Plan Review Details - Permit 08030060
Plan Review Stops For Permit 08030060
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 09:08 Rev Time 0.00
Received By shill Date 2008-05-29 Time 09:08 Sent To  
Notes
2008-05-29 09:08:36REVISED CALCULATIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-07 Cont ID  
Sent By shill Date 2008-05-05 Time 16:45 Rev Time 0.00
Received By shill Date 2008-05-05 Time 16:45 Sent To  
Notes
2008-05-07 16:10:45CALCULATIONS OK PER ENGINEER
  
 PROVISO - SUBMIT NEW CALCULATIONS BEFORE FINAL
  
2008-05-05 16:50:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE IMPORTANCE FACTOR WAS INCLUDED IN WIND DESIGN
 CRITERIA AS REQUESTED, BUT THE CALCULATIONS SHOW AN
 IMPORTANCE FACTOR OF 1.0 (RATHER THAN THE REQUIRED
 1.15).SEE THE CABINET DRAWINGS, ALSO OTHER
 CALCULATIONS.AS DISCUSSED, NEW CALCULATIONS CAN BE A
 PROVISO ITEM IF REQUESTED BUT THE ENGINEER IS TO
 CONFIRM THAT PLANS AS DRAWN COMPLY WITH THE 1.15
 REQUIREMENT AND THE ENGINEER IS TO REQUEST THIS AS A
 PROVISO ITEM.THIS CAN BE REQUESTED BY TELEPHONE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 14:29 Rev Time 0.00
Received By shill Date 2008-04-29 Time 14:28 Sent To  
Notes
2008-04-29 14:33:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN
 GOVERNING CODE.
  
 SEE OTHER REVIEWS WHICH CLARIFY WHY THIS IS REQUIRED.
 RESPONSE LETTER STATES THAT IT WAS ADDRESSED (EACH
 REVIEW), AND LANGUAGE REMAINS THE SAME.
  
 3.ADDRESSED.
  
 4.ADDRESSED.PLEASE KEEP THE HILTI FIRESTOP SPEC
 SHEET AS A PART OF THE PERMIT PACKAGE.
  
 NEW COMMENT:
  
 5.WHEN ADDRESSING COMMENT #1, ALSO INCLUDE IMPORTANCE
 FACTOR (1.15) AND BUILDING CLASSIFICATION FBC TABLE
 1604.5. IF NECESSARY, REVISE CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-15 Cont ID  
Sent By shill Date 2008-04-15 Time 15:58 Rev Time 0.00
Received By shill Date 2008-04-15 Time 15:58 Sent To  
Notes
2008-04-15 17:14:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN
 GOVERNING CODE.
  
 PLEASE ADD "2007 REVISIONS/SUPPLEMENTS" TO GOVERNING
 CODE.THIS ESTABLISHES WHICH VERSION OF THE FBC2004 IS
 TO BE USED ON THIS JOB AS IT HAS BEEN REVISED EACH
 YEAR, AND ON A DIFFERENT DATE EACH YEAR.
  
 3RD REVIEW, RESPONSE LETTER STATES THAT THIS WAS DONE
 BUT LANGUAGE IS STILL THE SAME; STATES "ALL SUBSEQUENT
 ADOPTED AMENDMENTS" RATHER THAN 2007
 REVISIONS/SUPPLEMENTS.AS STATED, THIS IS ESTABLISHED
 BY APPLICATION DATE AND NEEDS TO BE INCORPORATED INTO
 THE PLAN.NOTE THAT THIS IS STILL SHOWN AS REVISION 1,
 SAME AS PREVIOUSLY SUBMITTED.
  
 3.THE INDEX SHEET WAS ADDED TO THE CALCULATIONS.
 PLEASE INCLUDE CERTIFICATE OF AUTHORIZATION NUMBER
 FAC61G15-23.002.
  
 4.ADDRESSED.PLEASE KEEP THE HILTI FIRESTOP SPEC
 SHEET AS A PART OF THE PERMIT PACKAGE.
  
 NEW COMMENT:
  
 5.SEE ZONING COMMENT.APPROVAL IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 14:41 Rev Time 0.00
Received By shill Date 2008-04-01 Time 14:41 Sent To  
Notes
2008-04-01 14:46:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN
 GOVERNING CODE.
  
 PLEASE ADD "2007 REVISIONS/SUPPLEMENTS" TO GOVERNING
 CODE.THIS ESTABLISHES WHICH VERSION OF THE FBC2004 IS
 TO BE USED ON THIS JOB AS IT HAS BEEN REVISED EACH
 YEAR, AND ON A DIFFERENT DATE EACH YEAR.
  
 4.SPECIFY REQUIRED FIRE RATED WALLS.THERE ARE
 PENETRATION DETAILS BUT THE INFORMATION REGARDING WHICH
 DETAILS TO BE USED FOR THIS JOB IS NOT CLEAR.
  
