| Plan Review Stops For Permit 08030060 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-29 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-05-29 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2008-05-29 09:08:36 | REVISED CALCULATIONS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-05 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-05-05 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2008-05-07 16:10:45 | CALCULATIONS OK PER ENGINEER | | | | | | PROVISO - SUBMIT NEW CALCULATIONS BEFORE FINAL | | | | | 2008-05-05 16:50:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.THE IMPORTANCE FACTOR WAS INCLUDED IN WIND DESIGN | | | CRITERIA AS REQUESTED, BUT THE CALCULATIONS SHOW AN | | | IMPORTANCE FACTOR OF 1.0 (RATHER THAN THE REQUIRED | | | 1.15).SEE THE CABINET DRAWINGS, ALSO OTHER | | | CALCULATIONS.AS DISCUSSED, NEW CALCULATIONS CAN BE A | | | PROVISO ITEM IF REQUESTED BUT THE ENGINEER IS TO | | | CONFIRM THAT PLANS AS DRAWN COMPLY WITH THE 1.15 | | | REQUIREMENT AND THE ENGINEER IS TO REQUEST THIS AS A | | | PROVISO ITEM.THIS CAN BE REQUESTED BY TELEPHONE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-29 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-29 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2008-04-29 14:33:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LISTS: | | | | | | 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN | | | GOVERNING CODE. | | | | | | SEE OTHER REVIEWS WHICH CLARIFY WHY THIS IS REQUIRED. | | | RESPONSE LETTER STATES THAT IT WAS ADDRESSED (EACH | | | REVIEW), AND LANGUAGE REMAINS THE SAME. | | | | | | 3.ADDRESSED. | | | | | | 4.ADDRESSED.PLEASE KEEP THE HILTI FIRESTOP SPEC | | | SHEET AS A PART OF THE PERMIT PACKAGE. | | | | | | NEW COMMENT: | | | | | | 5.WHEN ADDRESSING COMMENT #1, ALSO INCLUDE IMPORTANCE | | | FACTOR (1.15) AND BUILDING CLASSIFICATION FBC TABLE | | | 1604.5. IF NECESSARY, REVISE CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-15 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-15 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2008-04-15 17:14:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LISTS: | | | | | | 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN | | | GOVERNING CODE. | | | | | | PLEASE ADD "2007 REVISIONS/SUPPLEMENTS" TO GOVERNING | | | CODE.THIS ESTABLISHES WHICH VERSION OF THE FBC2004 IS | | | TO BE USED ON THIS JOB AS IT HAS BEEN REVISED EACH | | | YEAR, AND ON A DIFFERENT DATE EACH YEAR. | | | | | | 3RD REVIEW, RESPONSE LETTER STATES THAT THIS WAS DONE | | | BUT LANGUAGE IS STILL THE SAME; STATES "ALL SUBSEQUENT | | | ADOPTED AMENDMENTS" RATHER THAN 2007 | | | REVISIONS/SUPPLEMENTS.AS STATED, THIS IS ESTABLISHED | | | BY APPLICATION DATE AND NEEDS TO BE INCORPORATED INTO | | | THE PLAN.NOTE THAT THIS IS STILL SHOWN AS REVISION 1, | | | SAME AS PREVIOUSLY SUBMITTED. | | | | | | 3.THE INDEX SHEET WAS ADDED TO THE CALCULATIONS. | | | PLEASE INCLUDE CERTIFICATE OF AUTHORIZATION NUMBER | | | FAC61G15-23.002. | | | | | | 4.ADDRESSED.PLEASE KEEP THE HILTI FIRESTOP SPEC | | | SHEET AS A PART OF THE PERMIT PACKAGE. | | | | | | NEW COMMENT: | | | | | | 5.SEE ZONING COMMENT.APPROVAL IS REQUIRED PRIOR TO | | | PERMIT ISSUANCE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-01 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-01 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2008-04-01 14:46:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN | | | GOVERNING CODE. | | | | | | PLEASE ADD "2007 REVISIONS/SUPPLEMENTS" TO GOVERNING | | | CODE.THIS ESTABLISHES WHICH VERSION OF THE FBC2004 IS | | | TO BE USED ON THIS JOB AS IT HAS BEEN REVISED EACH | | | YEAR, AND ON A DIFFERENT DATE EACH YEAR. | | | | | | 4.SPECIFY REQUIRED FIRE RATED WALLS.THERE ARE | | | PENETRATION DETAILS BUT THE INFORMATION REGARDING WHICH | | | DETAILS TO BE USED FOR THIS JOB IS NOT CLEAR. | | | | | | SHEET E7 WAS REVISED BUT REQUIREMENT IS STILL NOT | | | CLEAR.YOU HAVE A 2 AND 3 HOUR FLOOR/WALL ASSEMBLY, | | | TWO DIFFERENT FLOOR ASSEMBLIES, AND DETAILS 3 AND 6 | | | STATE "FIREPROOF" WITHOUT FIRE RATING REQUIREMENT OR | | | DETAIL REFERENCE.FROM THE PLAN, I CANNOT DETERMINE | | | WHAT IS REQUIRED AND WHAT THE CONTRACTOR'S OPTIONS ARE. | | | IF THIS IS A IA BUILDING, A 4 HOUR BEARING WALL | | | REQUIRED, 3 HOUR FOR TYPE IB, FBC TABLE 601.SEE | | | FBC712.3.1.SEE FBC712.4.1.NO T RATING WAS SHOWN, | | | BUT SEE E3, A PENETRATION SHOWN BETWEEN THE PH | | | ELECTRICAL ROOM AND FPL VAULT ROOM.IS THE FPL VAULT | | | REQUIRED TO BE RATED?WHY IS THERE NO T RATING?IF | | | THIS IS EXEMPTED IN THE CODE, PLEASE STATE EXEMPTION | | | AND PROVIDE SPEC SHEETS FOR THE PRODUCT TO SHOW | | | COMPLIANCE WITH THE EXEMPTION. | | | | | | PLEASE LABEL REQUIRED FIRE RESISTANCE AS REQUESTED SO | | | THAT CODE COMPLIANCE CAN BE DETERMINED.INDICATE | | | REQUIRED FIRE RESISTANCE FOR WALLS, ROOF, FLOORS. | | | PLEASE ALSO DECLARE BUILDING CONSTRUCTION TYPE FBC | | | CHAPTER 6. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-04 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-10 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2008-03-10 13:24:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.THE ADDRESS FOR MACTEC ON THE PLAN CONFLICTS WITH | | | THE ADDRESS ON FILE WITH DBPR.PLEASE ADDRESS. | | | | | | 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN | | | GOVERNING CODE. | | | | | | 3.PLEASE SEE FAC61G15=23.002; CALCULATIONS ARE TO BE | | | SIGNED AND SEALED EACH SHEET OR AN INDEX SHEET USED. | | | | | | 4.SPECIFY REQUIRED FIRE RATED WALLS.THERE ARE | | | PENETRATION DETAILS BUT THE INFORMATION REGARDING WHICH | | | DETAILS TO BE USED FOR THIS JOB IS NOT CLEAR. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-06-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-05 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-05 |
Time |
11:09 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-04-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-11 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-11 |
Time |
13:50 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-27 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-27 |
Time |
09:27 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-03-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-07 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-07 |
Time |
08:00 |
Sent To |
B |
|
| Notes |
| 2008-03-07 11:14:48 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER, .AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THE NOTES ON SHEET E2, SPECIFICALLY B7 A ) & B), DO NOT | | | REFERENCE THE NEC CURRENTLY ADOPTED BY THE FLORIDA | | | LEGISLATURE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA | | | LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION | | | FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE | | | SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO | | | REFLECT THIS CHANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-04 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-04 |
Time |
12:17 |
Sent To |
E |
|
| Notes |
| 2008-06-04 12:19:56 | TO "BTROBAUG' DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-05 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-05 |
Time |
16:24 |
Sent To |
B |
|
| Notes |
| 2008-05-05 16:25:40 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-21 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-21 |
Time |
15:32 |
Sent To |
Z |
|
| Notes |
| 2008-04-21 15:32:30 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-10 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-10 |
Time |
10:05 |
Sent To |
Z |
|
| Notes |
| 2008-04-10 10:05:28 | TO "Z" BOX/RESUB--NEW ELECT SHEETS SUBMITTED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-21 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-21 |
Time |
14:48 |
Sent To |
Z |
|
| Notes |
| 2008-03-21 14:48:36 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-10 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-04 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2008-03-04 15:02:35 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-04-22 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-04-22 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-04-22 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-04-10 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-04-10 |
Time |
16:09 |
Sent To |
E |
|
| Notes |
| 2008-04-10 16:13:10 | ***FAILED - RESUB #2*** | | | | | | | | | 1)PERMIT PACKET PLANS DO NOT MATCH PLANS APPROVED BY | | | PLANNING & ZONING DEPARTMENT'S INFORMAL SITE PLAN | | | REVIEW.HEIGHTS VARY, EQUIPMENT CONFIGURATION VARIES, | | | AND ADDITIONAL EQUIPMENT IS SHOWN ON PERMIT SET. | | | PLEASE REVISE/CLARIFY/UPDATE INFORMAL SITE PLAN REVIEW | | | DOCUMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-26 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-26 |
Time |
11:01 |
Sent To |
E |
|
| Notes |
| 2008-03-26 11:02:38 | ***FAILED - RESUB #1*** | | | | | | | | | REPEAT COMMENT: | | | | | | 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, AN | | | INFORMAL SITE PLAN REVIEW SHALL BE SUBMITTED TO AND | | | APPROVED BY THE PLANNING AND ZONING DEPARTMENT. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-06 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-06 |
Time |
09:31 |
Sent To |
E |
|
| Notes |
| 2008-03-06 09:33:58 | ***FAILED*** | | | | | | | | | 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, AN | | | INFORMAL SITE PLAN REVIEW SHALL BE PERFORMED BY THE | | | PLANNING AND ZONING DEPARTMENT (561)822-1435. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | SENT TO "E" - BT |
|
|