.
  
 6. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54 &
 FBC-2004 FUEL GAS SECTION 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 14:09 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 14:09 Sent To  
Notes
2009-03-04 14:10:02REVISIONS OK -- SHTS P-1 & P-4.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 13:09 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 13:09 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-07-15 Cont ID  
Sent By mperson Date 2008-07-15 Time 15:41 Rev Time 0.00
Received By mperson Date 2008-07-15 Time 15:41 Sent To  
Notes
2008-07-15 15:46:27**PLAN REVIEW ONLY**
 PLUMBING AND GAS PLANS ARE CODE COMPLIANT AND CAN BE
 STAMPED WHEN A CONTRACTOR MAKES AN APPLICATION FOR
 PERMIT. PERMIT MUST BE ISSUED BEFORE DECEMBER 31, 2008
 OR A REREVIEW UNDER THE 2007 CODES WILL BE REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By jleech Date 2008-05-20 Time 09:01 Rev Time 0.00
Received By jleech Date 2008-05-20 Time 07:59 Sent To  
Notes
2008-05-20 09:07:22PLUMBING PLANS ARE CODE COMPLIANT AND CAN BE STAMPED
 WHEN A CONTRACTOR MAKES APPLICATION. PERMIT MUST BE
 ISSUED BEFORE OCTOBER 1, 2008 OR WILL BE REREVIEW UNDER
 THE 2007 CODES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By jleech Date 2008-04-11 Time 07:52 Rev Time 0.00
Received By jleech Date 2008-04-09 Time 14:19 Sent To  
Notes
2008-04-11 08:46:22DENIED;
 1. ADD A DEMO NOTE; NO DEAD ENDS PERMITED IN THE
 DRAINAGE SYSTEM LONGER THAN 2 FEET, INSPECTION
 REQUIRED.
 2. BOTH BATHROOMS ARE REQUIRED TO MEET ACCESSIBILITY
 REQUIREMENTS. SEE FBC-BUILDING CHAPTER 11, SECTION
 11-4.1.2(6). MINUMUM WIDTH WOULD BE 5' 3", 18" TO
 CENTER OF W/C, 30" FROM CENTER OF W/C TO CENTER OF
 LAV., AND 15" FROM CENTER OF LAV TO WALL.
 3. STAFF LOUNGE SINKS TO MEET ACCESSIBILITY
 REQUIREMENTS, SEE SECTIONS 11-4.24.1 THRU 11-4.24.7,
 SHOW DETAIL DRAWING WITH ALL REQUIRED DIMENSIONS AND
 REQUIREMENTS.
 4. SHOW DETAIL OF DRINKING FOUNTAIN WITH ALL REQUIRED
 MEASUREMENTS, TO MEET CODE SECTIONS 11-4.15.1 THRU
 11-4.15.5.
 5. SHOW CLEAR FLOOR SPACE AT BREAK SINK ON FLOOR PLAN
 PAGE A-4.
 6. SHOW DETAIL OF ELECTRIC WATER HEATER, HOW HUNG,
 EXPANSION CONTROL, SECTION 607.3, HEATER PAN AND DRAIN,
 SECTION 504.7.1 AND 504.7.2.
 7. PLEASE REMOVE ALL AIR CHAMBER SYMBOLS FROM WATER
 RISER DIAGRAM, AIR CHAMBERS ARE NOT RECOGNIZED IN THE
 FBC-PLUMBING, SHOCK ARRESTORS ONLY AS REQUIRED BY
 SECTION 604.9.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-01 Cont ID  
Sent By kdfreema Date 2008-08-01 Time 16:41 Rev Time 0.00
Received By kdfreema Date 2008-08-01 Time 16:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-07-15 Cont ID  
Sent By kdfreema Date 2008-07-15 Time 10:12 Rev Time 0.00
Received By kdfreema Date 2008-07-15 Time 10:12 Sent To  
Notes
2008-07-15 10:13:57PLANS MEET ALL ZONING REQUIREMENTS. STATUS WILL BE
 CHANGED TO PASSED WHEN FULL PERMIT FEES ARE PAID
 ASSUMING NO CHANGES ARE MADE TO THE SHEETS STAMPED BY
 ZONING.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By kdfreema Date 2008-06-03 Time 15:00 Rev Time 0.00
Received By kdfreema Date 2008-06-03 Time 15:00 Sent To  
Notes
2008-06-03 16:00:00***FAILED***
  
 PER SECTION 94-213(A)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE MINIMUM FINISHED FLOOR TO
 FINISHED CEILING HEIGHT IS 12 FEET. THE PORTION OF THE
 SPACE WITH EXPOSED TRUSSES MEETS THE REQUIREMENTS,
 HOWEVER, ALL AREAS WITH PROPOSED DRYWALL CEILINGS DO
 NOT COMPLY AS THEY ARE BELOW THE 12 FOOT MINIMUM. THE
 CEILINGS COULD BE MODIFIED TO MEET THE 12-FOOT
 REQUIREMENT, OR A VARIANCE COULD BE REQUESTED. THE
 VARIANCE PROCESS, HOWEVER, WOULD ADD APPROXIMATELY 4 TO
 5 MONTHS TO THE PERMITTING PROCESS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.