Plan Review Details - Permit 08030070
Plan Review Stops For Permit 08030070
Review Stop AD ADDRESSING
Rev No 2 Status F Date 2008-03-19 Cont ID  
Sent By lursu Date 2008-03-19 Time 13:05 Rev Time 0.00
Received By lursu Date 2008-03-19 Time 13:05 Sent To  
Notes
2008-03-19 13:08:46THE LAST REVIEW WAS DONE BASED ON THE INFORMATION THAT
 A KIOSK WILL BE INSTALLED AT THE CORNER OF S ROSEMARY
 AVE & HIBISCUS ST .THE SITE ADDRESS FOR THE PROPERTY
 WAS ASSIGNED TO HIBISCUS ST ,BUT REVIEWING THE SITE
 PLANS THE KIOSK IS NOW A CONCRETE STRUCTURE WITH A DOOR
 FACING A SIDEWALK .PLEASE CLARIFY THE ORIENTATION OF
 THIS DOOR.THE SITE ADDRESS WAS CHANGED TO 620 S
 ROSEMARY AVE .
  
  
 QUESTIONS/COMMENTS :
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-03-10 Cont ID  
Sent By lursu Date 2008-03-10 Time 12:07 Rev Time 0.00
Received By lursu Date 2008-03-10 Time 12:07 Sent To  
Notes
2008-03-10 12:09:54BASED ON THE SITE PLANS THE LOCATION OF WORK ISAT THE
 SE CORNER OF HIBSICUS ST & S ROSEMARY AVE IN THE COMMON
 AREA .THE COMMON AREA WAS ASSIGNED WITH THE ADDRESS OF
 550 HIBISCUS ST .
  
 QUESTIONS/COMMENTS :
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 17:26 Rev Time 0.00
Received By shill Date 2008-03-07 Time 17:26 Sent To  
Notes
2008-03-07 17:31:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 2.DECLARE TOTAL SF AREA OF THIS PROPOSED IMPROVEMENT.
  
  
 3.IMPACT PROTECTION REQUIRED, FBC1609.1.4.USE OF
 REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES
 APPROVAL FROM THE BUILDING OFFICIAL.IF YOU PROPOSE TO
 USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE INSTALLATION
 PLAN, SEE ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT
 APPROVALS AND COMPLETE AN INSTALLATION SCHEDULE.
  
 4.AN OUTSWING DOOR PRODUCT APPROVAL WAS SUBMITTED,
 INSWING SHOWN ON THE PLAN.PLEASE RESOLVE
 INCONSISTENCY.
  
 5.PROVIDE ROOF TILE FOAM ADHESIVE PRODUCT APPROVAL,
 FAC9B72.
  
 6.PROVIDE LOUVER PRODUCT APPROVALS, FAC9B72 AND
 SPECIFY DESIGN PRESSURES.
  
 7.N/A (NO IMPACT FEES DUE PER GWEN/WILLY SWOPE).
  
 8.PLEASE DECLARE GOVERNING CODE, INCLUDING 2007
 SUPPLEMENTS/REVISIONS.
  
 9.PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 10. PROVIDE A SITE PLAN WHICH SHOWS DISTANCE TO
 PROPERTY LINES AND ASSUMED PROPERTY LINES.SHOW
 COMPLIANCE WITH FBC TABLE 602.
  
 11. SHOW ORIENTATION OF BUILDING ON EITHER THE FLOOR
 PLAN OR ELEVATIONS.NORTH IS NOT LABELED ON ANYTHING
 OTHER THAN THE SITE PLAN, WHICH DOES NOT SHOW ENOUGH
 DETAIL TO SHOW THE BUILDING ORIENTATION.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 18:47 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 18:46 Sent To  
Notes
2008-03-08 18:47:36** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW AT THIS TIME THE CORRECT ADDRESS
 IS NOT AS APPLIED OR AS STATED ON PLANS. THELOCATION IS
 IN QUESTION AND THIS REVIEW HAS FORWARDED INFORMATION
 TO ADDRESSING REVIEWER FOR CORRECTIONS AND ADDRESS TO
 BE CORRECTED UNDER ACTUAL PCN.
 THIS IS A NEW FREE-STANDING STRUCTURE LOCATED ON A PCN
 OTHER THAN AS APPLIED. PLEASE KNOW THE PCN BASED ON
 PAPA AERIALS AND BASED ON THE LOCATION SHOWN ON PLANS
 SUBMITTED PLACES THIS IN PCN 74434321130020040.
 THIS WILL REQUIRE A NEW ADDRESS TO THIS STRUCTURE.
 PLEASE BE AWARE THIS STRUCTURE IS ACTUALLY BEING FED
 FROM A NEW PROPOSED SERVICE AND METER. PLEASE ALSO SEE
 PRINT OUT THIS REVIEWER HAS ATTACHED TO NOTES FOR
 AERIAL.
  
 2) NOTE: PLEASE BE SURE THE ADOPTED CODES PER FS 553.73
 AND FBC ARE REQUIRED TO BE STATED ON PLANS FOR RELEVANT
 DESIGN.
 PLEASE BE SURE THE FOLLOWING IS STATED ON PLANS FOR
 THIS REVIEWER.
 2004 FBC W/2007 REVISIONS.
  
 3) NOTE: PLEASE SEE COVER SHEET SPECIFICALLY STATES
 THERE IS TO BE A SHEET M-1 YET NO M SHEETS ARE IN
 SETS.
 PLEASE SEE THIS SAME COVER SHEET STATES THERE IS ONE
 E-1 YET THE SETS CONTAIN TWO E-1 SHEETS IN BOTH SETS.
 PLEASE COORDINATE ALL SHEETS AND ADJUST COVER SHEETS AS
 NEEDED ALONG WITH ADDRESSING AS STATED IN NOTE #1
 ABOVE.
 FAC 61G1-16.004, FBC 106.1, 106.5 ETC
  
 4) NOTE:PLEASE COMPLETE AL CIRCUITING AND COORDINATE
 WITH THE PANEL SCHEDULE AS SHOWN.
 MORE SPECIFICALLY 700.12 FOR EM LT. (EVEN AS NOTED).
  
 5) NOTE: PLEASE SEE PLANS FOR BUILDING DOES NOT SHOW
 THE LOCATION OF THE METER CAN AS SHOWN ON RISER.
 PLEASE COMPLETE LOCATION.
 110.26
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE RISER IS MISSING THE REQUIRED
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT AS REQUIRED PER 250.24, 250.110, 250.122.
  
 7) NOTE: PLEASE CLARIFY RISER WHICH SHOWS THE GROUNDING
 ELECTRODE CONDUCTOR TO A METAL CWP YET THERE IS NO
 PLUMBING WATER RISER SHOWING ANY CWP OR WATER SYSTEM TO
 THIS STRUCTURE?
 PLEASE VERIFY.
 250.50
  
 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR SERVICE
 EQUIPMENT AND MAIN. PANEL SCHEDULE DOES SHOW A PANEL
 RATING OF 4200 HOWEVER THIS OFFICE/REVIEWER KNOWS OF NO
 EQUIPMENT WHICH EXISTS ON THE MARKET AS OF THIS REVIEW
 WHICH IS 4200. PLEASE SUBMIT DOCUMENTS ON THIS OR
 VERIFY THE RATING.
 90.7, 110.3
  
 9) NOTE: PLEASE SEE 13-400.3.A, 13-415.2,NEEDS ENERGY
 CALCULATIONS
 NEED NOTES ON PLANS PER 13-413.1.ABC.2.1 AND .2.2.
  
 10) NOTE: PLEASE CORRELATE RISER AND PANEL. PANEL SHOWS
 3-#3 FOR FEEDERS YET THE RISER SHOWS 3-1/0?
 PLEASE SEE 240.4, 310.16.
 FBC 106.1.2 FOR COORDINATION.
  