 SHEET E7 WAS REVISED BUT REQUIREMENT IS STILL NOT
 CLEAR.YOU HAVE A 2 AND 3 HOUR FLOOR/WALL ASSEMBLY,
 TWO DIFFERENT FLOOR ASSEMBLIES, AND DETAILS 3 AND 6
 STATE "FIREPROOF" WITHOUT FIRE RATING REQUIREMENT OR
 DETAIL REFERENCE.FROM THE PLAN, I CANNOT DETERMINE
 WHAT IS REQUIRED AND WHAT THE CONTRACTOR'S OPTIONS ARE.
 IF THIS IS A IA BUILDING, A 4 HOUR BEARING WALL
 REQUIRED, 3 HOUR FOR TYPE IB, FBC TABLE 601.SEE
 FBC712.3.1.SEE FBC712.4.1.NO T RATING WAS SHOWN,
 BUT SEE E3, A PENETRATION SHOWN BETWEEN THE PH
 ELECTRICAL ROOM AND FPL VAULT ROOM.IS THE FPL VAULT
 REQUIRED TO BE RATED?WHY IS THERE NO T RATING?IF
 THIS IS EXEMPTED IN THE CODE, PLEASE STATE EXEMPTION
 AND PROVIDE SPEC SHEETS FOR THE PRODUCT TO SHOW
 COMPLIANCE WITH THE EXEMPTION.
  
 PLEASE LABEL REQUIRED FIRE RESISTANCE AS REQUESTED SO
 THAT CODE COMPLIANCE CAN BE DETERMINED.INDICATE
 REQUIRED FIRE RESISTANCE FOR WALLS, ROOF, FLOORS.
 PLEASE ALSO DECLARE BUILDING CONSTRUCTION TYPE FBC
 CHAPTER 6.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-04 Time 13:10 Rev Time 0.00
Received By shill Date 2008-03-10 Time 13:10 Sent To  
Notes
2008-03-10 13:24:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE ADDRESS FOR MACTEC ON THE PLAN CONFLICTS WITH
 THE ADDRESS ON FILE WITH DBPR.PLEASE ADDRESS.
  
 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN
 GOVERNING CODE.
  
 3.PLEASE SEE FAC61G15=23.002; CALCULATIONS ARE TO BE
 SIGNED AND SEALED EACH SHEET OR AN INDEX SHEET USED.
  
 4.SPECIFY REQUIRED FIRE RATED WALLS.THERE ARE
 PENETRATION DETAILS BUT THE INFORMATION REGARDING WHICH
 DETAILS TO BE USED FOR THIS JOB IS NOT CLEAR.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-05 Cont ID  
Sent By btrobaug Date 2008-06-05 Time 11:09 Rev Time 0.00
Received By btrobaug Date 2008-06-05 Time 11:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-11 Cont ID  
Sent By btrobaug Date 2008-04-11 Time 13:50 Rev Time 0.00
Received By btrobaug Date 2008-04-11 Time 13:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By btrobaug Date 2008-03-27 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2008-03-27 Time 09:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-03-07 Cont ID  
Sent By btrobaug Date 2008-03-07 Time 11:21 Rev Time 0.00
Received By btrobaug Date 2008-03-07 Time 08:00 Sent To B
Notes
2008-03-07 11:14:48 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER, .AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE NOTES ON SHEET E2, SPECIFICALLY B7 A ) & B), DO NOT
 REFERENCE THE NEC CURRENTLY ADOPTED BY THE FLORIDA
 LEGISLATURE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA
 LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION
 FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE
 SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO
 REFLECT THIS CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 12:18 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 12:17 Sent To E
Notes
2008-06-04 12:19:56TO "BTROBAUG' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 16:24 Sent To B
Notes
2008-05-05 16:25:40TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 15:32 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 15:32 Sent To Z
Notes
2008-04-21 15:32:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 10:05 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 10:05 Sent To Z
Notes
2008-04-10 10:05:28TO "Z" BOX/RESUB--NEW ELECT SHEETS SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 14:48 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 14:48 Sent To Z
Notes
2008-03-21 14:48:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 13:25 Rev Time 0.00
Received By shill Date 2008-03-04 Time 15:02 Sent To  
Notes
2008-03-04 15:02:35TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-22 Cont ID  
Sent By bpowell Date 2008-04-22 Time 08:56 Rev Time 0.00
Received By bpowell Date 2008-04-22 Time 08:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-04-10 Cont ID  
Sent By choops Date 2008-04-10 Time 16:09 Rev Time 0.00
Received By choops Date 2008-04-10 Time 16:09 Sent To E
Notes
2008-04-10 16:13:10***FAILED - RESUB #2***
  
  
 1)PERMIT PACKET PLANS DO NOT MATCH PLANS APPROVED BY
 PLANNING & ZONING DEPARTMENT'S INFORMAL SITE PLAN
 REVIEW.HEIGHTS VARY, EQUIPMENT CONFIGURATION VARIES,
 AND ADDITIONAL EQUIPMENT IS SHOWN ON PERMIT SET.
 PLEASE REVISE/CLARIFY/UPDATE INFORMAL SITE PLAN REVIEW
 DOCUMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 11:01 Rev Time 0.00
Received By choops Date 2008-03-26 Time 11:01 Sent To E
Notes
2008-03-26 11:02:38***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, AN
 INFORMAL SITE PLAN REVIEW SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By choops Date 2008-03-06 Time 09:31 Rev Time 0.00
Received By choops Date 2008-03-06 Time 09:31 Sent To E
Notes
2008-03-06 09:33:58***FAILED***
  
  
 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, AN
 INFORMAL SITE PLAN REVIEW SHALL BE PERFORMED BY THE
 PLANNING AND ZONING DEPARTMENT (561)822-1435.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT