Plan Review Details - Permit 08030020
Plan Review Stops For Permit 08030020
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-30 Cont ID  
Sent By shill Date 2008-06-30 Time 12:09 Rev Time 0.00
Received By shill Date 2008-06-30 Time 12:09 Sent To  
Notes
2008-06-30 12:09:41INTERIOR WORK ONLY - SEPARATE PERMIT STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-29 Cont ID  
Sent By jwitmer Date 2008-04-29 Time 10:54 Rev Time 2.22
Received By jwitmer Date 2008-04-29 Time 10:54 Sent To  
Notes
2008-04-29 10:56:58BUILDING PLAN REVIEW
 PERMIT: 08030020
 ADD: 700 S ROSEMARY AVE #110
 CONT: RUSSCO INC. GENERAL CONTRACTORS
 TEL: (508)989-3077/ NEYITA 856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
 DATE: APRIL 29,2008
  
 1) COMPLIED.
  
 2) 2ND REQUEST,THE BUILDING OFFICIAL HAS DETERMINED
 THAT THE CBC RUSSCO INC. GENERAL CONTRACTORS ARE
 WORKING OUT OF THE SCOPE OF THEIR LICENSE. FL S S
 489.105 (B)
 BUILDING CONTRACTOR" MEANS A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL
 BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL
 BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND
 ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING. SHEET S01.1 & S02.1 BOTH INDICATE STRUCTURAL
 MEMBERS THAT WILL AFFECT THE STOREFRONT SYSTEM AND THUS
 THE BUILDING ENVELOPE ITSELF.
 RESPONSE INDICATES THAT THE CBC HAS APPLIED FOR THE
 ADDITIONAL LICENSE REQUIRED. UNTIL THE CGC ICENSE HAS
 BEEN ISSUED WE CAN NOT ISSUE THE PERMIT TO THE CBC.
  
 A SOLUTION IS TO HAVE A CGC PULL A SUB-PERMIT FOR THE
 INSTALLATION OF THE STOREFRONT SYSTEM AND HAVE THE CBC
 REMOVE THE STOREFRONT SYSTEM FROM THEIR SCOPE OF WORK.
 THIS HAS BEEN AN AVENUE USED BY OTHER CONTRACTORS THAT
 WERE IN THE SAME LICENSING SITUATION.
  
  
 3) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 KAWNEER350-MS, REQUIRES FLORIDA COVERSHEET, COMMENT
 FROM THE LAST REVIEW, THE SITUATION AT HAND, THE BATH &
 BODY WORKS COVERSHEET LIST 2 KAWNEER FLORIDA
 COVERSHEETS AND THE CORRESPONDING MIAMI-DADE NOA'SFL
 627 FOR STOREFRONT AND THE SECOND IS FL 629 FOR
 STOREFRONT SWINGING DOOR.BOTH OF THESE NUMBERS ARE
 UNDER THE 2001 FBC NOT THE CURRENT 2004 FBC. PLEASE
 REMOVE THESE NUMBERS FROM THE PLAN DOCUMENTS. THE TWO
 MIAMI-DADE NOA'S THAT WERE SUBMITTED CAN BE USED AS
 LOCAL PRODUCT APPROVALS SINCE MIAMI-DADE HAS THEIR OWN
 THIRD PARTY QUALITY ASSURANCE PROGRAM. THE ISSUE IS THE
 KANEER NOA 04-0329.03 DOES HAVE THE DESIGNERS WRITTEN
 APPROVAL ON THE FRONT PAGE OF THE REPORT WHERE AS THE
 ARCH ALUMINUM NOA 05-0906.05 IS NOT SPECED IN FOR THE
 JOB, A KAWNEER STOREFRONT SYSTEM IS SPECKED IN UNDER
 THE NOA 02-0220.01, THIS NOA HAS EXPIRED ON 8-29-07,
 NOT CURRENT REPORT.
  
 A SOLUTION. THE ARCH ALUMINUM MIAMI-DADE NOA 05-0906.05
 IS A CURRENT REPORT, IT MEETS THE WIND PRESSURES AND
 CAN BE A LOCAL PRODUCT APPROVAL WITH THE MIAMI-DADE
 THIRD PARTY QUALITY ASSURANCE PROGRAM. TWO ISSUES WILL
 NEED TO BE ADDRESSED.
 1) THE DESIGN TEAM WILL NEED TO REVIEW THIS NOA FOR
 CODE COMPLIANCE THEN APPLY THEIR SHOP DRAWING STAMP IF
 APPROVED.
 2) THE MIAMI-DADE NOA WOULD SECOND NEED TO BE
 REVIEWED BY CAPRI ENGINEERING FOR CODE COMPLIANCE, IF
 FOUND CODE COMPLIANT, STAMP AND SUBMIT TO THE BUILDING
 DEPARTMENT.
  
 IN REVIEWING THESE OPTIONS WITH THE BUILDING OFFICIAL
 HE HAS AGREED THAT AS FAR AS THE "BUILDING REVIEW" WE
 COULD ISSUE A PERMIT WITHOUT A THIRD AUDIT. ONLY ITEMS
 TO BE CORRECTED WOULD BE
 1) CGC TO TAKE ON THE RESPONSIBILITY OF THE STOREFRONT
 SYSTEMS, THE NOA'S THAT ARE FOUND TO BE CODE COMPLIANT
 WITH THE DESIGN TEAMS APPROVAL AND CAPRI'S APPROVAL
 COULD THEN BE ISSUED.
 2) THE CBC ON THEIR APPLICATION WOULD NEED TO IDENTIFY
 INTERIOR WORK ONLY, AND BUILDING COULD THEN CHANGE THIS
 REVIEW INTO A PASSED.
  
 4-7) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By jwitmer Date 2008-03-12 Time 16:55 Rev Time 3.33
Received By jwitmer Date 2008-03-12 Time 16:55 Sent To  
Notes
2008-03-12 16:56:59BUILDING PLAN REVIEW
 PERMIT: 08030020
 ADD: 700 S ROSEMARY AVE #110
 CONT: RUSSCO INC. GENERAL CONTRACTORS
 TEL: (508)989-3077/ NEYITA 856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. BATH & BODYWORKS
 NEW STOREFRONT CALCULATIONS INDICATE DESIGNED TO 2006
 FBC SUPPLEMENTS, PLEASE CORRECT.
  
 1F) SHEET S01.1 PLANSDO NOT REFER ONLY TO THE 2004
 FBC NOT THE 2007 SUPPLEMENTS.
  
 1G) SHEET S01.1 NOR THE STOREFRONT CALCULATIONS
 INDICATE THE PARAMETERS OF THE WIND DESIGN. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 1H) SHEET S01.1UNDER THE HEADING SPECIAL INSPECTION
 REFERENCES THE IBC 1701, PLEASE CORRECT THE REFERENCE
 TO THE FBC. NOTE THE BUILDING OFFICIAL HAS DETERMINED
 THAT ?NO?
 THRESHOLD PLAN WILL BE NECESSARY FOR THE REPLACEMENT OF
 STOREFRONT SYSTEMS.
  
 2)THE BUILDING OFFICIAL HAS DETERMINED THAT THE CBC
 RUSSCO INC. GENERAL CONTRACTORS ARE WORKING OUT OF THE
 SCOPE OF THEIR LICENSE. FL S S 489.105 (B)
 BUILDING CONTRACTOR" MEANS A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL
 BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL
 BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND
 ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING. SHEET S01.1 & S02.1 BOTH INDICATE STRUCTURAL
 MEMBERS THAT WILL AFFECT THE STOREFRONT SYSTEM AND THUS
 THE BUILDING ENVELOPE ITSELF.
  
 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
 ARCH ALUMINUM IMPACT WALL L-3000,REQUIRES FLORIDA
 COVERSHEET
 KAWNEER350-MS, REQUIRES FLORIDA COVERSHEET
  
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5)DOOR # 3 THAT LEADS INTO THE STORAGE ROOM HAS
 ISSUES WITH CLEAR FLOOR SPACE WITH THE LOCATION OF THE
 FIRE EXTINGUISHER AT THIS LOCATION, SEE 11-4.13.5 &
 11-4.4.1.
  
 6) CALCULATIONS WERE SUBMITTED FOR THE STOREFRONT BUT
 NO CALCULATIONS WERE SUBMITTED FOR THE FLOOR LOADING
 OVER THE RESTROOM. 110.4.2 ALL SUCH CALCULATIONS SHALL
 BE ACCOMPANIED BY AN AFFIDAVIT FROM THE ARCHITECT OR
 ENGINEER STATING THE SAFE ALLOWABLE FLOOR LOAD ON EACH
 FLOOR IN POUNDS PER SQ FOOT UNIFORMLY DISTRIBUTED. THE
 COMPUTATIONS AND AFFIDAVIT SHALL BE FILED AS A
 PERMANENT RECORD OF THE BUILDING DIVISION.
  
 7) SHEET A-801 INDICATESA DETAIL C/ A-803, THERE IS
 NO SECTION, PLANS ARE NOT CLEAR AS TO WHAT THE EXTERIOR
 WALLS ON EITHER SIDE OF THE FRONT ENTRY ARE MADE OF?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By dpalmer Date 2008-06-27 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2008-06-27 Time 08:42 Sent To  
Notes
2008-06-27 08:42:48** NOTE**
  
 TRACK FIXTURE T2 IS BASED ON CON TECH FIXTURE ONLY AT A
 MAXIMUM WATTAGE OF 40W PER FIXTURE. THE OTHER FIXTURES
 LISTED FOR T2 SUCH AS THE HALO, JONO, OR INDY WAS NOT
 FIGURED INTO THE CALCULATIONS AS THEIR FIXTURE MAXIMUM
 VA IS 50W.
  
 FINAL PLANS SHALL CONTAIN ALL ACTUAL FIXTURES USED
 ALONG WITH ANY REVISED CALCULATIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 14:01 Sent To PC
Notes
2008-05-05 14:01:45** DENIEDAUDIT **
  
 1) NOTE: PLEASE SEE THE NOTICE TO BUILDING OFFICIAL
 NEEDS TO COORDINATE WITH THE SIGNED AFFIDAVITS. PLEASE
 SEE THESE SHOW SEPARATE PRIVATE PROVIDERS AS THE
 RESPONSIBLE ENGINEERS.
 PLEASE SUBMIT.
 FS 553.791
  
 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ARE STILL IN NEED OF MEETING FBC
 13-415.2.ABC.1.1, .1.2, 13-415.2
 PLEASE SEE FOR EXAMPLE:
 PLEASE SEE TRACK FIXTURE WHICH IS NOTED AS USING 40W
 FIXTURE. HOWEVER THE WATTAGE REQUIRED BY CODE IS BASE
 DON THE MAXIMUM FIXTURE VA NOT THE RATING OF THE BULB.
 AS THE FIXTURE LEGEND LIST MULTIPLE FIXTURES INCLUDING
 FIXTURES WHICH CONTAIN A HIGHER VA RATING, THEN THE
 HIGHER SHALL BE USED.
 PLEASE DELETE ALL OTHER FIXTURES OR FIGURE AT THE
 HIGHER VA.
 THE VA IS BASED ON THE LENGTH OF TRACK AT 30VA PER FT
 *OR* THE VA OF FIXTURE/TRANSFORMER WHICH EVER IS
 GREATER.
 PLEASE EXPLAIN WHY THE CALCULATIONS TABLE FOR LIGHTING
 NEXT TO FIXTURES TA AND T2 STATE * USE TRACK LENGTH*
 WHEN THE CALCULATIONS FOR THESE TWO FIXTURES SHOW USE
 OF THE FIXTURE VA?
  
 ** THIS ONE EXAMPLE ONLY.
  
 3) NOTE: PLEASE SEE SECTIONS 13-415.1.ABC.1.1, .1.2 AND
 .1.3. PLEASE SEE THE OVER RIDE LOCATIONS ARE REQUIRED
 WHERE THE OCCUPANT ENTERS A SPACE/AREA. THE OCCUPANT IS
 REQUIRED TO CLEARLY SEE THE LIGHTING WHICH IS BEING
 CONTROLLED OR MEET THE EXCEPTIONS.
 RESPONSE MENTIONS THIS IS AN* ENCLOSED MALL* AND THERE
 IS NO OUTSIDE LIGHTING HOWEVER THIS IS NOT AN ENCLOSED
 MALL AND PLANS DO SHOW FIXTURES OUTSIDE FRONT DOORS.
 PLEASE VERIFY THE LOCATION OF THE SCOPE OF WORK. THIS
 AHJ DOES KNOW THE LOCATION OF THE PROPOSED SCOPE OF
 WORK.SEE COMMENTS BELOW AS INDOOR RATED FIXTURES
 SHALL NOT BE USED OUTSIDE.
 PLEASE SEE 13-415.1.ABC.1.4 AND ADJUST CONTROLS
 ACCORDINGLY.
 PLEASE SEE THE LIGHTING CONTROL INFORMATION PROVIDED IS
 NOT COMPLETE FOR REVIEW FOR CODE COMPLIANCE.
 THE EQUIPMENT APPEARS AS A LIGHTING PANEL BOARD HOWEVER
 NO INFORMATION/DETAILS WAS SHOWN TO SUPPORT OR
 DETERMINE MINIMUM CODE COMPLIANCE.
 INFORMATION ON RESPONSE LETTER CAN NOT DETERMINE CODE
 COMPLIANCE ON PLANS.
  