 11) NOTE: PLEASE SEE THE D IN SQUARE BOX ON PLANS IS
 NOT LISTED ON THE SYMBOL LEGEND. THIS CAN BE ASSUMED
 HOWEVER THIS NEEDS TO BE LISTED PER DESIGNER.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By mawillia Date 2008-03-19 Time 13:58 Rev Time 0.00
Received By mawillia Date 2008-03-19 Time 12:12 Sent To B1
Notes
2008-03-19 12:38:59*****DENIED*****
  
  
 1.THE ADDRESS SHOWN ON THE APPLICATION, 700 SOUTH
 ROSEMARY, DOES NOT CORRESPOND WITH THE ADDRESS SHOWN IN
 OUR PERMITTING SYSTEM (550 HIBISCUS STREET). FOR
 ADDRESSING CONCERNS OR MATTERS, CONTACT LILI URSU AT
 561-822-1239.
  
 2.THE ADDRESS OF THE SCOPE OF WORK LOCATION SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.CORRECT THE FOLLOWING ON SHEET A-1:*MISSPELLING
 OF ROSMARY, SHOULD BE ROSEMARY UNDER CITY PLACE KIOSK;
 *THE ZIP CODE SHOULD BE 33401 NOT 33405 AS LISTED.
  
 4.AMEND NOTE 2 ON SHEET A-1 TO READ:THE SCOPE OF
 WORK SHALL NOT INTERFERE/HINDER ACCESS TO OR EGRESS
 FROM THE SAID PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS, ALLEYS, FIRELANES, ETC.).
  
 5.DIRECTION ORIENTATION (NORTH, SOUTH, EAST, WEST)
 NEEDED FOR THE EXTERIOR ELEVATIONS ON SHEET A-2.
  
 6.SHOW/DIPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION WHICH FRONTS SOUTH ROSEMARY AVENUE.
  
 7.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 8.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 9.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-19 Cont ID  
Sent By mawillia Date 2008-03-19 Time 12:12 Rev Time 0.00
Received By mawillia Date 2008-03-05 Time 12:40 Sent To  
Notes
2008-03-05 12:42:21TO "COMM" BD#25--EXPEDITED--

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By rregueir Date 2008-03-17 Time 13:14 Rev Time 0.00
Received By rregueir Date 2008-03-17 Time 10:54 Sent To  
Notes
2008-03-17 13:14:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ARCHITECTURAL PLANS REFER TO PAGE M-1 FOR MECHANICAL
 DETAILS. NO PAGE M-1 WAS FOUND IN PLANS. HOWEVER, THERE
 WERE TWO E-1 PAGES, ONE OF WHICH APPEARS TO BE INTENDED
 FOR MECHANICAL. PLEASE CORRECT SHEET NUMBERING AND
 REFERENCES ON PLANS.
  
 2. PLANS DO NOT SHOW ANY MEANS OR LOCATION FOR
 CONDENSATE DISPOSAL. CONDENSATE FROM ALL COOLING COILS
 AND EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN
 OUTLET TO AN APPROVED PLACE OF DISPOSAL. CONDENSATE
 SHALL NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS
 SO AS TO CAUSE A NUISANCE IN ACCORDANCE WITH FBCM
 307.2.1. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL
 ON PLANS TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 3. IS THIS PTAC UNIT CONSTRUCTED AND WITH ATTACHMENT
 DETAILS TO WITHSTAND ANTICIPATED WIND PRESSURES?
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING PER FBCM 301.13. PROVIDE
 TESTING OF APPLIANCE AND ATTACHMENT DETAIL TO
 DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By eschneid Date 2008-03-17 Time 17:03 Rev Time 0.00
Received By eschneid Date 2008-03-17 Time 17:03 Sent To  
Notes
2008-03-17 17:32:06FAILED
  
 1) THIS BUILDING REQUIRES APPROVAL OF A MINOR PLANNED
 DEVELOPMENT AMENDMENT.NOTE:IT SHALL CONFORM TO THE
 CITYPLACE MASTER DESIGN GUIDELINES.
  
 2) A SURVEY AND SITE PLAN FOR THE NEW BUILDING, SHOWING
 SET BACK DIMENSIONS FROM ALL BUILDINGS AND THE
 RIGHT-OF-WAY.
  
 3) SHEET A-1 - THE COLUMNS SHOULD BE FILLED WITH
 "CONCRETE".
  
 4) SHEET A-2 - ALL ELEVATIONS SHALL BE LABELED FOR
 WHICH SIDE THEY ARE.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.