Plan Review Details - Permit 08020683
Plan Review Stops For Permit 08020683
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By shill Date 2008-03-24 Time 09:50 Rev Time 0.00
Received By shill Date 2008-03-24 Time 09:50 Sent To  
Notes
2008-03-24 09:53:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE SITE PLAN SHOWS THIS AS TWO LOTS, OUR RECORDS
 SHOW ONE LOT.SEE ZONING COMMENTS REGARDING THE NEW
 PLAT.
  
 2.SEVERAL PLANS WERE SUBMITTED FOR THIS ADDRESS, AND
 THERE WERE SOME REFERENCES TO BRADLEY PLACE AND
 SEMINOLE.PLEASE VERIFY ALL EASEMENT AND ADDRESS
 REFERENCES AND REVISE AS NECESSARY.
  
 3.SEPARATE PERMITS REQUIRED (INFORMATIONAL ONLY).
  
 4.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 5.DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 6.PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 7.ONE SHEET STATES THIS IS A KOHLER, ANOTHER STATES
 CATEPILLAR.ONE SHEET STATES THIS IS NON LIFE SAFETY
 GENERATOR, THE OTHER STATES THIS IS A LIFE SAFETY
 GENERATOR.PLEASE PROVIDE CONSISTENT INFORMATION ON
 THE PLANS.
  
 8.PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 19:33 Sent To  
Notes
2008-03-08 19:33:51** DENIED **
  
 ** 400 S. AUSTRALIAN AVE.
 PERMIT #08020683
  
 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW
 GENERATOR HOWEVER NO PLANS WERE SUBMITTED WITH THE
 SEPARATE PERMIT APPLICATION PACKAGE.
 SUBMIT COMPLETE PLANS, RISER, ETC
 PLEASE SEE NFPA-70 2005, NFPA-110 2002, NFPA-30,
 NFPA-101 ETC.
  
 2) NOTE: PLEASE KNOW THEVALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THIS INCLUDES THE
 GENERATOR, ATS ETC.
  
 ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER
 PERMIT APPLICATIONS FORTHIS SAME LOCATION, PLEASE SEE
 ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER
 REVIEWS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 17:21 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 17:04 Sent To  
Notes
2008-03-25 17:20:58*****DENIED*****
  
 1.NO PLANS SUBMITTED FOR PLAN REVIEW.
  
 2.NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS, SHALL BE REFERENCED.
  
 3.PLEASE INDICATE THE USE OF THE NEW GENERATOR.IS
 IT FOR STANDBY POWER, EMERGENCY POWER, OR BOTH?
  
 4.HOW IS MANUAL SHUT DOWM OF THE SYSTEM
 ACCOMPLISHED?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 19:38 Sent To  
Notes
2008-03-08 19:39:00ON COMM BOARD #26 BY AD.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 09:56 Rev Time 0.45
Received By tgordon Date 2008-03-21 Time 09:56 Sent To  
Notes
2008-03-21 09:57:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 DIESEL GENERATOR.
  
 2) PLEASE SHOW THE LOCATION OF THE 300 GALLON DIESEL
 FUEL TANK ON PLANS, IF MOUNTED BELOW THE GENERATOR
 PLEASE STATE SO ON PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 07:37 Rev Time 0.00
Received By kstevens Date 2008-03-26 Time 07:37 Sent To  
Notes
2008-03-26 07:38:37GENERATOR SHOWN TO HAVE DIESEL AS PRIME MOVER

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By eschneid Date 2008-02-29 Time 16:31 Rev Time 0.00
Received By eschneid Date 2008-02-29 Time 16:31 Sent To  
Notes
2008-02-29 16:36:57FAILED
  
 PLEASE RESPOND IN WRITING.
  
 1) A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 REFLECTIONS DPD TO APPROVE THE MODIFICATIONS, INCLUDING
 THE ADDITION OF THE PUMP HOUSE AND GENERATOR, IS
 REQUIRED PRIOR TO THE ISSUANCE OF BUILDING PERMITS.
 APPLICATION IS AVAILABLE FROM ERIC SCHNEIDER, PRINCIPAL
 PLANNER.
  
 2)THE ADDRESS OF THE SITE IS 400 SOUTH AUSTRALIAN
 AVENUE.THE PLANS STATE THE ADDRESS AS 300 SEMINOLE
 AVE. ON SHEET C-1.
  
 3) A SURVEY, LESS THAN A YEAR OLD, SHOWING ALL EXISTING
 CONDITIONS AND EASEMENTS IS REQUIRED.
  
 4) HAS THE PLAT THAT SUBDIVIDES THIS PROPERTY FROM 450
 SOUTH AUSTRALIAN AVENUE BEEN RECORDED?IF SO, PLEASE
 PROVIDE THE OR BOOK AND PAGE.
  
 5) IT APPEARS THAT THE LOCATION OF THE PUMP HOUSE AND
 GENERATOR ARE LOCATED ON PARKING SPACES.REQUIRED
 PARKING MAY NOT BE REMOVED.PROVIDE A TABLE WHICH
 LISTS THE PARKING COUNT FOR THE ENTIRE SITE AND THE NEW
 400 SOUTH AUSTRALIAN AVE. PARCEL.THE TABLE SHALL
 INCLUDE THE SQUARE FOOTAGE OF EACH BUILDING.
  
 6) THE GENERATOR SHALL BE SCREENED BY A WALL AND A
 HEDGE.
  
 7) THE FIRE PUMP HOUSE AND THE DOMESTIC WATER STRUCTURE
 REQUIRE FOUNDATION PLANTING ON THE SIDES THAT DO NOT
 HAVE A DOOR.
  
 8) THERE SHALL BE NO REDUCTION IN THE AMOUNT OF
 LANDSCAPE AS PART OF THIS PERMIT.IF LANDSCAPE IS TO
 BE REMOVED WITHIN THE AREA OF WORK, AN EQUAL AMOUNT
 SHALL BE REPLACED IN ANOTHER AREA.
  
 9) A FENCE PERMIT IS REQUIRED FOR THE NEW FENCE AND
 GATE.
  
 10) NO PLANS WERE INCLUDED WITH THE PERMIT.
  
 11) DOES THE SPEC PAGE LISTING THE DIMENSIONS FOR THE
 GENERATOR INCLUDE THE BASE MOUNTED FUEL TANK AND THE
 SKID?WHAT IS THE ULTIMATE HEIGHT OF THE ENTIRE
 GENERATOR UNIT?
  
 CONTACT ERIC SCHNEIDER @ 822-1435.