| 2008-03-08 18:47:36 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE KNOW AT THIS TIME THE CORRECT ADDRESS |
| | IS NOT AS APPLIED OR AS STATED ON PLANS. THELOCATION IS |
| | IN QUESTION AND THIS REVIEW HAS FORWARDED INFORMATION |
| | TO ADDRESSING REVIEWER FOR CORRECTIONS AND ADDRESS TO |
| | BE CORRECTED UNDER ACTUAL PCN. |
| | THIS IS A NEW FREE-STANDING STRUCTURE LOCATED ON A PCN |
| | OTHER THAN AS APPLIED. PLEASE KNOW THE PCN BASED ON |
| | PAPA AERIALS AND BASED ON THE LOCATION SHOWN ON PLANS |
| | SUBMITTED PLACES THIS IN PCN 74434321130020040. |
| | THIS WILL REQUIRE A NEW ADDRESS TO THIS STRUCTURE. |
| | PLEASE BE AWARE THIS STRUCTURE IS ACTUALLY BEING FED |
| | FROM A NEW PROPOSED SERVICE AND METER. PLEASE ALSO SEE |
| | PRINT OUT THIS REVIEWER HAS ATTACHED TO NOTES FOR |
| | AERIAL. |
| | |
| | 2) NOTE: PLEASE BE SURE THE ADOPTED CODES PER FS 553.73 |
| | AND FBC ARE REQUIRED TO BE STATED ON PLANS FOR RELEVANT |
| | DESIGN. |
| | PLEASE BE SURE THE FOLLOWING IS STATED ON PLANS FOR |
| | THIS REVIEWER. |
| | 2004 FBC W/2007 REVISIONS. |
| | |
| | 3) NOTE: PLEASE SEE COVER SHEET SPECIFICALLY STATES |
| | THERE IS TO BE A SHEET M-1 YET NO M SHEETS ARE IN |
| | SETS. |
| | PLEASE SEE THIS SAME COVER SHEET STATES THERE IS ONE |
| | E-1 YET THE SETS CONTAIN TWO E-1 SHEETS IN BOTH SETS. |
| | PLEASE COORDINATE ALL SHEETS AND ADJUST COVER SHEETS AS |
| | NEEDED ALONG WITH ADDRESSING AS STATED IN NOTE #1 |
| | ABOVE. |
| | FAC 61G1-16.004, FBC 106.1, 106.5 ETC |
| | |
| | 4) NOTE:PLEASE COMPLETE AL CIRCUITING AND COORDINATE |
| | WITH THE PANEL SCHEDULE AS SHOWN. |
| | MORE SPECIFICALLY 700.12 FOR EM LT. (EVEN AS NOTED). |
| | |
| | 5) NOTE: PLEASE SEE PLANS FOR BUILDING DOES NOT SHOW |
| | THE LOCATION OF THE METER CAN AS SHOWN ON RISER. |
| | PLEASE COMPLETE LOCATION. |
| | 110.26 |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE RISER IS MISSING THE REQUIRED |
| | EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF |
| | DISCONNECT AS REQUIRED PER 250.24, 250.110, 250.122. |
| | |
| | 7) NOTE: PLEASE CLARIFY RISER WHICH SHOWS THE GROUNDING |
| | ELECTRODE CONDUCTOR TO A METAL CWP YET THERE IS NO |
| | PLUMBING WATER RISER SHOWING ANY CWP OR WATER SYSTEM TO |
| | THIS STRUCTURE? |
| | PLEASE VERIFY. |
| | 250.50 |
| | |
| | 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR SERVICE |
| | EQUIPMENT AND MAIN. PANEL SCHEDULE DOES SHOW A PANEL |
| | RATING OF 4200 HOWEVER THIS OFFICE/REVIEWER KNOWS OF NO |
| | EQUIPMENT WHICH EXISTS ON THE MARKET AS OF THIS REVIEW |
| | WHICH IS 4200. PLEASE SUBMIT DOCUMENTS ON THIS OR |
| | VERIFY THE RATING. |
| | 90.7, 110.3 |
| | |
| | 9) NOTE: PLEASE SEE 13-400.3.A, 13-415.2,NEEDS ENERGY |
| | CALCULATIONS |
| | NEED NOTES ON PLANS PER 13-413.1.ABC.2.1 AND .2.2. |
| | |
| | 10) NOTE: PLEASE CORRELATE RISER AND PANEL. PANEL SHOWS |
| | 3-#3 FOR FEEDERS YET THE RISER SHOWS 3-1/0? |
| | PLEASE SEE 240.4, 310.16. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 11) NOTE: PLEASE SEE THE D IN SQUARE BOX ON PLANS IS |
| | NOT LISTED ON THE SYMBOL LEGEND. THIS CAN BE ASSUMED |
| | HOWEVER THIS NEEDS TO BE LISTED PER DESIGNER. |
| | FBC 106.1.2 ADDITIONAL INFORMATION. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |