Plan Review Details - Permit 08020675
| Plan Review Stops For Permit 08020675 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-03-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-03-19 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-03-19 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-03-07 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-03-07 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-03-07 11:13:26 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED | | | | | | 1)PROVIDE BUCK FASTENING DETAILS. SPECIFY THE SPACING | | | AND EMBED DEPTH OF THE TAPCONS THAT WILL BE USED TO | | | ATTACH THE 2X WOOD BUCKS. | | | | | | 2) SUBMIT (2) TWO COPIES OF PRODUCT APPROVALS FOR STORM | | | PANELS THAT ARE REQUIRED FOR THE NEW FRENCH DOORS. FAC | | | RULE 9B-72 AND R301.2.1.2. | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | NEW FRENCH DOORS REQUIRE THE DOORS TO HAVE IMPACT | | | PROTECTION. SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR | | | THE STORM PANELS THAT WILL BE INSTALLED. SPECIFY THE | | | MOUNT TYPE, FASTENER TYPE AND SPACING BY CIRCLING THE | | | ONES THAT WILL BE USED ON THE PRODUCT APPROVAL. | | | | | | 4)THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN IS REQUIRED ON THE DRAWINGS. FBC | | | 106.1.3* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-02-29 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-02-29 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-02-29 13:05:27 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED | | | | | | 1) THE SCOPE OF WORK ON THE APPLICATION STATES THAT THE | | | EXISTING BEDROOM WINDOW IS BEING REPLACED BY FRENCH | | | DOORS. SUBMIT STRUCTURAL DETAILS FOR THE OPENING. | | | SPECIFY THE EXISTING OPENING SIZE AND THE NEW OPENING | | | SIZE. IF CBS CONSTRUCTION SHOW LOCATION AND SIZE OF | | | STEEL REINFORCING, BLOCK LINTEL AND TIE BEAM. IF WOOD | | | FRAME SHOW HEADER SIZE, FRAMING DETAILS, HURRICANE | | | STRAPPING. | | | | | | 2)PROVIDE BUCK FASTENING DETAILS. | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR STORM PANELS THAT ARE | | | REQUIRED FOR THE NEW FRENCH DOORS. FAC RULE 9B-72 AND | | | R301.2.1.2. | | | | | | 4) THE VALUE OF THE WORK ($200) IS TOO LOW. THE VALUE | | | IS TO INCLUDE THE COST OF MATERIALS AND LABOR AS WOULD | | | BE CHARGED BY A CONTRACTOR. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-06 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-06 |
Time |
12:21 |
Sent To |
B |
|
| Notes |
| 2008-03-06 12:21:24 | TO "RMCDOUGAL" DESK/RESUB |
|
|
|