| 2008-03-12 16:56:59 | BUILDING PLAN REVIEW |
| | PERMIT: 08030020 |
| | ADD: 700 S ROSEMARY AVE #110 |
| | CONT: RUSSCO INC. GENERAL CONTRACTORS |
| | TEL: (508)989-3077/ NEYITA 856-6655 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS |
| | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. BATH & BODYWORKS |
| | NEW STOREFRONT CALCULATIONS INDICATE DESIGNED TO 2006 |
| | FBC SUPPLEMENTS, PLEASE CORRECT. |
| | |
| | 1F) SHEET S01.1 PLANSDO NOT REFER ONLY TO THE 2004 |
| | FBC NOT THE 2007 SUPPLEMENTS. |
| | |
| | 1G) SHEET S01.1 NOR THE STOREFRONT CALCULATIONS |
| | INDICATE THE PARAMETERS OF THE WIND DESIGN. 1603.1.4 |
| | WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. |
| | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5.COMPONENTS AND CLADDING. THE DESIGN WIND |
| | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 1H) SHEET S01.1UNDER THE HEADING SPECIAL INSPECTION |
| | REFERENCES THE IBC 1701, PLEASE CORRECT THE REFERENCE |
| | TO THE FBC. NOTE THE BUILDING OFFICIAL HAS DETERMINED |
| | THAT ?NO? |
| | THRESHOLD PLAN WILL BE NECESSARY FOR THE REPLACEMENT OF |
| | STOREFRONT SYSTEMS. |
| | |
| | 2)THE BUILDING OFFICIAL HAS DETERMINED THAT THE CBC |
| | RUSSCO INC. GENERAL CONTRACTORS ARE WORKING OUT OF THE |
| | SCOPE OF THEIR LICENSE. FL S S 489.105 (B) |
| | BUILDING CONTRACTOR" MEANS A CONTRACTOR WHOSE |
| | SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL |
| | BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING |
| | RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL |
| | BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND |
| | ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A |
| | CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING, |
| | REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE |
| | SERVICES DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE |
| | BUILDING. SHEET S01.1 & S02.1 BOTH INDICATE STRUCTURAL |
| | MEMBERS THAT WILL AFFECT THE STOREFRONT SYSTEM AND THUS |
| | THE BUILDING ENVELOPE ITSELF. |
| | |
| | 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. |
| | ARCH ALUMINUM IMPACT WALL L-3000,REQUIRES FLORIDA |
| | COVERSHEET |
| | KAWNEER350-MS, REQUIRES FLORIDA COVERSHEET |
| | |
| | |
| | 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5)DOOR # 3 THAT LEADS INTO THE STORAGE ROOM HAS |
| | ISSUES WITH CLEAR FLOOR SPACE WITH THE LOCATION OF THE |
| | FIRE EXTINGUISHER AT THIS LOCATION, SEE 11-4.13.5 & |
| | 11-4.4.1. |
| | |
| | 6) CALCULATIONS WERE SUBMITTED FOR THE STOREFRONT BUT |
| | NO CALCULATIONS WERE SUBMITTED FOR THE FLOOR LOADING |
| | OVER THE RESTROOM. 110.4.2 ALL SUCH CALCULATIONS SHALL |
| | BE ACCOMPANIED BY AN AFFIDAVIT FROM THE ARCHITECT OR |
| | ENGINEER STATING THE SAFE ALLOWABLE FLOOR LOAD ON EACH |
| | FLOOR IN POUNDS PER SQ FOOT UNIFORMLY DISTRIBUTED. THE |
| | COMPUTATIONS AND AFFIDAVIT SHALL BE FILED AS A |
| | PERMANENT RECORD OF THE BUILDING DIVISION. |
| | |
| | 7) SHEET A-801 INDICATESA DETAIL C/ A-803, THERE IS |
| | NO SECTION, PLANS ARE NOT CLEAR AS TO WHAT THE EXTERIOR |
| | WALLS ON EITHER SIDE OF THE FRONT ENTRY ARE MADE OF? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |