Plan Review Details - Permit 08020680
Plan Review Stops For Permit 08020680
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-11-05 Cont ID  
Sent By jgomez Date 2008-11-05 Time 16:19 Rev Time 0.00
Received By jgomez Date 2008-11-05 Time 10:54 Sent To PC
Notes
2008-11-05 16:55:22RESIDENTIAL (R3) ADDITION, BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13.
 NOTE: THIS MAY BE RECORDED AT A LATER TIME AT TIME OF
 PERMIT PICK UP TO AVOID EXPIRATION OF DOCUMENT.
  
 2- STORM SHUTTERS. PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. AND, CLEARLY MARK ON
 SHUTTER DRAWINGS SPECIFIC MOUNTING CONDITIONS. EG: WALL
 MOUNTED CONDITION OR BUILT OUT CONDITION. ALSO, MARK ON
 SHUTTERS DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, CONNECTION TYPE, PANEL SPAN AND STRUCTURE TO
 BE ATTACHED TO. (REPEAT COMMENT. THIRD TIME). SEE PAGE
 5 AND 6 OF SHUTTERS DRAWINGS AND CIRCLE PROPER
 INFORMATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH DESIGN PRESSURES OF SEC. R301
 2004 FLORIDA RESIDENTIAL CODE AND PRODUCT APPROVAL
 LIMITATIONS.
  
 ***NOTE:
 PRODUCT APPROVAL SUBMITTED FOR SWING DOOR REQUIRES
 PROTECTION FOR GLASS. TAKE THIS OPENING INTO
 CONSIDERATION FOR STORM SHUTTERS INSTALLATION
 SCHEDULE.
  
 3- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED
 FOR THE EXTERIOR SWING DOOR. ONE IS FROM JELD-WEN AND
 THE OTHER ONE IS FROM THERMA-TRU. PROVIDE ONLY
 INFORMATION FOR SPECIFIC DOOR TO BE INSTALLED.
 ***NOTE: BOTH PRODUCT APPROVALS SUBMITTED ARE EXPIRED.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL FOR SPECIFIC
 DOOR TO BE INSTALLED.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- A) PROVIDE STRUCTURAL BUCK DETAIL USING 2X BUCK AS
 REQUIRED BY PRODUCT APPROVAL SUBMITTED.
 ***NOTE: REVISE DOOR BUCK DETAIL TO PROVIDE DOOR FRAME
 FULL SUPPORT AS REQUIRED BY SEC. R613.6 OF 2004 FLORIDA
 RESIDENTIAL CODE. SEE SIZE OF DOOR FRAME IN DOOR
 PRODUCT APPROVAL SO CORRECT BUCK SIZE CAN BE SPECIFIED.
 DETAIL PROVIDE DOESN'T SHOW FULL SUPPORT OF DOOR FRAME
 AND DOESN'T SPECIFY STRUCTURAL BUCK SIZE(REPEAT
 COMMENT).
 B) BUCK DETAIL CALLS FOR #8 X 2 1/2" WOOD SCREWS. WOOD
 SCREWS ARE NOT GOOD TO BE ATTACHED TO CONCRETE BLOCK.
 REVISE AS REQUIRED.
 C) SPECIFY ANCHOR SPACING. DETAIL DOESN'T SPACY ANCHOR
 LOCATION AND SPACING.
  
 6- SHEET A1:
 A) INFORMATION SHOWN ON DIAPHRAGM SCHEDULE FOR ROOF
 SHEATHING AND INFORMATION ON EXT. C.M.U. WALL DOESN'T
 MATCH. REVISE AS REQUIRED TO MATCH.
 ALSO, SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR MINIMUM TYPE AND NAILING SPACING REQUIRED AT
 ROOF ZONE #3 AND REVISE AS REQUIRED. (REPEAT COMMENT).
  
 B) SPECIFY ROOF ZONE #3 DIMENSION. SEE FOOTNOTE ON
 FIGURE R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE AND
 REVISE AS REQUIRED.
  
 C) REVISE ROOF COVERING REFERENCE CITED IN THE WIND
 PRESSURE ZONES ROOF DIAGRAM. CORRECT CODE TO CITE IS
 THE 2004 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED.
 REFERENCE THIS CODE AND THE SPECIFIC SECTION. (REPEAT
 COMMENT).
  
 D) SEE SIMPSON PRODUCT APPROVAL AND REVISE CONNECTOR
 HETAL20 FASTENER NUMBER AND UPLIFT LOADS. (REPEAT
 COMMENT).
  
 E) BUILDING INFORMATION SHOWN ON DESIGN CRITERIA SHOWN
 AT BOTTOM RIGHT TABLE OF SHEET DOESN'T MATCH BUILDING
 INFORMATION. REVISE BUILDING WIDTH, LENGTH AND ROOF
 SLOPE TO MATCH PLANS.
  
 F) SPECIFY ALL DESIGN LOADS INCLUDING THE ATTIC LIVE
 LOADS AS REQUIRED BY SEC. R301.1 AND TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE. MAKE SURE TO IDENTIFY IF
 ATTIC WILL BE USED FOR STORAGE OR NOT. ACCORDING TO
 SIZE OF ATTIC ACCESS SHOWN ON ROOF FRAMING PLAN, THE
 ATTIC MAY BE DESIGNED FOR STORAGE. CLARIFY INFORMATION
 ON PLANS AS REQUIRED.
  
 G) DESIGN PRESSURES FOR WINDOW SHOWN ON DOOR & WINDOW
 SCHEDULE DON'T MATCH DESIGN PRESSURES SHOWN ON DESIGN
 CRITERIA AT BOTTOM RIGHT OF SHEET. REVISE AS REQUIRED.
  
 H) EXT. C.M.U. WALL SECTION: FOOTING DOESN'T MATCH
 FOOTING SHOWN ON DETAIL F1. REVISE AS REQUIRED TO
 MATCH.
  
 7- PROVIDE SURVEY OR SITE PLAN SHOWING EXACT LOCATION
 OF NEW GARAGE. SEE ZONING COMMENTS.
  
 8- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 553.80(2)(B) REGARDING FEES TO BE CHARGED TO THE DESIGN
 PROFESSIONAL FOR MULTIPLE REVIEWS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By jgomez Date 2008-04-23 Time 14:26 Rev Time 0.00
Received By jgomez Date 2008-04-23 Time 12:40 Sent To PC
Notes
2008-04-23 15:46:55RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13.
 NOTE: THIS MAY BE RECORDED AT A LATER TIME AT TIME OF
 PERMIT PICK UP TO AVOID EXPIRATION OF DOCUMENT.
  
 2- OWES $146.78 FOR PERMIT VALUATION AND RADON FEES.
 THIS FEE WAS CHARGED ON PREVIOUS CHECKLIST AND IT WAS
 NOT PAID YET. IN ADDITION, RESUBMITTAL FEES WILL BE
 ASSESSED AFTER THE FIRST RE-SUBMITTAL.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GARAGE DOOR THAT MEETS THE ENGINEER CALCULATED
 DESIGN PRESSURES. (REPEAT COMMENT. NO INFORMATION WAS
 SUBMITTED).
  
 B) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE 2 COPIES OF EVERYTHING. PROVIDE
 ONLY THE COPY OF FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTORS. (REPEAT COMMENT). ONLY
 ONE COPY OF A LIST OF FL NUMBERS FOR SIMPSON CONNECTORS
 WAS PROVIDED. INFORMATION FOR USP CONNECTORS WAS NOT
 PROVIDED.
  
 C) STORM SHUTTERS. PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. AND, CLEARLY MARK ON
 SHUTTER DRAWINGS SPECIFIC MOUNTING CONDITIONS. EG: WALL
 MOUNTED CONDITION OR BUILT OUT CONDITION. ALSO, MARK ON
 SHUTTERS DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, CONNECTION TYPE, PANEL SPAN AND STRUCTURE TO
 BE ATTACHED TO. (REPEAT COMMENT). SEE PAGE 5 AND 6 OF
 SHUTTERS DRAWINGS AND CIRCLE PROPER INFORMATION. SEC.
 106.1.2 CITY AMAMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH DESIGN PRESSURES OF SEC. R301 2004
 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE:
 PRODUCT APPROVAL SUBMITTED FOR SWING DOOR REQUIRES
 PROTECTION FOR GLASS. TAKE THIS OPENING INTO
 CONSIDERATION FOR STORM SHUTTERS INSTALLATION
 SCHEDULE.
  
 D) ROOF SHINGLES. NONE SUBMITTED THIS TIME.
  
 E) PRECAST LINTELS. NONE SUBMITTED THIS TIME.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- PROVIDE STRUCTURAL BUCK DETAIL USING 2X BUCK AS
 REQUIRED BY PRODUCT APPROVAL SUBMITTED.
 ***NOTE: REVISE DOOR BUCK DETAIL TO PROVIDE DOOR FRAME
 FULL SUPPORT AS REQUIRED BY SEC. SEE SIZE OF DOOR FRAME
 IN DOOR PRODUCT APPROVAL SO CORRECT BUCK SIZE CAN BE
 SPECIFIED.
  
 6- SHEET A1:
 A) INFORMATION SHOWN ON DIAPHRAGM SCHEDULE FOR ROOF
 SHEATHING AND INFORMATION ON EXT. C.M.U. WALL ON SHEET
 A2 DOESN'T MATCH. REVISE THICKNESS AND ANCHOR TYPE AND
 SPACING TO MATCH.. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM TYPE AND NAILING SPACING
 REQUIRED AT ROOF ZONE #3.
  
 B) REVISE WIND PRESSURE ZONES ROOF DIAGRAM. ONE CORNER
 SHOWS CORNER "A" ZONE AS 4'-0" , WHILE THE OTHER CORNER
 SHOWS "A" ZONE AS 5'-0". REVISE AS REQUIRED.
  
 C) REVISE ROOF COVERING REFERENCE CITED IN THE WIND
 PRESSURE ZONES ROOF DIAGRAM. CORRECT CODE TO CITE IS
 THE 2004 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED.
 REFERENCE THIS CODE AND THE SPECIFIC SECTION.
  
 D) PROVIDE SECTION/DETAIL SHOWING HOW ARE THE TWO TRUSS
 CONNECTORS INSTALLED ON EACH TRUSS AS SPECIFIED ON ROOF
 FRAMING PLAN. (EG: SIMPSON MGT WITH USP LPTA AND
 SIMPSON HHETA-20 WITH USP LPTA). SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 CALCULATED UPLIFT LOADS AND LATERAL LOADS OF SEC.
 R301.
 ***NOTE: ONE CONNECTOR MAY INTERFERE WITH THE OTHER FOR
 PROPER INSTALLATION.
  
 E) SEE CURRENT SIMPSON CATALOG AND REVISE CONNECTOR
 HETA20 FASTENER NUMBER AND UPLIFT LOADS. (REPEAT
 COMMENT).
  
 F) REVISE CODE INFORMATION LOCATED AT BOTTOM OF PAGE.
 THE CURRENT REVISIONS ARE THE 2007 REVISIONS, NOT 2006.
  
 G) CODE INFORMATION SPECIFIED THIS CONSTRUCTION TO BE
 TYPE 3-B. TYPE 3-B IS FOR 2 HOUR FIRE RATED CONCRETE
 BLOCK. PROVIDE COMPLETE SPECIFICATIONS FOR TWO HOUR
 CONCRETE BLOCK OR REVISE CONSTRUCTION TYPE AS REQUIRED.
 TYPICALLY RESIDENTIAL STRUCTURES ARE SPECIFIED AS
 CONSTRUCTION TYPE V-B. REVISE AS REQUIRED.
  
 7- COORDINATE WITH ZONING REGARDING THE CONSTRUCTION OF
 PRIVACY WALL. THIS IS DONE UNDER A SEPARATE PERMIT.
 (REPEAT COMMENT).
  
 8- SPECIFY ATTIC ACCESS AND LOCATION AS REQUIRED BY
 SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By jgomez Date 2008-03-06 Time 13:42 Rev Time 0.00
Received By jgomez Date 2008-03-06 Time 13:42 Sent To PC
Notes
2008-03-06 14:34:02RESIDENTIAL GARAGE ADDITION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE DONE AT A LATER TIME AT TIME OF
 PERMIT PICK TO AVOID EXPIRATION OF DOCUMENT.
  
 2-OWES $146.78.PERMIT VALUATION WAS UPDATEDTO
 $13,505AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SWING DOOR AS SHOWN ON PLANS.
 ***NOTE: MAKE SURE PRODUCT APPROVAL HAS DOOR THAT
 RESISTSTHE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER.
  
 B) GARAGE DOOR:
 * NEED PRODUCT APPROVAL FOR GARAGE DOORTHAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER. PRODUCT
 APPROVAL SUBMITTED DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 ** FLORIDA PRODUCT APPROVALFL 4913 AND NOA 03-0507.08
 DON'T CORRESPOND TO EACH OTHER.PROVIDE COMPLETE
 PRODUCT APPROVAL EITHER FROM THE FLORIDA WEBSITE OR
 COMPLETE NOA THAT MEETS THE CALCULATED DESIGN
 PRESSURES.
  
 C) SINGLE HUNG WINDOWS. NOA02-0507.06 EXPIRED ON
 11/14/2007. NEED TO PROVIDECURRENT NOA.
  
 NOTE: FL239-R10 AND NOA 02-0507.06 DON'T CORRESPOND TO
 EACH OTHER. PROVIDECOMPLETE INFORMATION FOR EITHER
 ONE.
  
 D) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
 NOTE: PROVIDE ONLY THE COVER PAGE AND PAGE WHERE
 CONNECTOR IS SHOWN.
  
 E) STORM SHUTTERS (SINCE SINGLE HUNG WINDOW HAS NOT
 IMPACT GLASS).
 NOTE:CLEARLY MARK ON PRODUCT APPROVAL SPECIFIC
 MOUNTING CONDITIONS (EG: WALL MOUNTED) AND CONNECTOR
 TYPE AND SPACING TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN AND STRUCTURE TO
 BE ATTACHED TO (CONCRETE BLOCK). SEE INSTALLATION
 SCHEDULES ON INSIDE OF STORM SHUTTERS DRAWINGS AND MARK
 CORRESPONDING INFORMATION.
  
 4- SHEET A1:
 A) WIND PRESSURES ZONESROOF DIAGRAM DOESN'T
 CORRESPOND THE TYPE OF ROOF SHOWN. REVISE AS REQUIRED.
 SEE SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE AND
 REVISE AS REQUIRED.
 ALSO, REVISE REFERENCED SECTION OF CODE. SEE 2004
 FLORIDA RESIDENTIAL CODE FOR CORRECT SECTIONS TO BE
 CITED.
  
 B) SPECIFY ROOF SHEATHING NAILING AS REQUIRED BY
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 NOTE: MAKE SURE ALL ROOF NAILING ZONES ARE IDENTIFIED
 WITH RESPECTIVE NAILING SIZE, TYPE AND SPACING.
  
 C) WHERE IS FASTENER SCHEDULE INFORMATION TAKEN
 FROM.SEE CURRENT SIMPSON CATALOG AND REVISE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCEWITH SEC. R301.
  
 ALSO, CLARIFY WHYTHE LATERAL LOADS ARE NEG'L AND WHAT
 IT STANDS FOR?. SEC. 106.1.2 CITY AMENDMENT STO FBC
 2004 TO VERIFY COMPLIANCE WITH DESIGN LOADS OF SEC.
 R301.
  
 D) BUILDING INFORMATION AT BOTTOM OF PAGE:
 * BULDING WIDTH IS INCORRECT.
 ** BUILDING LENGTH IS INCORRECT.
 *** ROOF SLOPE IS INCORRECT.
 **** DESIGN PRESSURES FOR WINDOW DOESN'T MATCH DESIGN
 PRESSURES SHOWN ON DOOR AND WINDOW SCHEDULE. REVISE AS
 REQUIRED.
 *****PROVIDE CALCULATIONS FORCALCULATED DESIGN
 PRESSURES AT ALL DOORS AND WINDOWS TO VERIFY COMPLIANCE
 WITH THE SPECIFIED BUILDING EXPOSURE C.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301.
  
 E) REVISE DOOR BUCK DETAIL.2X4 PT WOOD BUCK IS NOT
 ADEQUATE TO PROVIDE FRAME FULL SUPPORT AS REQUIRED BY
 SEC. R613.6 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET A2:
 A) EXT. C.M.U. WALL SECTION:
 * SPECIFY WHEREIS THE INFORMATION FOR 7/16" O.S.B.
 ROOF SHEATHIHNG INFORMATION TAKEN FROM TO VERIFY
 COMPLIANCE WITH PROPOSED INSTALLATION AND SEC. R301 AND
 R803 OF 2004 FLORIDA RESIDENTIAL CODE.
 ** FOOTING DOESN'T MATCH FOOTING TYPE SHWON ON FOOTING
 SCHEDULE.
 *** ACCORDING TOTHIS DETAIL THE FOOTING IS 12" ABOVE
 GRADE AND 4" BELOWGRADE SINCE FOOTING SCHEDULE CALLS
 FOR 16" DEEP FOOTING.REVISE AS REQUIRED TO COMPLY
 WITH SEC. R403.1.4 OF 2004 FLORIDA RESIDENTAIL CODE.
 NEED TO SHOW MINIMUM FOOTING EMBEDMENT BELOW GRADE AND
 FOOTING ABOVE GRADE.
 **** SPECIFY R-VALUE FOR INSULATION SPECIFIED FOR THE
 WALL.
  
 B) COORDINATE WITH ZONING REGARDING CONSTRUCTION OF
 PRIVACY WALL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By btrobaug Date 2008-11-04 Time 12:23 Rev Time 0.00
Received By btrobaug Date 2008-11-04 Time 12:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-14 Cont ID  
Sent By btrobaug Date 2008-04-14 Time 11:41 Rev Time 0.00
Received By btrobaug Date 2008-04-14 Time 11:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By btrobaug Date 2008-02-29 Time 07:11 Rev Time 0.00
Received By btrobaug Date 2008-02-29 Time 07:05 Sent To Z
Notes
2008-02-29 07:11:14 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 INDICATE COMPLIANCE WITH THE FOLLOWING:
  
 1} 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE
 BUILDING OR STRUCTURE.
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-29 Cont ID  
Sent By adarroug Date 2008-10-29 Time 11:04 Rev Time 0.00
Received By adarroug Date 2008-10-29 Time 11:04 Sent To Z
Notes
2008-10-29 11:05:13TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 09:03 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 09:03 Sent To Z
Notes
2008-04-11 09:03:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-06 Cont ID  
Sent By jgomez Date 2008-03-06 Time 14:34 Rev Time 0.00
Received By jgomez Date 2008-02-28 Time 14:33 Sent To  
Notes
2008-02-28 14:33:43TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 13:54 Rev Time 0.20
Received By tgordon Date 2008-03-03 Time 13:54 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-11-02 Cont ID  
Sent By mcruz Date 2008-11-02 Time 10:39 Rev Time 0.00
Received By mcruz Date 2008-11-02 Time 10:31 Sent To E
Notes
2008-11-02 10:39:08***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM
 THE PRPOSED GARAGE TO ALL ADJACENT PROPERTY LINES.
 NOTE: PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-304(B)(2): SETBACKS FOR ACCESSORY STRUCTURES IN
 RESIDENTIAL DISTRICTS ARE AS FOLLOWS:
  
 FRONT: 25 FEET.
  
 SIDE: FIVE FEET FROM THE LOT LINES.
  
 REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE
 OF THE ALLEY TO A GARAGE DOOR FACING THE ALLEY,
 WHICHEVER IS GREATER.
  
 3. INDICATE THE SEPARATION DISTANCE OF THE PROPOSED
 GARAGE TO THE PRINCIPAL STRUCTURE. NOTE: PURSUANT TO
 THE ZLDR, SECTION 94-304(B)(3): ACCESSORY STRUCTURES
 SHALL BE LOCATED NO CLOSER THAN SIX (6) FEET TO THE
 PRINCIPAL STRUCTURE.
  
 4. INDICATE THE HEIGHT OF THE PROPOSED GARAGE. PURSUANT
 TO THE ZLDR, SECTION 94-304(B)(4): HEIGHT. ACCESSORY
 STRUCTURES SHALL NOT EXCEED 25 FEET.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-14 Cont ID  
Sent By choops Date 2008-04-14 Time 09:18 Rev Time 0.00
Received By choops Date 2008-04-14 Time 09:18 Sent To E
Notes
2008-04-14 09:20:35***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY.
  
  
 NEW COMMENT:
  
 1)AS THE SCOPE OF WORK FOR THIS PERMIT APPLICATION
 DOES NOT INCLUDE THE SHOWN CONCRETE PRIVACY WALL, IT
 SHALL EITHER BE REMOVED FROM THIS SET OF PLANS OR
 LABELED "PERMITTED SEPARATELY"
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By choops Date 2008-02-29 Time 11:28 Rev Time 0.00
Received By choops Date 2008-02-29 Time 11:28 Sent To M
Notes
2008-02-29 11:29:38***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY.
  
 2)INDICATE HEIGHT OF PROPOSED ACCESSORY GARAGE,
 MEASURED FROM GRADE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "M" - SF RACK