 4) NOTE: PLEASE SEE SECTION NOTED ABOVE FOR EXTERIOR
 LIGHTS PER 13-415.1.ABC.1.4.
 PLEASE COMPLETE WITH ONE OF THE TWO MINIMUM REQUIRED BY
 CODE.
  
 5) NOTE: PLEASE KNOW AS NOTED ABOVE IN NOTE #3 THE
 OUTSIDE LIGHT FIXTURES SHALL BE LISTED FOR LOCATION.
 THESE ARE OUTSIDE AND THE LOCATION IS NOT AN ENCLOSED
 MALL.
 PLEASE ADJUST LIGHT FIXTURE TYPES ACCORDINGLY.
 110.3, 410.4A
  
 6) NOTE: PLEASE SEE NOTICE WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE IS GIVEN AS PER FS
 553.80(2)(B).
 THIS IS ONLY A NOTICE AT THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By dpalmer Date 2008-03-10 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 23:47 Sent To  
Notes
2008-03-10 18:37:082008-03-10 18:37:08
  
 ** DENIED**
  
  
  
 1) NOTE:PLEASE SEE THE FLA-COM ENERGY CALCULATIONS
 SUBMITTED WHICH ARE IN NEED OF COORDINATION WITH THE
 LIGHTING ON THE ELECTRICAL PLANS.
 PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH
 THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3.
 PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER
 SPECIALTY LIGHTING SYSTEMS)
 PLEASE SEE SECTION 13-415.2.ABC.1.2 AS THE WATTAGE
 WHICH IS REQUIRED SHALL BE BASED ON THE LABELED FIXTURE
 WATTAGE AND NOT THE BULB WATTAGE INSTALLED.
 PLEASE SEE THE TRACK LIGHTING IS REQUIRED TO BE FIGURED
 AT THE FIXTURE WATTAGE PER UNIT OR LENGTH OF TRACK,
 WHICH EVER IS GREATER. PLANS STATE TO USE THE LENGTH OF
 TRACK HOWEVER BASED ON THE LENGTHS SHOWN ON PLANS THE
 INPUT DATA REPORT DOES NOT CORRELATE. (FOR EXAMPLE:
 TRACK LENGTHS ARE GREATER THAN 208FT)
 PLEASE SEE THE LENGTHS ON PLANS AND ADJUST.
 PLEASE SEE THE TOTAL WATTAGE IN THE DESIGN AS STATED ON
 E03.1 IS NOT THE ACTUAL TOTAL DESIGN ON PLANS. PLEASE
 SEE THE TOTAL DESIGN WATTAGE SHOWN ON THE SUMMARY
 SHEETS OF THE ENERGY CALCULATIONS IS NOT THAT AS SHOWN
 ON PLANS.
 PLEASE SEE THE DESIGN WATTAGE ON SHEET 4 OF 6 NOTES
 7622W AND YET THE ALLOWANCE IS LISTED AS 5301.9 AND THE
 CRITERION IS 1382. PLEASE EXPLAIN HOW THIS IS
 POSSIBLE.
 PLEASE ALSO SEE THE NON SALES AREA ON SHEET 4 OF 6
 NOTES *FINE MATERIAL STORAGE*. PLEASE SEE STORAGE AREA
 DOES NOT MEET *FINE STORAGE* AS NOTED IN THE CODE.
 PLEASE ALSO COORDINATE WATTAGE USE ON ALL OTHERS PLEASE
 SEE THE IDR ON THE SUBMITTED CALCULATIONS WHICH SHOWS
 NO LIGHTING FIGURED INTO THE REPORT. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY SHOW EXTERIOR
 LIGHTING?
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH
 RESPECT TO THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES
 AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE
 SIGNATURE FROM THE OWNER AGENT.
 FS 471.025, FBC 13-103.1.1.1
  
 2) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V
 SYSTEMS TO BROWN, PURPLE AND YELLOW.
 PLANS SHOWS YELLOW, PURPLE, YELLOW.
 THE CITY OF WEST PALM BEACH AND ALL SURROUNDING
 JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST
 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN
 AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT
 KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT
 IN THIS JURISDICTION AS WELL KEEPING WITH THE
 ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE
 REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG
 OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC
 DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A
 LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY
 MEASURE.
 90.4.
  
 3) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00
 ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF
 1992*??
 PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES
 SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE
 CHAPTER 13.
  
 4) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING
 DEVICES DOES NOT APPLY.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED
 FOR LIGHTING CONTROL SYSTEM.
 PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED.
 FOR EXAMPLE REAR ENTRANCE AND OTHER LOCATIONS. PLEASE
 SEE PLANS ARE SHOWING STANDARD WALL SP SWITCHES IN SOME
 LOCATIONS WHICH IS NOT POSSIBLE WHEN THE MINIMUM FOR
 CODE COMPLIANCE REQUIRES AUTOMATED CONTROLS AND OVER
 RIDES. (FOR EXAMPLE:
 PLEASE SEE MISSING EXTERIOR LIGHTING CONTROLS.
 AN OCCUPANT IS REQUIRED TO VISUALLY SEE THE LIGHTING
 BEING CONTROLLED OR MEETING THE EXCEPTION OF PILOT
 LIGHTS ETC.
 PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE
 TIMES.
 PLEASE SHOW A LAYOUT OF ZONES REQUIRED.
 ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING
 COMPLIANCE CAN NOT BE DONE AS THERE ARE MISSING ITEMS.
  
 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC).
 PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS
 REFLECT 220.12)
  
 7) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO CONTAIN
 MINIMUM RATINGS FOR HORN AND STROBE DEVICES MEETING FBC
 AND CHAPTER ADA REQUIREMENTS HOWEVER PLEASE SEE THE FA
 SHEETS AS THE STROBE RATINGS ARE NOTED AS CD AND ALSO
 SHOW CD ON LEGEND.
 PLEASE SEE FBC 11-4.28.3(4) FOR MINIMUM 75CD REQUIRED
 FOR ADA COMPLIANCE.
  
 8) NOTE: PLEASE PROVIDE A MORE CLEAR LOCATION OF THE
 SERVICE EQUIPMENT/PANEL LOCATIONS.
 240.24, 408.17,AND 110.26.
 IT IS NOT ENTIRELY CLEAR ON ELECTRICAL PLANS WHERE THIS
 EQUIPMENT IS LOCATED.
  
 9) NOTE: PLEASE KNOW ANY LOCK OFF DEVICES AS NOTED ON
 PANEL SCHEDULE WILL BE REQUIRED TO BE LISTED FOR
 PERMANENT INSTALLATIONS AND NOT THE *CLICK OR SNAP ON*
 TYPE. SHALL BE LISTED ACCORDINGLY WHERE REQUIRED. MANY
 OF THE DEVICES ON THE MARKET ARE LISTED FOR TEMPORARY
 USE AS/ LOCK OUT/TAG OUT.
 SHALL BE AN INTEGRAL PART OF BREAKER OR LISTED AS
 SUCH.
 110.3
  
 10) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS
 DOWN THE LEFT HAND SIDE OF PLANS. THESE HAVE BEEN
 REMOVED FROM THE REVIEWED SET. PLEASE PLACE DOCUMENTS
 IN SOME SORT OF FOLDER WITH LABELING OF TABS ETC.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-08 23:48:072008-03-08 23:48:07
  
 IN ELECTRIC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2008-04-28 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By mawillia Date 2008-03-20 Time 14:02 Rev Time 0.00
Received By mawillia Date 2008-03-20 Time 12:34 Sent To  
Notes
2008-03-20 13:48:53*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE/HINDER ACCESS
 TO AND (OR) EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRELANES, ETC).
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, SHOW/DISPLAY THE SUITE NUMBER
 FOR THIS TENANT SPACE.AS PER WEST PALM BEACH CODE,
 SUITE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALL
 AND CEILINGS IN TERMS OF CLASS A OR CLASS B.
  
