| 2008-04-01 12:08:45 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 2.PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3, AREA PER OCCUPANCY, |
| | OCCUPANT LOAD. |
| | |
| | AT A MINIMUM, PLEASE PROVIDE INFORMATION REGARDING USE |
| | OF SPACE ON EACH FLOOR AND TOTAL SQUARE FOOT AREA FOR |
| | EACH FLOOR.USE IS TO BE SPECIFIC; ARE ALL OF THESE |
| | ROOMS CLASSROOMS, WHAT AGE ARE THE STUDENTS?SPRINKLER |
| | INFORMATION REQUIRED.IF THE CORRIDORS ARE FIRE RATED, |
| | IT IS POSSIBLE THAT ONLY FIRE RATED DOORS ARE |
| | PERMITTED.PRIOR TO A REVIEW, ALL INFORMATION |
| | REQUESTED MUST BE PROVIDED TO DETERMINE CODE |
| | REQUIREMENTS OR ENOUGH INFORMATION FOR ME TO DISCERN |
| | THE ABOVE INFORMATION. |
| | |
| | 3.PROVIDE DIMENSIONS OF CORRIDORS. |
| | |
| | YOU CANNOT REDUCE THE MEANS OF EGRESS WITH DOOR SWING |
| | BY MORE THAN HALF.DIMENSION OF DOORS, OCCUPANT LOAD, |
| | AND CORRIDOR DIMENSION REQUIRED.FBC1005.4. |
| | |
| | 4.THE PROPOSED EGRESS DOORS ARE OBSTRUCTED BY OTHER |
| | DOORS.SEE FBC1003.6. |
| | |
| | 5.SEE FBC1004.1 .NOTE THAT YOU PROPOSE TO REDUCE |
| | THE CLEAR WIDTH OF A COMPONENT OF MEANS OF EGRESS. CODE |
| | COMPLIANCE MUST BE DEMONSTRATED. |
| | |
| | PLEASE PROVIDE DOOR DIMENSIONS.THEY ARE SHOWN |
| | GRAPHICALLY ON THE PLAN AS MUCH SMALLER THAN OTHER |
| | DOORS.ONLY ONE DIMENSION IS PROVIDED.IS THIS THE |
| | DOOR DIMENSION, OR THE CORRIDOR DIMENSION? |
| | |