 6.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATIFY THE 75' TRAVEL DISTANCE. THE SYMBOL FOR THE FIRE
 EXTINGUISHER SHOWN ON SHEET F02.1 MAKES IT DIFFICULT TO
 DISTINGUISH FROM OTHER ITEMS ON THAT FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET)
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 12:42 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 10:58 Sent To E
Notes
2008-06-24 12:43:04TO "COMM" BD#59--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 08:58 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 08:58 Sent To  
Notes
2008-04-24 08:59:15TO "COMM" BD#48--PRIVATE PROVIDER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-20 Cont ID  
Sent By mawillia Date 2008-03-20 Time 12:34 Rev Time 0.00
Received By mawillia Date 2008-03-03 Time 14:39 Sent To  
Notes
2008-03-03 14:40:10TO "COMM" BD#64--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-28 Cont ID  
Sent By rregueir Date 2008-04-28 Time 11:35 Rev Time 0.00
Received By rregueir Date 2008-04-28 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-12 Cont ID  
Sent By rregueir Date 2008-03-12 Time 13:31 Rev Time 0.00
Received By rregueir Date 2008-03-11 Time 16:35 Sent To  
Notes
2008-03-12 13:30:59NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED AS PART OF
 THIS PERMIT APPLICATION FOR PURPOSES OF MECHANICAL
 COMPLIANCE. ENERGY CALCULATIONS ARE NOT REQUIRED FOR
 THIS PERMIT AS THIS PROJECT IS NOT A RENOVATION IN
 ACCORDANCE WITH FBC 13-101.1.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-24 Cont ID  
Sent By kstevens Date 2008-04-24 Time 11:06 Rev Time 0.00
Received By kstevens Date 2008-04-24 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By kstevens Date 2008-03-04 Time 11:43 Rev Time 0.00
Received By kstevens Date 2008-03-04 Time 11:43 Sent To  
Notes
2008-03-04 11:55:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A00.0 RESTROOM REQUIREMENTS INDICATE UNISEX
 TOILET ROOM PERMITTED PER EXCEPTION 4 OF SECTION 403.2.
 THE EXCEPTION IS ONLY APPROVED IN MERCANTILE
 OCCUPANCIES WITH TOTAL FLOOR AREA OF 3000SF OR LESS.
 THE GROSS AREA INDICATED AS 3273 DOES NOT ALLOW FOR
 THIS EXCEPTION. TWO TOILET ROOMS ARE REQUIRED PER TABLE
 403.1. (SECTION 302.1.1 INCIDENTIAL USE AREAS. AREAS
 THAT ARE INCIDENTAL TO THE MAIN OCCUPANCY SHALL BE
 CLASSIFIED IN ACCORDANCE WITH THE MAIN OCCUPANCY OF THE
 PORTION OF THE SPACE IN WHICH THE INCIDENTAL USE AREA
 IS LOCATED).
  
 2. SHT A05.1 PER SECTION 1210.2 WALLS WITH IN 2 FEET OF
 A WATERCLOSET SHALL HAVE A "SMOOTH, HARD, SURFACE". NO
 WALL COVERING INDICATED BY THE WATER CLOSET. PLEASE
 SHOW COMPLIANCE.
  
 3. DEMO SINK SHOWS COLD WATER SUPPLY BUT NO SANITARY
 DRAINAGE IN THE PLUMBING RESPONSIBILITY SCHEDULE.
 PLEASE CLARIFY. SECTION 301.3
  
 4. ALL E, M & P SHEETS REQUIRE THE ADDRESS OF THE
 ENGINEER. THE ADDRESS INDICATED IN THE TITLE BLOCK DOES
 NOT REFLECT THE ADDRESS OF RECORD INDICATED IN THE
 STATE OF FLORIDA DBPR WEBSITE. PRIOR TO RESUBMITTING,
 PLEASE UPDATE EITHER THE TITLE BLOCKS OR THE DBPR
 WEBSITE TO REFLECT THE CORRECT ADDRESS OF THE ENGINEER.
 FAC 61G1-16.004(1) & FS 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-24 Cont ID  
Sent By eschneid Date 2008-04-24 Time 15:30 Rev Time 0.00
Received By eschneid Date 2008-04-24 Time 15:30 Sent To  
Notes
2008-04-24 15:31:04PASSED
  
 PLEASE NOTE THAT THE CONSTRUCTION BARRIER AND ALL
 SIGNAGE REQUIRE SEPARATE PERMITS.SIGNAGE IS LIMITED
 TO ONE SQUARE FOOT OF AREA PER ONE LINEAR FOOT OF
 BUILDING FRONTAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-04 Cont ID  
Sent By eschneid Date 2008-03-04 Time 11:06 Rev Time 0.00
Received By eschneid Date 2008-03-04 Time 11:06 Sent To  
Notes
2008-03-04 11:08:35PASSED
  
 PLEASE NOTE THAT THE CONSTRUCTION BARRIER AND ALL
 SIGNAGE REQUIRE SEPARATE PERMITS.SIGNAGE IS LIMITED
 TO ONE SQUARE FOOT OF AREA PER ONE LINEAR FOOT OF
 BUILDING FRONTAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.